6.1 Setting the air quantity

The air quantities of the MRXBOX90L unit for settings 1, 2 and 3 are 

factory-set and are shown on page one. 

The performance of the unit depends on the quality of the duct system

as well as on the filter resistance.

Important:

Setting 1: must always be lower than setting 2.

Setting 2: must always be lower than setting 3.

Setting 3: adjustable between 50 and 300/400 m

3

/h.

If these conditions are not complied with, the air quantity of the

higher setting will automatically be adjusted.

The air quantities can be modified as follows (as an example here the

air quantity for setting 3 will be changed from 300 to 280 m

3

/h).

1.

Press key 

"F"

for 3 seconds to activate 

the settings menu.

2. Use key 

“+”

to select the desired parameter 

(U1 = setting 1, U2 = setting 2, U3 = setting 3). 

Settings U4 and U5 only apply when bypass 

is required).

3. Press key 

"OK"

for 1 second to display the 

selected parameter value.

4. The selected parameter value can be changed 

using keys 

"+"

or 

“-”.

5. The modified setting can now:

A. Be saved and stored

B. Be removed

C. Be restored to factory setting

A. 

Simultaneously press keys 

“F” 

and 

“+”

(first 

press 

“F”

and then 

“+”

) to save the modified 

setting; this value now blinks 3x to confirm that

it has been stored. The value remains on the 

display.

Press key 

"OK"

to return to the settings menu; 

if required other settings can now be modified. 

(step 2 - 5).  Continue with item 6.

B. 

Press key 

"OK"

to return to the settings menu; 

without saving the modified setting. 

if required other settings can now be modified. 

(step 2 - 5).  Continue with item 6.

C.

Simultaneously press keys 

“F” 

and 

“-”

(first 

press 

“F”

and then 

“-”

) to go back to factory 

setting. The factory setting will blink 3x and 

remains at that value. The modified setting has 

now been removed and the factory setting 

remains on the display.

Press key 

"OK"

to return to the settings menu; 

If required several settings can now be 

modified. (see item 2 to 5) Now continue with 

item 6.

6. Press key 

"F"

for 1 second to leave the 

settings menu.

8

Leaflet Number 611272 January 2012

Installation and Maintenance

MRXBOX90L Mechanical Ventilation with Heat Recovery

-  RESET -

-  ON -

-  SE

T -

-  O

FF -

Summary of Contents for MRXBOX90L

Page 1: ...es heat transfer between inlet and outlet air 3 Filters filter both air flows 4 Atmospheric temperature sensor measures outside air temperature 5 Communication connection port for cable to multiple sw...

Page 2: ...ol fresh air A Electric connections B Detail wall mounting make sure to correctly place the rubber strip washers and caps C Connection condensate discharge B Detail of wall mounting Air Performance of...

Page 3: ...ctions F Function key switching on and off parameter menu next parameter increase value previous parameter decrease value OK Switching on and off settings menu manual fault reset Other commands can be...

Page 4: ...to emergency mode As standard that is set to switch off the fans 5 0 Installation Installation must be carried out by competent personnel in accordance with the appropriate authority and conforming t...

Page 5: ...if the resistance of the duct system is higher the maximum ventilation capacity will be lower the location of the mechanical ventilation outlet and the sewer stack vent relative to the inlet must be...

Page 6: ...reless Controller optional 1 General If required this optional control see fig 10 can be purchased direct fom Nuaire Part number MRXBOX90 BS Wireless remote control exists from a receiver and a sender...

Page 7: ...n the top and bottom Transmission Range The following figures for expected transmission range may be used as a rough guide only Line of sight connections 30m range in corridors up to 100m in halls Pla...

Page 8: ...sing keys or 5 The modified setting can now A Be saved and stored B Be removed C Be restored to factory setting A Simultaneously press keys F and first press F and then to save the modified setting th...

Page 9: ...ween 3 situations Mode 0 The bypass valve is not operated Mode 1 The bypass valve if installed is opened when standard The temperature conditions are complied with setting Mode 2 The inlet fan starts...

Page 10: ...for pre heater unit E X4 1 2 4 3 Mains in Mains in Figure 12 Typical installation for pre heater Figure 13 A Heating element max 1000W B Safety switch for maximum temperature with manual reset C Powe...

Page 11: ...ce MRXBOX90L Mechanical Ventilation with Heat Recovery Figure 14 6 6 Wiring diagram connection pre heater to MRXBOX90L without option pcb A Heating coil B Maximum safety with manual reset C Connecting...

Page 12: ...igure 15 Typical installation for post heater Figure 16 A Heating element max 1000W B Safety switch for maximum temperature with manual reset C Temperature sensor D Power connector 230V E Cable to be...

Page 13: ...5 minutes Press key OK 1 second If no key is operated during 1 minute Press keys F and OK 3 seconds Press key or Press F or key 1 second Press F or key 1 second Press OK key 1 second If no key is oper...

Page 14: ...of the multiple switch and the connected outlet volume are shown operational mode on the left of the multiple switch to the left of the dot The three remaining positions shown to the right of the dot...

Page 15: ...to activate the settings menu 2 Press keys F and OK for 3 seconds to activate the comprehensive parameters section for the installer 3 The desired parameter can be found with the aid of keys and 4 The...

Page 16: ...ond to reset the filter indication The text FIL will blink for a moment and then the display will return to operational mode 16 Leaflet Number 611272 January 2012 Installation and Maintenance MRXBOX90...

Page 17: ...acing the filters The filter only has to be cleaned when that is indicated on the display it shows the text FIL or if a multiple switch with filter indication is mounted when the red LED at the switch...

Page 18: ...t and the ARC number of the purchase if possible This information will be available on the fan label 11 0 Warranty The 5 year warranty starts from the day of delivery and includes 1 year parts and lab...

Page 19: ...Where access to any part of equipment which moves or can become electrically live are not prevented by the equipment panels or by fixed installation detail eg ducting then guarding to the appropriate...

Page 20: ...20 Leaflet Number 611272 January 2012 Western Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2088 5911 F 029 2088 7033 E info nuaire co uk W www nuaire co uk...

Reviews: