background image

4.5 Option pcb 

(MRXBOX90-OB)

The MRXBOX90L appliance can be equipped with an option pcb. 

It provides the following functions.

Input 0-10 V for a carbon dioxide sensor

When several people are present in the dwelling, more C02 is produced

and then this sensor automatically increases the ventilation quantity.

Input 0-10 V for a moisture sensor

When the moisture content in the dwelling increases, for instance

when someone is taking a shower, this sensor automatically increases

the ventilation quantity.

Switching input for bedroom valve

With this input (make contact) the bedroom valve can be controlled,

for instance using a time switch.

Switching output for bedroom valve 24 VAC

The option pcb has a built-in control for a 24 VAC bedroom valve. 

The valve can be connected directly to the pcb. The valve can be 

controlled from the switching input for the bedroom valve.

Switching output for 24 VAC flue gas safety valve

If it is recommended to combine the discharge of the central heating

and the MRXBOX90L unit. The MRXBOX90L unit connection to the

joint discharge must be protected with a flue gas safety valve. 

The valve can directly be connected to this pcb.

Control for pre-heater up to 1000 W 

(MRXBOX90-PRE-HEATER)

The pre-heater ensures that the input air is kept above 0°C, so the

MRXBOX90L unit can continue the balanced ventilation also at very

low atmospheric temperatures. The option pcb contains a control for 

a preheater up to 1000 W. The pre-heater can be connected to the

option pcb without separate control. The hook-up wire of the pre-

heater must be fed into the appliance; the 230V power cable must

separately be connected to the option pcb.

Control for post-heater up to 1000 W 

(MRXBOX90-POST-HEATER)

The post-heater ensures that the supply air that is blown into the

dwelling can be kept at the preset temperature. That way additional

warmth can be brought into the dwelling. The option pcb contains a

control for a pre-heater up to 1000 W. The pre-heater can be connected

to the option pcb without separate control. The hook-up wire of the

pre-heater must be fed into the appliance; the 230V power cable must

separately be connected to the option pcb.

Two freely programmable make contact inputs

These inputs make it possible :

•  to open the bypass without regard for the temperature 

conditions;

•  to switch the inlet or outlet low or high, to circumvent the

frost protection;

•  to switch the inlet low when the bypass opens.

Switching input for emergency

For instance a fire alarm can be connected to this input. As soon as

the fire alarm is triggered, the appliance switches to emergency mode.

As standard that is set to switch off the fans.

5.0 Installation 

Installation must be carried out by competent personnel in 

accordance with the appropriate authority and conforming to all

statutory and governing regulations.

All mains wiring must be in accordance with the current I.E.E.

Regulations, or the appropriate standards. 

Ensure that the mains supply (Voltage, Frequency and Phase) 

complies with the rating label. It is recommended that the connection

to the unit is made with flexible cable.

The unit must be fitted indoors, away from any direct sources of heat,

water spray or moisture generation.

The units condensate drain must be connected to the building foul

water drainage system.

If an extract grille associated with the unit is sited in a room containing

a fuel burning unit, the installer must ensure that air replacement is

adequate for both units. Also ensure that the units external grilles are

located at least 600mm away from any flue outlet.

If the ductwork passes through an unheated loft void or similar

location, it should be insulated.

Certain applications may require the installation of sound attenuation

to achieve the sound levels required.

Unit installation procedure can be summarised  

as follows:

1.  Placing the unit (5.1)

2.  Connecting the ducts (5.2)

3.  Connecting the condensate discharge (5.3)

4.  Electric wiring diagram:

connecting the multiple switch and the power supply (5.4)

MRXBOX90L units must be installed in accordance with:

•  the regulations for ventilation of dwellings and residential 

buildings

•  the safety regulations for low-voltage installations (current 

IEE regulations)

•  the regulations for connection to interior sewers in dwellings 

and residential buildings

• any additional regulations of the local utilities

• the installation instructions for MRXBOX90L

5.1 Placing the unit

MRXBOX90L units can be directly mounted to the wall using the 

suspension strips supplied for that purpose. For a vibration-free

result the unit must be mounted to a solid wall with a minimum mass

of 200kg/m

2

. (NB. a gypsum block or metal stud wall does not 

suffice. Additional measures such as double panelling or extra studs

are required).

A mounting support for floor mounting is available (article code

217031) if required. In addition, the following aspects must be taken

into account:

•  the unit must be placed level

•  the installation room must be such that a good condensate 

dis charge with air trap and pitch for condensate can be made

•  the installation room must be frost-free

•  make sure there is a free space of at least 70cm at the front of

the unit and a free headroom of 1.8m for cleaning the filters 

and carrying out maintenance

4

Leaflet Number 611272 January 2012

Installation and Maintenance

MRXBOX90L Mechanical Ventilation with Heat Recovery

Summary of Contents for MRXBOX90L

Page 1: ...es heat transfer between inlet and outlet air 3 Filters filter both air flows 4 Atmospheric temperature sensor measures outside air temperature 5 Communication connection port for cable to multiple sw...

Page 2: ...ol fresh air A Electric connections B Detail wall mounting make sure to correctly place the rubber strip washers and caps C Connection condensate discharge B Detail of wall mounting Air Performance of...

Page 3: ...ctions F Function key switching on and off parameter menu next parameter increase value previous parameter decrease value OK Switching on and off settings menu manual fault reset Other commands can be...

Page 4: ...to emergency mode As standard that is set to switch off the fans 5 0 Installation Installation must be carried out by competent personnel in accordance with the appropriate authority and conforming t...

Page 5: ...if the resistance of the duct system is higher the maximum ventilation capacity will be lower the location of the mechanical ventilation outlet and the sewer stack vent relative to the inlet must be...

Page 6: ...reless Controller optional 1 General If required this optional control see fig 10 can be purchased direct fom Nuaire Part number MRXBOX90 BS Wireless remote control exists from a receiver and a sender...

Page 7: ...n the top and bottom Transmission Range The following figures for expected transmission range may be used as a rough guide only Line of sight connections 30m range in corridors up to 100m in halls Pla...

Page 8: ...sing keys or 5 The modified setting can now A Be saved and stored B Be removed C Be restored to factory setting A Simultaneously press keys F and first press F and then to save the modified setting th...

Page 9: ...ween 3 situations Mode 0 The bypass valve is not operated Mode 1 The bypass valve if installed is opened when standard The temperature conditions are complied with setting Mode 2 The inlet fan starts...

Page 10: ...for pre heater unit E X4 1 2 4 3 Mains in Mains in Figure 12 Typical installation for pre heater Figure 13 A Heating element max 1000W B Safety switch for maximum temperature with manual reset C Powe...

Page 11: ...ce MRXBOX90L Mechanical Ventilation with Heat Recovery Figure 14 6 6 Wiring diagram connection pre heater to MRXBOX90L without option pcb A Heating coil B Maximum safety with manual reset C Connecting...

Page 12: ...igure 15 Typical installation for post heater Figure 16 A Heating element max 1000W B Safety switch for maximum temperature with manual reset C Temperature sensor D Power connector 230V E Cable to be...

Page 13: ...5 minutes Press key OK 1 second If no key is operated during 1 minute Press keys F and OK 3 seconds Press key or Press F or key 1 second Press F or key 1 second Press OK key 1 second If no key is oper...

Page 14: ...of the multiple switch and the connected outlet volume are shown operational mode on the left of the multiple switch to the left of the dot The three remaining positions shown to the right of the dot...

Page 15: ...to activate the settings menu 2 Press keys F and OK for 3 seconds to activate the comprehensive parameters section for the installer 3 The desired parameter can be found with the aid of keys and 4 The...

Page 16: ...ond to reset the filter indication The text FIL will blink for a moment and then the display will return to operational mode 16 Leaflet Number 611272 January 2012 Installation and Maintenance MRXBOX90...

Page 17: ...acing the filters The filter only has to be cleaned when that is indicated on the display it shows the text FIL or if a multiple switch with filter indication is mounted when the red LED at the switch...

Page 18: ...t and the ARC number of the purchase if possible This information will be available on the fan label 11 0 Warranty The 5 year warranty starts from the day of delivery and includes 1 year parts and lab...

Page 19: ...Where access to any part of equipment which moves or can become electrically live are not prevented by the equipment panels or by fixed installation detail eg ducting then guarding to the appropriate...

Page 20: ...20 Leaflet Number 611272 January 2012 Western Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2088 5911 F 029 2088 7033 E info nuaire co uk W www nuaire co uk...

Reviews: