1.0 Introduction

The Nuaire Short Cased Axial Fan range is produced 

in a range of sizes from 250mm to 1600mm diameter.

Cases are manufactured from various materials such 

as pre-galvanised steel, stainless steel or hot dipped 

galvanised steel. Impellers are selected to meet the specific 

performance and are available in a variety of materials to

ensure suitability for the application. 

Units are available for single and three phase supply.

2.0 Handling and Storage

The fan impeller is carefully balanced prior to despatch

and great care must be exercised when handling the unit. 

This will ensure that the case is not damaged or distorted,

causing the impeller to foul against the casing. The fan

should be stored on a flat surface and the impeller rotated

at regular intervals.

3.0 Installation 

Installation must be carried out by competent 

personnel in accordance with good industry practice,

the appropriate authority and in conformance with all

statutory and governing regulations.

,

Prior to installation the impeller should be rotated by hand

 

to ensure free and smooth rotation and that no transit or

 

handling damage has occurred.

General advice

Ensure that impeller and motor are free from obstruction

 

and that all optional accessories such as guards and bell

 

mouths are securely fastened before commencing unit 

start up.

When operating at low temperatures, ice formation can

 

occur, and suitable prevention should be adopted to avoid

 

ice build up.

Motors

In  general motors are totally enclosed, protected to IP55 

(Dust and low pressure water jets) and have an integral 

terminal box. Motors may incorporate drain holes to allow

 

any condensation to escape from the motor casing.

 

It is 

essential that drain hole plugs positioned at the lowest 
point of the motor are removed to allow condensate to 
drain out of the motor. For vertical applications an 
optional capillary drain plug is advised.

All bearings are pre-packed with grease and sealed for life

 

requiring no further lubrication.

Connection Details

Electrical connections are made directly to the motor 

terminal box as standard. Check that the voltage on the fan 

rating label is suitable for your supply. Full load and

 

starting currents are also indicated. 

Motors below 4kW are designed for Direct On Line starting

 

whilst 4kW and above are suitable for Direct On Line or

 

Star/Delta starting.

Start Up Procedure

On start up ensure the impeller rotation follows the arrow

 

indicator on the fan casing. Should the direction be 

incorrect on a three phase unit reverse any two of the 

supply leads.

Single phase rotational direction is set at the factory and

 

should not be altered. Equipment should be run for 

approximately 30 minutes to ensure correct operatIon. 

If any fault occurs the equipment should be switched off 

and not re-started until the fault has been rectified.

Reversing Fans

If the unit is specified as ‘reversing fan’ care must be taken

 

when designing the control gear to ensure that enough time 

is allowed for the fan impeller to come to a standstill before

 

switching to the opposite rotation.

Any damages or deviations should be immediately 

reported to Nuaire quoting the order/Arc number and

product details, detailed on the product rating label.

AXUS

Circular Short Cased Axial Flow Fans

Installation and Maintenance

Figure 1. Correct method 

of lifting/removing from 

a pallet. 

Figure 2. Moving/positioning

unit to application using a

spreader.

The EMC Directive 

2014/30/EU  

The Low Voltage 

directive 

2014/35/EU