If motor overheat protection is specified, terminals 

T1 and T2 must be connected to the fan control circuit. 

Failure to do this will invalidate the warranty.

5.0 Wiring Connections for Motor

Installation and Maintenance

AXUS Circular Short Cased Axial Flow Fans

2

19. 10. 16. Leaflet Number 671351

Single phase.

Three phase - up to and including 3kW.

Three phase - 4kW and above.

Important. 

T1 and T2 = Thermistor connections

H1 and H2 = A.C. Heater connections

For good EMC engineering practice, any sensor cables 

or switched live cables should not be 

placed within 50mm of other cables or on the same 

metal cable tray as other cables.

4.0 Electrical Installation

Units are not supplied with electrical isolators, their 

selection and provision is the responsibility of the installer.

Ensure the electrical supply is suitable for the fan and that

all wiring, fuse and overload protection etc is appropriately

sized by comparing with the rating plate. 

Electrical connection is made direct to the motor terminal box.

For DOL starting of 4kW and above, 3ph, the final 

connection must be in DELTA. If a STAR/DELTA starter 

is to be used connect all six motor terminals to the

appropriate terminals of the starter. 

Isolation - Before commencing inspection or 

maintenance work make sure that the unit 

is electrically isolated from the mains supply.