background image

2.1 Condensate Drain installation

1.

Unit comes complete with external drain pipe (21.5mm waste 

pipe). Use conventional plumbing connections to link up with

U-trap or alternative drain method (Solvent cement 

connections or compression fit connections are 

recommended). The condensate must be discharged under a 

water level in a U-trap drainpipe or an alternative drain 

method which acts as an airlock.  

2. This condensate discharge connection is suitable for 21.5mm

dia. overflow pipe. Solvent cement should be used to make 

the joint. 

3. If using a U-trap please ensure the U-trap has been filled to 

a suitable level of water to avoid any air locks.

4. If the condensation pipe is fitted in an unheated space the 

pipe should be in insulated to prevent freezing. 

Nuaire recommend MVHR-DRAIN be used as the primary

condensate take-off. (see figures 4a and 4b).

Fixing

Offer up the MVHR-DRAIN inlet to the threaded tail of the 

appliance waste outlet or MVHR-DRAIN knuckle or running

adaptor, and tighten the threaded cap sufficiently hand-tight to

provide a water-tight seal (check that the cap screws on square

and does not ‘cross-thread’). When the screwed cap is tight, the

MVHR-DRAIN

body is secure.

1.  Cut the pipe to length, allowing for the full compression 

socket depth (using an appropriate pipe cutter, such as a 

Hepworth rachet pipe cutter).

2. Remove any ‘swarf’ from the end of the plastic pipe. 

Ream the copper pipe end to remove any ‘burr’, and file if 

necessary to remove any external sharp edges. Mark the 

socket depth on the pipe, and check that the pipe section to 

be jointed is free of any surface damage which may affect 

the joint seal.

3. Unscrew the cap from the MVHR-DRAIN outlet, and slide the 

cap and rubber seal onto the pipe.

4. Insert the pipe end fully into the socket.

5. Slide the rubber seal and screwed cap up against the face of

the socket, and tighten the cap sufficiently hand-tight (check

that the cap is square to the body and does not ‘cross-

thread’). Hand tight should be adequate to form a proper seal.

2.2 Extract/input areas

The unit is designed to extract air from all wet rooms 

e.g. bathroom, kitchen, en-suite, utility room (with sink). 

WC’s do not need to be ventilated if openable windows are fitted.

Supply air should be to all habitable rooms e.g. bedrooms and

lounge. Extract / input grilles should be adjustable valve types

(not supplied).

External grilles to have a minimum free area of 12,250 sq mm.

2.3 Ducting

Before commencing ducting installation reference should be

made to building regulations document “Domestic ventilation

compliance guide”. This document supports ADF2010 and

details installation, testing and commissioning of all ventilation

systems.

It is recommended that rigid ducting must be used it all times. 

Flexible ducting has a very high resistance and it is impossible

to calculate how much resistance will be on a system if used.

If used the flexible ducting must be kept to a minimum and

should always be pulled taut. A maximum of 300mm should 

be used on each leg.

To prevent condensation on the outside of the outside air inlet

duct and the air outlet duct from the MRXBOX95B-LP1EH,

these ducts should be insulated. 

Ducting must be installed in such a way that resistance to 

airflow is minimised. Bends should be kept to a minimum.

A minimum distance of 200mm between the appliance and 

any bends in ductwork is recommended.

204 x 60mm rectangular ducting should be used. (Refer to

dwelling ducting design drawing, figure 6 on page 4 for further 

information).

Ducting joints must be sealed with silicone type sealant and

needs to be taped. Ducting shall be adequately and reliably

fixed to the appliance.

2.4 Ventilation flow rates

Table 1.

ADF2006 / 2010  – Extract ventilation rates

Room

Min high rate

Min low rate

Kitchen

13 l/s

Utility room

8 l/s

Bathroom

8 l/s

Sanitary 
accommodation

6 l/s

Table 2.

Whole dwelling ventilation rates

Number of bedrooms in dwelling

1

2

3

4

5

Whole

13

17

21

25

29

dwelling 
ventilation 
rate l/s

1, 2

Notes:

1, In addition, the minimum ventilation rate should be not less than 0.3 l/s

per m2 of internal floor area. 

(This includes all floors, e.g. for a two-story building add the ground and

first floor areas).

2, This is based on two occupants in the main bedroom and a single occu-

pant in all other bedrooms. This should be used as the default value. If a

greater level of occupancy is expected add 4 l/s per occupant. 

2

05. 09. 13. Leaflet Number 671632

Installation and Maintenance

MRXBOX95B-LP1EH Mechanical Ventilation with Heat Recovery & Summer Bypass

Figure 4a. MVHR-DRAIN condensate drain, running to SVP.

Total extract rate should

be at least the whole

dwelling ventilation rate

given in table 2.

Figure 4b. MVHR-DRAIN correct installation.

RIGHT

WRONG

Flow

Side elevation

When installed horizontally the ribs must be at the bottom to 
ensure correct operation. 

Summary of Contents for MRXBOX95B-LP1EH

Page 1: ...mains wiring must be in accordance with the current I E E Regulations or the appropriate standards Ensure that the mains supply Voltage Frequency and Phase complies with the rating label Please note...

Page 2: ...d be adjustable valve types not supplied External grilles to have a minimum free area of 12 250 sq mm 2 3 Ducting Before commencing ducting installation reference should be made to building regulation...

Page 3: ...um high rate from Table 1 For sanitary accommmodation only as an alternative the purge ventilation provisions given in ADF 2010 can be used where security is not an issue In this case minimum high ext...

Page 4: ...in ceilings Exhaust air from kitchen bathroom to outside via air brick Part no PVC505NS Supply and extract ducts from external air bricks to the unit needs to be insulated Minimum 300mm Top of ceilin...

Page 5: ...erving kitchen and bathroom Unit serving kitchen and two bathrooms Figure 8 Figure 9 For good EMC engineering practice any sensor cables or switched live cables should not be placed within 50mm of oth...

Page 6: ...eds to operate the fan to maximum airflow See wiring diagram for details of operating this facility 7 2 Humidity adjustment This product contains an internal humidity sensor fitted into the airflow ex...

Page 7: ...ffected 3 2 When handling the equipment care should be taken with corners and edges and that the weight distribution within the unit is considered Lifting gear such as slings or ropes must be arranged...

Page 8: ...8 05 09 13 Leaflet Number 671632 Western Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2085 8400 F 029 2085 8444 E info nuaire co uk W www nuaire co uk...

Reviews: