Trinity
│
Installation and Operation Instructions
Tx Series
10
4.0 GENERAL VENTING
The Trinity Tx is certified as a “Category IV” boiler requiring a “Special Venting System” designed for
pressurized venting. The Exhaust Vent must be piped to the outdoors, using the vent materials and rules outlined
in this section. Under no conditions may this unit vent gases into a masonry chimney, unless it is vacant, and
utilizes the approved venting material and rules described in this section.
Vent and Air-inlet are to be piped separately. The Trinity Tx cannot share a common vent
or air-inlet with multiple boilers.
Failure to comply will result in serious injury or death.
Direct Vent Installation (Best Practice)
When installed as a Direct Vent boiler the combustion air-inlet must also be piped directly to the outdoors using
the methods described in this section and in accordance with the National Fuel Gas Code, ANSI Z223.1 (U.S.) or
CSA B149.1 (Canada) and local requirements.
Installation Using Indoor Combustion Air
When the installation uses Indoor Combustion Air (i.e. piping is not directly connecting the appliance air-inlet
fitting to the outdoors), the combustion air-inlet is drawn from Indoors or Outdoors via the appliance area using
the methods described in this section and in accordance with the National Fuel Gas Code, ANSI Z223.1 (U.S.) or
CSA B149.1 (Canada) and local requirements.
The boiler shall be located so as not to interfere with proper circulation of combustion,
ventilation, and dilution air.
Make up air requirements for the operation of exhaust fans, kitchen ventilation systems,
clothes dryers, and fireplaces shall be considered in determining the adequacy of a space
to provide combustion air requirements. Failure to ensure adequate make up air to all
appliances may result in personal injury or death.
Indoor Combustion Air - Opening Size and Location:
The methods detailed below for determining Opening
Size and Location for accessing indoor combustion air, shall be used when the air infiltration rate is adequate, i.e.
greater than 0.4 ACH (air changes per hour) and when the boiler area and communicating spaces have a
minimum volume of 50 cubic ft per 1000 Btu/hr. If the air infiltration rate is known to be less that 0.4 ACH,
refer to the National Fuel Gas Code for further guidance.
1.
Combined spaces on the same story
– Each opening shall have a minimum free area of 1 in.
2
/1000 Btu/hr
of the total input rating of all appliances in the space, but not less than 100 in.
2
. One opening shall
commence within 12 in. of the top, and one opening shall commence within 12 in. of the bottom, of the
enclosure, see Figure 4-1a. The minimum dimension of air openings shall be not less than 3in.
2.
Combined spaces in different stories
– The volumes of spaces in different stories shall be considered as
communicating spaces where such spaces are connected by one or more openings in doors or floors having a
total minimum free area of 2 in.
2
/1000 Btu/hr of total input rating of all appliances.
Outdoor Combustion Air – Opening Size and Location:
Outdoor combustion air shall be provided through
opening(s) to the outdoors in accordance with the methods detailed below. The minimum dimension of air
openings shall not be less than 3in.
1.
Two Permanent Openings Method
– Two permanent openings, one commencing within 12in. of the top,
and one commencing within 12in. of the bottom of the enclosure, shall be provided. The openings shall
communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors, as
follows:
a.
Where communicating with the outdoors or where communicating to the outdoors through vertical ducts,
each opening shall have a minimum free area of 1 in.
2
/4000 Btu/hr of total input rating of all appliances
in the enclosure; see Figures 4-1b and 4-1c.
b.
Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum
free area of 1 in.
2
/2000 Btu/hr of total input rating of all appliances in the enclosure; see Figure 4-1d.