background image

8

15. 03. 21. Document Number  671857

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

MRXBOXAB-ECO4-(SC/SW)

Installation Manual

5.0 COMMISSIONING

The filters fitted inside the unit are protected with a plastic film. 
Prior to commissioning remove the covers (Figure 201), take off the 
film and replace.

For the required air flow rates please refer to the design 
specification for the property, follow Section 3.7, or refer to 
building regulations ADF 2010.

The unit should be run for a minimum of 10 minutes to reach 
steady state before commencing commissioning.

The humidity sensor is initially set to its least sensitive position, 
this should be adjusted during commissioning.  Depending on 
storage and site conditions, the unit may boost due to high relative 
humidity levels, this will continue until the level drops below the 
specified set point.

The unit is supplied with independent control for both normal and 
boost airflows (Figure 19).

Correct commissioning is essential to ensure the ventilation air 
flow rates are met. It also ensures the unit is not over ventilating 
and causing excessive power consumption.

Commissioning should be carried out in accordance with 
building regulations document “Domestic ventilation compliance 
guide”. www.planningportal.gov.uk/building regulations/
approved documents/partf/associated. A calibrated moving 
vane anemometer and hood will be required to carry out 
commissioning.

Adjustment valves should be locked in place to prevent further 
adjustment.

Once commissioned the home owner / tenant should be informed 
that the unit should not be adjusted as it will have a detrimental 
effect on the indoor air quality and could result in condensation 
and mould growth. The clear panel covering the control has 
an adhesive panel which should be exposed and sealed post 
commissioning to prevent tampering.

 

+

-

Post commissioning remove
adhesive backing and seal 

061021

Power  Fan

Failure

+

-

Ventilation Controls

- +

+

- +

-

Speed 1 

- +

Speed 2 

Speed 3

Supply  Extract  Supply  Extract  Supply  Extract

18 

Unit Control On Front Panel

6.0 CONTROLS

6.1 Humidity Adjustment

This product contains an internal humidity sensor fitted into the air-
flow extracting from the wet rooms. When the unit senses that the 
humidity exceeds the set point the unit will boost to that set by the 
commissioned boost speed. The set point can be found on the front 
of the unit (Figure 18) and is at its least sensitive when turned fully 
clockwise. Note that the sensor is measuring humidity from all the wet 
rooms at the same time and should not be relied on to solely boost the 
unit. Additional switch should be used local to the wet rooms (Section 
4.2).

6.2 Status Indication

The status of the unit is indicated by a series of LED’s on the front cover. 

The variants are listed below.

The display on the unit control panel will not indicate when a 

higher speed setting has been triggered by an external source, such 

as an ES-PIR2 etc.

 

 

19 

Unit Control On Front Panel

HX Bypass

(AB units only)

Speed 1

Speed 2

Speed 3

Supply Fan Fault

Extract Fan Fault

Frost Protection

Filter Change

6.3 Integral Automatic HX Bypass

Intake and extract temperatures are monitored at the point the 

airflows enter the unit, if the range falls within the set parameters the 

bypass damper is opened automatically to target an indoor comfort 

temperature all year round.
The extract temperature is an average from all wet rooms. If this 

exceeds 25°C the unit may go into bypass depending on outside 

temperatures.

6.4 Summer / Winter Switch

When the switch position is set to Summer the integral automatic 
summer bypass is fully operational, in the alternative Winter position 
the HX bypass is disabled to ensure the unit is constantly in heat 
recovery mode.

6.5 Speed 3 Operation (SW Units Only)

Speed 3 will be non-operational if the intake temperature is greater 

than the extract temperature.

6.6 Frost Protection

In the event of the intake air temperature at the unit dropping below 

the predetermined set point (-5°C as standard) the supply fan will 

reduce to minimum speed, once the temperature rises above the set 

point the fan will return to its commissioned speed.
Frost protection will only activate after ten days of continuous run 

time. If commissioning of the unit is outside of this time frame please 

notify the after sales department prior to site visit.

Summary of Contents for MRXBOXAB-ECO4-OHSC

Page 1: ...erson responsible for their safety Children shall not play with the appliance Cleaning and user maintenance shall not be carried out by children 1 1 Hazard Symbols REFER TO INSTRUCTION MANUAL Read and...

Page 2: ...nted bracket to mount the unit on Figure 5 2 0 INTRODUCTION The ECO4 wall mounted units are designed to provide mechanical supply and extract ventilation with heat recovery and an integral automatic H...

Page 3: ...o not need to be ventilated if openable windows are fitted Supply air should be to all habitable rooms e g bedrooms and lounge Extract input grilles should be adjustable valve types not supplied Exter...

Page 4: ...where the design air permeability is intended to be more than 5m3 h m2 50 Pa allow for infiltration for all dwelling types by subtracting from the whole dwelling ventilation supply rate from Whole Dwe...

Page 5: ...485 710 710 585 Ecosmart connection 4 x Spigots 180mm Internal Diameter 200mm External Diameter View from top Side view Front view 18 Mounting Bracket AB AB 200 176 534 67 492 CRS 67 40 0 CRS 5 Fixing...

Page 6: ...r Valve mounted unit Nuaire wall MVHR DRAIN Condensate drain uninsulated drain pipe with min 5o fall running to SVP Insulated extract duct 3 9 2 Rectangular Ducting 13 Typical Rectangular Ducting Arra...

Page 7: ...ring installation via a fused isolator in accordance with current IEE wiring regulations 4 2 Wiring Diagrams 4 2 1 Unit Only 14 Wiring Diagram Unit Only MAINS 230V 50Hz N L 3 Position Switch Ancillary...

Page 8: ...Humidity Adjustment This product contains an internal humidity sensor fitted into the air flow extracting from the wet rooms When the unit senses that the humidity exceeds the set point the unit will...

Page 9: ...ate attached to the unit casing Telephone 02920 858 400 aftersales nuaire co uk Technical or commercial considerations may from time to time make it necessary to alter the design performance and dimen...

Page 10: ...10 15 03 21 Document Number 671857 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO4 SC SW Installation Manual NOTES...

Page 11: ...11 15 03 21 Document Number 671857 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO4 SC SW Installation Manual NOTES...

Page 12: ...12 15 03 21 Document Number 671857 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO4 SC SW Installation Manual NOTES...

Reviews: