background image

2

15. 03. 21. Document Number  671857

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

MRXBOXAB-ECO4-(SC/SW)

Installation Manual

Care must be taken to ensure the unit is installed true in all 3 
dimensions. Failure to do so may result in overflow from the 
internal condensation drip tray. 

If fitting the MVHR in conjuntion with a MRXBOX-SIL4 the unit 
should be mounted using alternative brackets supplied under part 
code MRXBOX-AV4, the standard wall brackets supplied with the 
MVHR are not rated for the additional load.

One part of the mounting bracket (supplied) should be offered 
up to the wall, ensuring it’s located horizontally. Mark the fixing 
points through the pre drilled holes in the bracket and install with 
screws (by others), whilst ensuring the interlock side is at the top 
(Figure 3).

Install the unit on the wall by ensuring the bracket on the unit 
interlocks over the wall mounted bracket (Figure 4). Ensure the 
mains power cable does not become trapped between the brackets 
during this process as this will prevent engagement and potentially 
damage the electrical insulation. The cable gland can be rotated 
through 90° to assist this operation and subsequent cable routing.

 

Wall Mounting Bracket

3.1 Solid Wall Mounting

The MVHR unit fixed to a solid wall construction using a suitable 

mounting structure (supplied by others).  

Ducting in the 

ceiling void.

Side view of unit 

mounted on the

block wall in a 

cupboard.

MVHR-DRAIN

Condensate drain,

uninsulated drain 

pipe with min 5

o

fall running to SVP.

Valve in ceiling.

Solid Wall Mounted Unit Installation

3.2 Non-Solid Wall Mounting

The unit is designed for wall mounting, only on a solid wall. A 
gypsum block or stud/plasterboard wall will not suffice.

If it is not practical to use a solid wall, the MVHR unit should be 
fixed to a stud partition with a 25mm minimum thickness MDF 
panel solidly fixed behind the plasterboard.

If fixing to a stud wall the MDF panel should extend, width wise, over a 
minimum of 3 vertical studs with centres of no more than 400mm. Add 
additional vertical supports if necessary.  Height wise, ideally, the MDF 
panel should extend from floor to ceiling but as a minimum should be a 
least 2m high.

Fix the mounting bracket to the wall (Figure 3) and use the wall 
mounted bracket to mount the unit on (Figure 5).

2.0 INTRODUCTION

The ECO4 wall mounted units are designed to provide mechanical 
supply and extract ventilation with heat recovery and an integral 
automatic HX bypass.

The MVHR unit is fitted with two independent fans to provide 
mechanical supply and extract ventilation, each fan has full speed 
control for background and boost ventilation rates. To recover heat 
from the extract air, the heat exchanger block is utilised. The heat 
exchanger can recover up to 95% of the normally wasted heat.

Bypass operation can be disabled via a manual switch in colder months 
so the unit recovers heat continually.

 
 

Extract air 
from house

Intake air 

Exhaust air 

from outside

to outside

from house

to house

Supply air 

Intake air 
from outside

Extract air 
from house

Supply air 
to house

Exhaust air 
from house
to outside

Airflow Through unit (Standard Hand Unit)

 
 

Extract air 
from house

Intake air 

Exhaust air 

from outside

to outside

from house

to house

Supply air 

Intake air 
from outside

Extract air 
from house

Supply air 
to house

Exhaust air 
from house
to outside

Airflow Through OH unit (Opposite Hand Unit)

3.0 MECHANICAL INSTALLATION

Installation must be carried out by competent personnel in accordance 
with the appropriate authority and conforming to all statutory 
governing regulations. All mains wiring must be in accordance with the 
current I.E.E. Regulations, or the appropriate standards. Ensure that the 
mains supply (Voltage, Frequency and Phase) complies with the rating 
label. 

A clear working space is required around the installed unit to allow the 
cover to be removed and provide sufficient access for maintenance 
such as filter change. 

A minimum of 480mm is required in front of 

the unit.

The fan must be installed indoors, on a suitable wall away from direct 
sources of frost, heat and water spray or moisture generation. For a 
vibration-free result the unit must be mounted to a solid wall.

The unit must remain switched on at all times to maintain 
ventilation within the dwelling. Turning the unit off will cause long 
term damage to the unit and building fabric.

This appliance is not intended for use by persons (including 
children) with reduced physical, sensory or mental capabilities, 
or lack of experience and knowledge, unless they have been given 
supervision or instruction concerning the use of the appliance by a 
person for their safety. Children should be supervised so that they 
do not play with the appliance.

Summary of Contents for MRXBOXAB-ECO4-OHSC

Page 1: ...erson responsible for their safety Children shall not play with the appliance Cleaning and user maintenance shall not be carried out by children 1 1 Hazard Symbols REFER TO INSTRUCTION MANUAL Read and...

Page 2: ...nted bracket to mount the unit on Figure 5 2 0 INTRODUCTION The ECO4 wall mounted units are designed to provide mechanical supply and extract ventilation with heat recovery and an integral automatic H...

Page 3: ...o not need to be ventilated if openable windows are fitted Supply air should be to all habitable rooms e g bedrooms and lounge Extract input grilles should be adjustable valve types not supplied Exter...

Page 4: ...where the design air permeability is intended to be more than 5m3 h m2 50 Pa allow for infiltration for all dwelling types by subtracting from the whole dwelling ventilation supply rate from Whole Dwe...

Page 5: ...485 710 710 585 Ecosmart connection 4 x Spigots 180mm Internal Diameter 200mm External Diameter View from top Side view Front view 18 Mounting Bracket AB AB 200 176 534 67 492 CRS 67 40 0 CRS 5 Fixing...

Page 6: ...r Valve mounted unit Nuaire wall MVHR DRAIN Condensate drain uninsulated drain pipe with min 5o fall running to SVP Insulated extract duct 3 9 2 Rectangular Ducting 13 Typical Rectangular Ducting Arra...

Page 7: ...ring installation via a fused isolator in accordance with current IEE wiring regulations 4 2 Wiring Diagrams 4 2 1 Unit Only 14 Wiring Diagram Unit Only MAINS 230V 50Hz N L 3 Position Switch Ancillary...

Page 8: ...Humidity Adjustment This product contains an internal humidity sensor fitted into the air flow extracting from the wet rooms When the unit senses that the humidity exceeds the set point the unit will...

Page 9: ...ate attached to the unit casing Telephone 02920 858 400 aftersales nuaire co uk Technical or commercial considerations may from time to time make it necessary to alter the design performance and dimen...

Page 10: ...10 15 03 21 Document Number 671857 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO4 SC SW Installation Manual NOTES...

Page 11: ...11 15 03 21 Document Number 671857 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO4 SC SW Installation Manual NOTES...

Page 12: ...12 15 03 21 Document Number 671857 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO4 SC SW Installation Manual NOTES...

Reviews: