background image

19

Leaflet Number 611272 January 2012

Technical or commercial considerations may, from time to time, make it necessary to alter the design, performance and 

dimensions of equipment and the right is reserved to make such changes without prior notice.

DECLARATION OF INCORPORATION AND INFORMATION FOR SAFE INSTALLATION, 

OPERATION AND MAINTENANCE

To comply with EC Council Directives 98/37/EC Machinery Directive and

2004/108/EC (EMC).

To be read in conjunction with the relevant Product Documentation (see 2.1)

1.0

GENERAL

1.1

The equipment referred to in this 

Declaration of Incorporation 

is supplied by 

Nuaire to be assembled into a ventilation system which may or may not include 

additional components.

The entire system must be considered for safety purposes and it is the 

responsibility of the installer to ensure that all of the equipment is installed in 

compliance with the manufacturers recommendations and with due regard to 

current legislation and codes of practice.

2.0

INFORMATION SUPPLIED WITH THE EQUIPMENT

2.1

Each item of equipment is supplied with a set of documentation which provides 

the information required for the safe installation and maintenance of the 

equipment. This may be in the form of a Data sheet and/or Installation and 

Maintenance instruction.

2.2

Each unit has a rating plate attached to its outer casing.  The rating plate 

provides essential data relating to the equipment such as serial number, unit 

code and electrical data.  Any further data that may be required will be found 

in the documentation. If any item is unclear or more information is required, 

contact Nuaire.

2.3

Where warning labels or notices are attached to the unit the instructions given 

must be adhered to.

3.0

TRANSPORTATION, HANDLING AND STORAGE

3.1

Care must be taken at all times to prevent damage to the equipment.  Note that 

shock to the unit may result in the balance of the impeller being affected.  

3.2

When handling the equipment, care should be taken with corners and edges and 

that the weight distribution within the unit is considered.  Lifting gear such as 

slings or ropes must be arranged so as not to bear on the casing.

3.3

Equipment stored on site prior to installation should be protected from the 

weather and steps taken to prevent ingress of contaminants.

4.0

OPERATIONAL LIMITS

4.1

It is important that the specified operational limits for the equipment are 

adhered to e.g. operational air temperature, air borne contaminants and unit 

orientation.

4.2

Where installation accessories are supplied with the specified equipment eg.  

wall mounting brackets.  They are to be used to support the equipment only.  

Other system components must have separate provision for support.

4.3

Flanges and connection spigots are  provided for the purpose of joining to 

duct work systems.  They must not be used to support the ductwork.

5.0

INSTALLATION REQUIREMENTS

In addition to the particular requirements given for the individual product, the 

following general requirements should be noted.

5.1

Where access to any part of equipment which 

moves

, or can become 

electrically

live

are not prevented by the equipment panels or by fixed installation detail 

(eg ducting), then guarding to the appropriate standard must be fitted.

5.2

The electrical installation of the equipment must comply with the requirements 

of the relevant local electrical safety regulations.

5.3

For EMC all control and sensor cables should not be placed within 50mm or on 

the same metal cable tray as 230V switched live, lighting or power cables and 

any cables not intended for use with this product.

6.0

COMMISSIONING REQUIREMENTS

6.1 

General pre-commissioning checks relevant to safe operation consist of the 

following: 

Ensure that no foreign bodies are present within the fan or casing. 

Check electrical safety.  e.g. Insulation and earthing.

Check guarding of system.

Check operation of  Isolators/Controls.

Check fastenings for security.

6.2

Other commissioning requirements are given in the relevant product documentation.

7.0

OPERATIONAL REQUIREMENTS

7.1

Equipment access panels must be in place at all times during operation of the 

unit, and must be secured with the original  fastenings.

7.2

If failure of the equipment occurs or is suspected then it should be taken out of 

service until a competent person can effect repair or examination. (Note that 

certain ranges of equipment are designed to detect and compensate for fan failure).

8.0

MAINTENANCE REQUIREMENTS

8.1

Specific maintenance requirements are given in the relevant product documentation.

8.2

It is important that the correct tools are used for the various tasks required.

8.3

If the access panels are to be removed for any reason the electrical supply to the 

unit must be isolated.

8.4

A minium period of two minutes should be allowed after electrical disconnection 

before access panels are removed.  This will allow the impeller to come to rest.

NB: Care should still be taken however since airflow generated at some 

other point in the system can cause the impeller to “windmill”  even when 

power is not present.

8.5

Care should be taken when removing and storing access panels in windy 

conditions.

INFORMATION FOR SAFE INSTALLATION, OPERATION AND MAINTENANCE 

OF NUAIRE VENTILATION EQUIPMENT

We declare that the machinery named below is intended to be assembled
with other components to constitute a system of machinery.  All parts 
except for moving parts requiring the correct installation of safety guards
comply with the essential requirements of the Machinery Directive. The 
machinery shall not be put into service until the system has been 
declared to be in conformity with the provisions of the EC Machinery 
Directive.

Designation of machinery:

MRXBOX90L

Machinery Types:

Mechanical Ventilation with 

Heat Recovery Unit

Relevant EC Council Directives:

2006/42/EC (Machinery Directive)

Applied Harmonised Standards:

BS EN ISO 12100-1, BS EN ISO 12100-2, 
EN60204-1, BS EN ISO 9001, 
BS EN ISO 13857

Applied National Standards:

BS848 Parts 1, 2.2 and 5 

Note: All standards used were current and valid at the date of signature.

Signature of manufacture representatives:

Name:

Position:

Date:

1)  C. Biggs

Technical Director

23. 01. 12

2)  A. Jones

Manufacturing Director 

23. 01. 12

Summary of Contents for MRXBOX90L

Page 1: ...es heat transfer between inlet and outlet air 3 Filters filter both air flows 4 Atmospheric temperature sensor measures outside air temperature 5 Communication connection port for cable to multiple sw...

Page 2: ...ol fresh air A Electric connections B Detail wall mounting make sure to correctly place the rubber strip washers and caps C Connection condensate discharge B Detail of wall mounting Air Performance of...

Page 3: ...ctions F Function key switching on and off parameter menu next parameter increase value previous parameter decrease value OK Switching on and off settings menu manual fault reset Other commands can be...

Page 4: ...to emergency mode As standard that is set to switch off the fans 5 0 Installation Installation must be carried out by competent personnel in accordance with the appropriate authority and conforming t...

Page 5: ...if the resistance of the duct system is higher the maximum ventilation capacity will be lower the location of the mechanical ventilation outlet and the sewer stack vent relative to the inlet must be...

Page 6: ...reless Controller optional 1 General If required this optional control see fig 10 can be purchased direct fom Nuaire Part number MRXBOX90 BS Wireless remote control exists from a receiver and a sender...

Page 7: ...n the top and bottom Transmission Range The following figures for expected transmission range may be used as a rough guide only Line of sight connections 30m range in corridors up to 100m in halls Pla...

Page 8: ...sing keys or 5 The modified setting can now A Be saved and stored B Be removed C Be restored to factory setting A Simultaneously press keys F and first press F and then to save the modified setting th...

Page 9: ...ween 3 situations Mode 0 The bypass valve is not operated Mode 1 The bypass valve if installed is opened when standard The temperature conditions are complied with setting Mode 2 The inlet fan starts...

Page 10: ...for pre heater unit E X4 1 2 4 3 Mains in Mains in Figure 12 Typical installation for pre heater Figure 13 A Heating element max 1000W B Safety switch for maximum temperature with manual reset C Powe...

Page 11: ...ce MRXBOX90L Mechanical Ventilation with Heat Recovery Figure 14 6 6 Wiring diagram connection pre heater to MRXBOX90L without option pcb A Heating coil B Maximum safety with manual reset C Connecting...

Page 12: ...igure 15 Typical installation for post heater Figure 16 A Heating element max 1000W B Safety switch for maximum temperature with manual reset C Temperature sensor D Power connector 230V E Cable to be...

Page 13: ...5 minutes Press key OK 1 second If no key is operated during 1 minute Press keys F and OK 3 seconds Press key or Press F or key 1 second Press F or key 1 second Press OK key 1 second If no key is oper...

Page 14: ...of the multiple switch and the connected outlet volume are shown operational mode on the left of the multiple switch to the left of the dot The three remaining positions shown to the right of the dot...

Page 15: ...to activate the settings menu 2 Press keys F and OK for 3 seconds to activate the comprehensive parameters section for the installer 3 The desired parameter can be found with the aid of keys and 4 The...

Page 16: ...ond to reset the filter indication The text FIL will blink for a moment and then the display will return to operational mode 16 Leaflet Number 611272 January 2012 Installation and Maintenance MRXBOX90...

Page 17: ...acing the filters The filter only has to be cleaned when that is indicated on the display it shows the text FIL or if a multiple switch with filter indication is mounted when the red LED at the switch...

Page 18: ...t and the ARC number of the purchase if possible This information will be available on the fan label 11 0 Warranty The 5 year warranty starts from the day of delivery and includes 1 year parts and lab...

Page 19: ...Where access to any part of equipment which moves or can become electrically live are not prevented by the equipment panels or by fixed installation detail eg ducting then guarding to the appropriate...

Page 20: ...20 Leaflet Number 611272 January 2012 Western Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2088 5911 F 029 2088 7033 E info nuaire co uk W www nuaire co uk...

Reviews: