Page
3
of
29
1
INSTALLATION
Locating the Fan Coil
1.1
Clean the floor of debris where the fan coil is to be placed. With the fan coil tipped at the
top, feed the risers down to the unit below through the sleeves provided. Solder the
mating risers and insulate the remaining copper on the supply and return water risers.
Shim the fan coil plumb and level if necessary.
Framing
1.2
Using nominal 2” studs, frame around the fan coil rough-in flange on the left, right, top
and bottom as shown below.
Electrical Power Connection
1.3
Supply the fan coil with 120VAC terminating at the junction box provided inside the
unit. The table below outlines the breaker sizes needed.