Rev 2.3 July 17, 2017
23
12
Troubleshooting
SYMPTOM
EXPLANATION
ANSWER
Frosting up of HRV and/or
Duct(s).
HRV air flows incorrectly balanced.
HRV defrost system is not working.
Balance HRV.
Install dampers.
Check defrost system.
Note minimal frost build up is expected
on cores before unit initiates defrost
cycle function.
Supply air feels cool.
HRV air flows incorrectly balanced.
Improper location of supply grills.
Velocity of air is too high.
Extremely cold outside temperatures.
Heating coil is not working.
Balance HRV.
Locate grills high on walls or in ceiling.
Adjust diffusers, resize duct.
Add a duct heater.
Call your service contractor.
Outside duct has ice build-up or
condensation.
Improperly installed vapour barrier
around insulated duct.
Tape all joints.
Ensure the vapour barrier is completely
sealed and insulated.
Water in the bottom of HRV.
Drain pans are plugged.
Incorrect connections of HRV drain
lines.
HRV is not level.
Drain lines plugged.
HRV heat exchange core improperly
installed.
Look for kinks in the line.
Check water drain connections.
Ensure that water drains from pan.
Poor air flow(s).
HRV incorrectly balanced.
Filters need to be cleaned.
Hoods needs to be cleaned.
Grills are closed.
Inline dampers are closed.
Low power supply.
Wrong size ducting.
Under-sized HRV.
HRV is not working.
Tape all joints.
Use proper airflow measuring
equipment.
Open grills.
Remove obstructions in duct(s),
hoods(s), and grill(s).
Balance airflow.
Clean filter.
Have a professional look at the system.
Humidity levels too low.
HRV air flows incorrectly balanced.
Dehumidistat control set too low.
Balance Air Flow(s).
Increase Dehumidistat.
Humidifiers may need to be added.
Humidity levels too high.
HRV air flows
incorrectly balanced.
HRV undersized.
High humidity areas not ventilated
properly.
Dehumidistat is not working.
Balance airflow.
Set dehumidistat.
Dehumidistat is not working.
Incorrect connection of outside low
voltage wiring between HRV and
Dehumidistat.
Check outside wiring for short.
Check wall switch for correct
connection.
Check wires are connected to proper
terminals at the HRV.
Summary of Contents for NU0103
Page 25: ...Rev 2 3 July 17 2017 25...
Page 26: ...Rev 2 3 July 17 2017 26...
Page 27: ...Rev 2 3 July 17 2017 27...
Page 28: ...Rev 2 3 July 17 2017 28...
Page 29: ...Rev 2 3 July 17 2017 29...
Page 30: ...Rev 2 3 July 17 2017 30...
Page 31: ...Rev 2 3 July 17 2017 31...
Page 32: ...Rev 2 3 July 17 2017 32...
Page 33: ...Rev 2 3 July 17 2017 33...
Page 34: ...Rev 2 3 July 17 2017 34...
Page 35: ...Rev 2 3 July 17 2017 35...
Page 36: ...Rev 2 3 July 17 2017 36...
Page 37: ...Rev 2 3 July 17 2017 37...
Page 38: ...Rev 2 3 July 17 2017 38...