background image

MRXBOX95-WALL

Mechanical Ventilation Unit with 

Heat Recovery for Wall Mounting

Installation and Maintenance

Unit must not be switched off during normal operation, the

product is designed to run continuously.

1.0 Introduction

MRXBOX95-WALL is designed to provide mechanical supply

and extract ventilation with heat recovery.

The unit is fitted with two independent fans. Each fan has full

speed control for background and boost ventilation rates as

well as a run-on timer facility. To recover heat from the extract

air the heat exchanger block is utilised. This heat exchanger

can recover up to 95% of the normally wasted heat.

2.0 Installation

Installation must be carried out by competent personnel in

accordance with the appropriate authority and conforming

to all statutory governing regulations.

All mains wiring must be in accordance with the current I.E.E.

Regulations, or the appropriate standards. Ensure that the

mains supply (Voltage, Frequency and Phase) complies with

the rating label. 

Please note a clear working space is required around the

installed unit to allow the cover to be removed and provide 

sufficient access for maintenance such as filter change.

The fan must be installed indoors, on a wall away from direct

sources of frost, heat, water spray or moisture generation. For

a vibration-free result the unit must be mounted to a solid wall.

The unit is designed for wall mounting only.

1. One part of the mounting bracket should be offered up to 

the wall, ensuring it’s located horizontally. Mark the fixing 

points through the pre drilled holes in the bracket and 

install with screws (by others), ensuring the interlock side 

is at the top (fig. 2). 

2. Fix the remaining part of the bracket to the unit using the 

M6 screws ensuring the interlock side is at the bottom (fig. 3).

3. Install the unit on the wall by ensuring the bracket on the 

unit interlocks over the wall mounted bracket (fig. 4).

2.1 Condensate Drain

1.

Remove the front cover from the unit. 

2. Insert the drain connector through the base of the unit from

outside. The condensate must be discharged under a water 

level in a U-trap drainpipe or an alternative drain method 

which acts as an airlock.  

3. Ensure the drain connector forms a seal with the drain tray 

applying sealant if necessary. This condensate discharge 

connection is suitable for 21.5mm dia. overflow pipe. 

Solvent cement should be used to make the joint. 

4. Pour water into the drip tray to create an air trap.

Nuaire Limited

Western Industrial Estate  Caerphilly  United Kingdom  CF83 1NA  

T: 029 2085 8400  F: 029 2085 8444  E: info@nuaire.co.uk  W: www.nuaire.co.uk

1

02. 07. 15. Leaflet Number 671437

Extract air 

from house

Intake air 

from outside

Exhaust air 

from house

to outside

Supply air 

to house

Figure 1. Airflow through unit.

The EMC Directive 

2004/108/EC  

The Low Voltage 

Directive 

2006/95/EC

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 3. Fixing the mounting

bracket to the rear of unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 4. Mounting the unit

on the wall mounted bracket.

Figure 5. Condensate pipe connection to unit and a typical example

of a “U” trap drainpipe.

Figure 2. Fixing the mounting bracket to the wall.

21.5mm dia. condensate pipe. 

See point 3 above for sealing.

5

Drop

Collar

Reviews: