Leaflet Number 611272 January 2012

Installation and Maintenance

MRXBOX90L Mechanical Ventilation with Heat Recovery

8.0 Error code table

Error code

Cause 

Action user

Action installer

F2

The inlet fan has stopped 

• Contact the installer 

• Replace the inlet fan, it is defective

F5

The outlet fan has stopped

•  Contact the installer

• Replace the outlet fan, it is defective

F9

The temperature sensor that

•  Contact the installer

•  Check the wiring from the sensor

measures the temperature of

to the basic pcb

the input air is defective. The

•  Check the sensor connection to

unit operates as expected but

the wiring

the bypass is out of operation

• Replace the sensor

F10

The temperature sensor that

•  Contact the installer

•  Check the wiring from the sensor

measures the temperature of

to the basic pcb

the output air is defective. The

•  Check the sensor connection to

unit operates as expected but

the wiring

the bypass is out of operation

• Replace the sensor

9.0 Routine maintenance

Routine maintenance is limited to periodically cleaning or replacing the

filters. The filter only has to be cleaned when that is indicated on

the display (it shows the text 

"FIL"

) or, if a multiple switch with filter

indication is mounted, when the red LED at the switch lights up.

The filters must be replaced every year. It is not permitted to use the

appliance without filters.

1.  Put the 3-way switch at setting 1 to let the 

appliance’s fans run at low speed. 

Open the filter door.

2. Remove the filters and note how the filters are 

fitted into the unit. The filters can be cleaned 

with a vacuum cleaner.

3.  Refit the filters back into the unit the same way 

they were taken out.

4. Close the filter door.

After cleaning the filter or replacing with a new 

filter, the filter indication must be reset by 

pressing the key 

"OK"

during 1 second

.

The display will blink for a moment to confirm 

that the filter has been reset.

The unit will return to operational mode.

Put the 3-way switch back to the original 

setting.

1

2

3

Figure 18.

1

2

3

-  RESET -

-  ON -

-  

SET

 -

-  

OFF -

Note: If setting 2 does not work with a mechanical rpm control device, such as a multiple switch, the RJ connector has been 

connected the wrong way round. Cut off one of the RJ connectors to the rpm control and mount a new connector the other way round.

Summary of Contents for MRXBOX90L

Page 1: ...es heat transfer between inlet and outlet air 3 Filters filter both air flows 4 Atmospheric temperature sensor measures outside air temperature 5 Communication connection port for cable to multiple sw...

Page 2: ...ol fresh air A Electric connections B Detail wall mounting make sure to correctly place the rubber strip washers and caps C Connection condensate discharge B Detail of wall mounting Air Performance of...

Page 3: ...ctions F Function key switching on and off parameter menu next parameter increase value previous parameter decrease value OK Switching on and off settings menu manual fault reset Other commands can be...

Page 4: ...to emergency mode As standard that is set to switch off the fans 5 0 Installation Installation must be carried out by competent personnel in accordance with the appropriate authority and conforming t...

Page 5: ...if the resistance of the duct system is higher the maximum ventilation capacity will be lower the location of the mechanical ventilation outlet and the sewer stack vent relative to the inlet must be...

Page 6: ...reless Controller optional 1 General If required this optional control see fig 10 can be purchased direct fom Nuaire Part number MRXBOX90 BS Wireless remote control exists from a receiver and a sender...

Page 7: ...n the top and bottom Transmission Range The following figures for expected transmission range may be used as a rough guide only Line of sight connections 30m range in corridors up to 100m in halls Pla...

Page 8: ...sing keys or 5 The modified setting can now A Be saved and stored B Be removed C Be restored to factory setting A Simultaneously press keys F and first press F and then to save the modified setting th...

Page 9: ...ween 3 situations Mode 0 The bypass valve is not operated Mode 1 The bypass valve if installed is opened when standard The temperature conditions are complied with setting Mode 2 The inlet fan starts...

Page 10: ...for pre heater unit E X4 1 2 4 3 Mains in Mains in Figure 12 Typical installation for pre heater Figure 13 A Heating element max 1000W B Safety switch for maximum temperature with manual reset C Powe...

Page 11: ...ce MRXBOX90L Mechanical Ventilation with Heat Recovery Figure 14 6 6 Wiring diagram connection pre heater to MRXBOX90L without option pcb A Heating coil B Maximum safety with manual reset C Connecting...

Page 12: ...igure 15 Typical installation for post heater Figure 16 A Heating element max 1000W B Safety switch for maximum temperature with manual reset C Temperature sensor D Power connector 230V E Cable to be...

Page 13: ...5 minutes Press key OK 1 second If no key is operated during 1 minute Press keys F and OK 3 seconds Press key or Press F or key 1 second Press F or key 1 second Press OK key 1 second If no key is oper...

Page 14: ...of the multiple switch and the connected outlet volume are shown operational mode on the left of the multiple switch to the left of the dot The three remaining positions shown to the right of the dot...

Page 15: ...to activate the settings menu 2 Press keys F and OK for 3 seconds to activate the comprehensive parameters section for the installer 3 The desired parameter can be found with the aid of keys and 4 The...

Page 16: ...ond to reset the filter indication The text FIL will blink for a moment and then the display will return to operational mode 16 Leaflet Number 611272 January 2012 Installation and Maintenance MRXBOX90...

Page 17: ...acing the filters The filter only has to be cleaned when that is indicated on the display it shows the text FIL or if a multiple switch with filter indication is mounted when the red LED at the switch...

Page 18: ...t and the ARC number of the purchase if possible This information will be available on the fan label 11 0 Warranty The 5 year warranty starts from the day of delivery and includes 1 year parts and lab...

Page 19: ...Where access to any part of equipment which moves or can become electrically live are not prevented by the equipment panels or by fixed installation detail eg ducting then guarding to the appropriate...

Page 20: ...20 Leaflet Number 611272 January 2012 Western Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2088 5911 F 029 2088 7033 E info nuaire co uk W www nuaire co uk...

Reviews: