background image

4

02. 07. 15. Leaflet Number 671437

Installation and Maintenance

MRXBOX95-WALL Mechanical Ventilation with Heat Recovery

Electrical connection cont.

Figure 10. Detail of unit control on front panel.  

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

Optional Connections

Ecosmart control 

(see figure 7b)

(a) J11/12/13

The IDC plug-in connectors are provided for the connection of

compatible sensors. 

NOTE: Do not run the data cable in the same conduit as the

mains cable and leave a 50mm separation with any power

cables.

(b) Volt Free Relay Contacts 

Note that the volt free contacts are not fused. If these are used

to power any external equipment, the installer must provide

adequate fusing or other protections. These contacts are rated

at 5A resistive, 0.5A inductive.

Run connections (J5)

- These contacts are closed when the

fan is running.

Fault connections (J7)

- No fault = the contacts are closed.

Fault

= the contacts are opened (this includes no power supply

at the unit).

(c) Data Cable installation

A 4-core data cable is used to connect devices such as sensors

to the fan and for interconnecting multiple fan units.

Do not run data cable in the same conduit as the mains cables

and ensure there is a 50mm separation between the data cable

and other cables. The maximum cable run between any two

devices is 300m when it is installed in accordance with the

instructions.

Please note that the total data cable length used in any system

must be less than 1000m. Keep the number of cable joints to a

minimum to ensure the best data transmission efficiency

between devices.

LED Indication

PWR GREEN: 

Power on and OK,

RED: 

Standby LED on when fan is not running. 

As the unit runs continuously this LED should 

be off. If it is illuminated locate the trickle 

switch and change its position.

Fan 1 GREEN:

Fan 1 is running, 

RED:

Fan 1 faulty.

Fan 2 GREEN: 

Fan 2 is running,

RED:

Fan 2 faulty.

5.0  Ancillaries

Passive Infra red detector

MRXBOX95-PIR

External Humidity sensor

MRXBOX95-HUM

Remote Fail Indicator

MRXBOX95-RFI

6.0 Commissioning

1.

For the required airflow rates refer to the design 

specification for the property or refer to Building 

Regulations Part F.

2.

The unit is supplied with control of both the normal 

airflow and boost airflow. (see figure below).

3.

Commissioning should be carried out using a moving 

vane anemometer in conjunction with a hood.

4.

Once commissioned the house owner / tenant should 

be informed that the unit should not be adjusted as it 

will have a detrimental effect on the indoor air quality 

and could result in condensation and mould growth.

Reviews: