Page
5
of
29
HRV Outside Air (Fresh Air from Outside)
1.6.5
At the top, right, front of the fan coil a 5” diameter collar is provided. The outside air
collar can be specified when ordering to be top or side and can be changed in the field by
swapping the cover plate and collar plate.
2
COMMISSIONING
Supply Air Balancing
2.1
The supply air motor is an ECM operating in constant cfm mode. Adding static will not
significantly reduce the total air flow as you would expect with a psc motor. On ducted
systems the amount of air at each grille can be regulated with dampers.
HRV Balancing
2.2
The HRV
exhaust air
can be adjusted in low and high speed using the control board and
the procedure that follows. The amount of outside air is adjusted using dampers. The
damper in the return air grille can be closed (partially) to increase outside air flow or
opened to decrease outside air flow. If outside air needs to be further reduced, a sliding
damper located in the HRV outside air compartment should be used.
When balancing the HRV:
-Close all windows, doors and
fireplace dampers.
-Turn off any exhaust systems
such as bathroom fans, range
hoods, central vacuums or
dryers.
There are three modes of
operation in which the HRV
needs to be balanced.
1) High speed (High ventilation
switch).
2) Low speed (thermostat fan
ON, no heat or cool calls).
3) Low ventilation with a call for heat or cooling.
Balancing Sequence:
High Speed Balancing – set supply and exhaust to the specified flows
Low speed balancing – Fan On. Reduce the higher flow to match the lower
Low speed with heat/cool call on – using the throttling damper, match the outside air
flow to that of the exhaust air.
Exhaust air
measuring
port
Fresh Air
measuring
port
Summary of Contents for Enerboss 400C Series
Page 20: ...Page 20 of 29...
Page 21: ...Page 21 of 29...
Page 22: ...Page 22 of 29...
Page 23: ...Page 23 of 29...
Page 24: ...Page 24 of 29...
Page 26: ...Page 26 of 29...
Page 27: ...Page 27 of 29...
Page 29: ...Page 29 of 29 400C Fan Coil...