background image

2.5 Air permeability and 
infiltration

Is the uncontrolled exchange of air between inside and outside

through cracks, porosity and other unintentional openings in

the building. ADF2006 gives an allowance for this in both multi

and single storey buildings, however ADF2010 has an

allowance for multi storey only. Additionally ADF2010  only

applies this allowance for dwellings leakier than 5 m

3

/(h.m

2

) at

50Pa. (See below).

2.6 ADF 2006 Ventilation 
calculations
Continuous supply and extract

Step 1: 

Determine the whole building ventilation rate 

from Table

2.

Allow for infiltration by subtracting from this value:

for multi-storey dwellings: 0.04 x gross internal volume of 

the dwelling heated space (m

3

);

for single-storey dwellings: 0.06 x gross internal volume of 

the dwelling heated space (m

3

).

Step 2: 

Calculate the whole dwelling air extract rate at 

maximum operation by summing the individual room rates for

‘minimum high rate’ 

from Table 1.

(For sanitary accommmodation only, as an alternative, the

purge ventilation provisions given in ADF 2006 can be used

where security is not an issue. In this case ‘minimum high

extract rate’ for the sanitary accommodation should be omitted

from the step 2 calculation).

Step 3: 

The required airflow rates are as follows:

the maximum extract rate (e.g. boost) should be at least 

the greater of step 1 and step 2. Note that the maximum 

individual room extract rate should be at least those given 

in table 1

. for minimum high rate.

the minimum air supply rate should be at least the whole 

building ventilation rate found in step 1.

2.7 ADF 2010 Ventilation 
calculations
Design of MVHR systems

The MVHR system has been sized for the winter period.

Additional ventilation may be required during the warmer

months and it has been assumed that the provisions for purge

ventilation (e.g. openable windows) could be used.

Step 1:

For any design air permeability, determine the whole

dwelling ventilation supply rate 

from Table 2.

As an alternative where the design air permeability is intended

to be leakier than (>) 5m

3

/(h.m

2

) 50 Pa, allow for infiltration

for all dwelling types by subtracting from the whole dwelling

ventilation supply rate 

from Table 2

; 0.04 x gross internal 

volume of the dwelling heated space (m

3

).

Step 2:

Calculate the whole dwelling extract ventilation rate by

summing the individual room rates for ‘minimum high rate’ 

from

Table 1.

(For sanitary accommmodation only, as an alternative, the

purge ventilation provisions given in ADF 2010 can be used

where security is not an issue. In this case ‘minimum high

extract rate’ for the sanitary accommodation should be omitted

from the step 2 calculation).

Step 3: 

The required airflow rates are as follows:

the maximum whole dwelling extract ventilation rate 

(e.g. boost) should be at least the greater of step 1 and 

step 2. 

Note that the maximum individual room extract rate should 

be at least those given

in table 1.

for minimum high rate.

the minimum air supply rate should be at least the whole 

building ventilation rate found in step 1.

For Scotland refer to BRE Digest 398.

3.0  Optional Ecosmart Sensors 
and Control available for 
MRXBOX95B-LP1EH

ES-UFC - 

Manual user control

ES-HUM2 - 

Humidity sensor 

ES-AV12 - 

Remote Fail Indicator 

ES-PIR - 

Passive Infra-Red Detector 

ES-JB - 

Pre-plugged Junction Box 

ES-Temp - 

Room Temperature Sensor 

ES-RH - 

Relative Humidity Sensor 

ES-THERMOSTAT - 

Activates system when  

temperature rises above set point 

ES-VF - 

Volt Free Relay Box 

a) Control connections

Net

- the 4 IDC plug-in connectors are provided for the 

connection of compatible sensors, manual controls and for 

linking the fans together under a common control. If more 

than 4 connections are required, the junction box (product 

code ES-JB) should be used (see data cable installation).

b) Data Cable Installation

A 4-core SELV data cable is used to connect devices. 

Do not run data cable in the same conduit as the mains 

cables and ensure there is a 50mm separation between the

data cable and other cables. The maximum cable run between

any two devices is 300m when it is installed in accordance

with the instructions.

Please note that the total data cable length used in any 

system must be less than 1000m. Keep the number of 

cable joints to a minimum to ensure the best data 

transmission efficiency between devices.

3

05. 09. 13. Leaflet Number 671632

Installation and Maintenance

MRXBOX95B-LP1EH Mechanical Ventilation with Heat Recovery & Summer Bypass

Any air intake terminal MUST be installed in accordance with the

appropriate regulation. 

As a guide, the BS5440 series of British Standards deals with

this issue and currently states that an air intake must be at a

minimum distance of 300mm from a gas boiler balanced flue.

Installers are advised to be aware of the requirements of this

standard when installing ‘through the wall’ supply air ducting.

Similarly, supply and extract air grilles should be at least

300mm apart.

Summary of Contents for MRXBOX95B-LP1EH

Page 1: ...mains wiring must be in accordance with the current I E E Regulations or the appropriate standards Ensure that the mains supply Voltage Frequency and Phase complies with the rating label Please note...

Page 2: ...d be adjustable valve types not supplied External grilles to have a minimum free area of 12 250 sq mm 2 3 Ducting Before commencing ducting installation reference should be made to building regulation...

Page 3: ...um high rate from Table 1 For sanitary accommmodation only as an alternative the purge ventilation provisions given in ADF 2010 can be used where security is not an issue In this case minimum high ext...

Page 4: ...in ceilings Exhaust air from kitchen bathroom to outside via air brick Part no PVC505NS Supply and extract ducts from external air bricks to the unit needs to be insulated Minimum 300mm Top of ceilin...

Page 5: ...erving kitchen and bathroom Unit serving kitchen and two bathrooms Figure 8 Figure 9 For good EMC engineering practice any sensor cables or switched live cables should not be placed within 50mm of oth...

Page 6: ...eds to operate the fan to maximum airflow See wiring diagram for details of operating this facility 7 2 Humidity adjustment This product contains an internal humidity sensor fitted into the airflow ex...

Page 7: ...ffected 3 2 When handling the equipment care should be taken with corners and edges and that the weight distribution within the unit is considered Lifting gear such as slings or ropes must be arranged...

Page 8: ...8 05 09 13 Leaflet Number 671632 Western Industrial Estate Caerphilly United Kingdom CF83 1NA T 029 2085 8400 F 029 2085 8444 E info nuaire co uk W www nuaire co uk...

Reviews: