background image

Page 11

NOL 18-100 HL

Establish that the operation of plant other

than that being commissioned will not have

an adverse effect on the operation of the

plant to be commissioned and similarly, that

the operation of the plant to be

commissioned will not have and adverse

effect on other plant.
Confirm that the operation of adjacent plant

and machinery will not constitute a hazard

to the personnel involved in commissioning.

Pre-firing Checks

With the oil and power switched off, carry out the

following checks.

Check the nozzle size and position relative

to the diffuser plate. (The burner head

dimensional details are given on page 17).

Check that the electrode positions and H.T.

leads are correct.

Check the fan motor overload settings.

If the appliance is a boiler, check that the

water level is correct, the controlling valves

are open and that the water pumps are in

working order.

If a flue damper is fitted, check that it is

correctly interlocked to the burner or fixed

in the fully open position.

Ensure that there is a good oil supply to the

burner pump. Bleed one or two gallons from

the flexible to eliminate any pipe scale and

air from the system.

Check that the oil supply is of the

recommended temperature and pressure.

For single pipe systems bleed the burner

pump manually by opening a pressure port

until air-free oil flows. With two pipe

operation bleeding is automatic.

Switch on the electricity supply to the burner.

Switch on the burner at the control panel.

The hydraulic ram will remain in the low fire

position during the pre-purge period.

Allow the fan motor to run up to speed,

switch off the burner and check the fan

rotation (Anticlockwise as viewed from the

motor side) as the fan slows down.

Remove and cover the photoelectric cell with

a clean lint free cloth, switch on the burner,

and allow it to run through to lockout.

During this run check that the ignition spark

is occurring, and note oil pressures at the

moment of ignition. Reset the sequence

control and repeat the run if necessary to

check these functions. If necessary, adjust the

pump to the required pressure and recheck.

Replace the photoelectric cell.

THE BURNER IS NOW READY TO BE

COMMISSIONED.

Commissioning the Burner

Open the low flame hold switch (LFC) or

temporarily disconnect the live feed to the

H/L thermostat from its connection in the

burner terminal block.

Switch on the burner, the hydraulic ram will

remain in the low fire position during the pre-

purge period (approx. 30 Seconds).

The burner should light in the low fire

position. If ignition is not achieved refer to

the fault finding section at the rear of the

handbook

Check the flame visually. If the flame is dirty,

adjust the low fire stop until the flame

becomes clean.

Allow the burner to run until the system is at

normal operating temperature. Turn off the

burner, the flame should go out immediately

and the pressure gauge drop to, or just

above, zero.

Switch off the electricity supply and close the

low flame hold switch. Restart the burner and

allow the burner to change to high flame.

Adjust the high flame stop until the  damper

is sufficiently open to give clean combustion.

 Check the oil consumption. If this is not

correct for the full burner rating then further

adjustments to the fuel pressure and the high

flame stop will be required.

Switch the burner back to the low flame

position. The oil consumption rate should

now be up to 50% of the rated maximum.

The burner can now be switched between

the high and low position whilst measuring

the flue gas composition. Adjust the

combustion air volume as necessary to give

a high flame CO

2

 should be within 11% and

12% and the low flame about 1% lower than

these figures.

Summary of Contents for NOL100-38

Page 1: ...stallation Maintenance Manual Series NOL forced draught oil burner Models NOL18 to 100 38 High Low Oil Burner 11 12 Tel 44 0 1905 794331 Fax 44 0 1905 794017 Email info nu way co uk Web www nu way co...

Page 2: ...himney Requirements 6 Plant Room Ventilation 6 Existing Appliances 6 Combustion Chamber Conditions 6 INSTALLATION 6 General 6 Fitting to the Appliance 6 Oil Supply Connections 6 Electrical Power Conne...

Page 3: ...ely should comply with EN267 oil burners or EN676 gas burners and EN303 1 boiler bodies Burner adjustments must be made in accordance with boiler manufactures instructions and these must include flue...

Page 4: ...335 265 400 254 305 NOL50 38 721 465 480 250 340 295 475 254 305 NOL60 28 674 440 457 250 335 265 400 254 305 NOL60 34 674 440 480 250 335 265 400 254 305 NOL60 38 721 465 480 250 340 295 475 254 305...

Page 5: ...orrect installation and use Pre commissioning and Live Run are described and the location of necessary controls and adjustments to undertake these are illustrated and supported by appropriate tabular...

Page 6: ...ance which can be maintained over extended periods of operation leading to optimal appliance thermal efficiency and reduced running costs This high specification ensures low level emission of pollutan...

Page 7: ...SCRIPTION ITEM DESCRIPTION F2 Appliance Limit Instrument P1 Burner Operating Hours Run Counter H1 Burner Fault Signal HL High Low Instrument H2 Burner Operating Signal LO Remote Lockout Signal N1 Appl...

Page 8: ...d 0 25 mbar Should the over fire draught exceed this figure then steps should be taken to reduce it to this level INSTALLATION General Check that the burner is appropriate for the appliance rating Det...

Page 9: ...orizontally controlled by two magnetic valves The right hand nozzle looking from the rear of the burner sprays only on low flame whilst both nozzles spray together on high flame Hydraulic Oil Ram Adju...

Page 10: ...appliance or of any instrument machine or service in the vicinity of the burner the OIL AND ELECTRICITY SUPPLIES SHALL BE ISOLATED IMMEDIATELY and they shall remain isolated until the fault has been i...

Page 11: ...otoelectric cell with a clean lint free cloth switch on the burner and allow it to run through to lockout During this run check that the ignition spark is occurring and note oil pressures at the momen...

Page 12: ...manufacturer The burner should be kept clean inside and out It will be more reliable and if an oil leak occurs it will be spotted more readily Inspect the burner regularly to check if there is any var...

Page 13: ...out No ignition Fuel supply problem Solenoid valve defective YELLOW WITH FLAME End Lockout Photo cell dirty Photo cell or circuit faulty No voltage at terminal 20 FLAME FAILURE SEQUENCE CONTROL Variou...

Page 14: ...T INDICATION LAL1 25 In the event of fault conditions the sequence switch stops and simultaneously the lockout indicator The symbol appearing above the reading mark indicates the kind of fault encount...

Page 15: ...nsure correct expedition of your order Nu way Ltd is able to offer on site Commissioning Service and Repair through its worldwide network of authorised distributors and sales offices Please contact th...

Page 16: ...ng resistance The appliance starting resistance is derived from a combination of the combustion chamber shape volume start rate and flue conditions It may be necessary to select a burner with a higher...

Page 17: ...Page 17 NOL 18 100 HL BURNER PERFORMANCE CURVES Burner outputs are based on a gross calorific value of class D fuel of 12 66 kW Kg Graphs produced in accordance with BS EN 267...

Page 18: ...l Nozzles BURNER A B C D BURNER A B C D NOL18 34 178 165 152 165 NOL50 34 220 197 178 206 NOL18 38 178 165 152 165 NOL50 38 220 197 178 206 NOL30 25 178 165 152 NONE NOL60 28 220 206 178 NONE NOL35 25...

Page 19: ...800 15 3 6 1 8 2 8 1 5 NOL35 25 1 1 2800 15 3 6 1 8 2 8 1 5 NOL35 34 2 2 2800 25 4 6 4 6 2 1 5 NOL35 38 3 0 2800 35 6 1 6 9 2 1 5 NOL50 28 2 2 2800 25 4 6 4 6 2 1 5 NOL50 34 3 0 2800 35 6 1 6 9 2 1 5...

Page 20: ...oke Hood Fan Static mbar mm Oil Temperature C Oil Pressure Atomising bar bar Return Pressure bar Oil Throughput cal metre Boiler Temperature Pressure Boiler Starting Resistance mbar mm Air Control Set...

Page 21: ...NOL 18 100 HL BURNER SERVICE RECORD The details below are to be completed by the Servicing Engineer This sheet to be completed and signed following each service adjustment Date Details Of Service Sig...

Page 22: ...NOL 18 100 HL Page 22 NOTES...

Page 23: ...Page 23 NOL 18 100 HL...

Page 24: ...Enertech Limited P O Box 1 Vines Lane Droitwich Worcestershire WR9 8NA Tel 44 0 1905 794331 Fax 44 0 1905 794017 Email info nu way co uk Web www nu way co uk...

Reviews: