Any air intake terminal MUST be installed in accordance

with the appropriate regulation. 

As a guide, the BS5440 series of British Standards

deals with this issue and currently states that an air

intake must be at a minimum distance of 300mm from a

gas boiler balanced flue. Installers are advised to be

aware of the requirements of this standard when

installing ‘through the wall’ supply air ducting.

Similarly, supply and extract air grilles should be 

at least 300mm apart.

Key

Extract 

- stale air ducted from within ‘Wet’ rooms 

in the building.

Discharge 

- is the extracted air from the building 

ducted to the outside and removed.

Supply 

- is the fresh air ducted into the building. 

This may be sent to more than one room.

Intake 

- is the fresh air source ducted from outside.

1

2

3

4

2

16. 06. 15. Leaflet Number 671391

Installation and Maintenance

LPXBOXAC-2 Mechanical Ventilation with Heat Recovery

Side view (view from B) 

 

 

 

 

End view (view from A)

297 

 

        553

Plan view (view from underside 

with covers removed)

Plan view (Mounting bracket)

Plan view (view from top 

with covers removed)

106 

 

 598

623 

 

 140

97

6

6

 

14

0

 

3

3

3

 

View B

View A

General view of unit

2.0 Dimensions 

Figure 5. Dimensions in mm.

1

1

3

2

4

1

1