background image

1.0 The Nuaire NA-SRHR-100 Single Room
Heat Recovery Fan

The fan is suitable for refurbishment or new build in Kitchen,
Bathroom and Toilet applications. The fan can be directly installed
into existing 100mm fan holes.

The fan will run continuously at a 6l/s trickle extraction rate with
an automatic boost to 15l/s when activated by the integral
humidistat sensor.

2.0 Where to install the fan

1 In walls 380mm maximum thickness.

2. Locate it as high as possible.

3. At least 100mm from the edges of the mounting surface to 

sides/top of unit.

4. As far away as possible from and opposite to the main 

source of air replacement to ensure airflow across the room 
(e.g. opposite the internal doorway.

5. Near the source of steam or odours.

6. Not where ambient temperatures are likely to exceed 50°C 

or are below -20°C.

7. If installed in a kitchen fans must not be mounted immediately

above a cooker hob, or eye level grill.

8. If installing in a room containing a fuel burning device which 

has a non-balanced flue, it is the installer's responsibility to 
ensure that there is enough replacement air to prevent fumes 
being drawn down the flue when the fan is operating up to 
maximum extract. Refer to Building Regulations for specific 
requirements.

9. Exhaust air must not be discharged into a flue used for

exhausting of fumes from appliances supplied with energy 
other than electric. Requirements of all authorities concerned 
must be observed for exhaust air discharge and intake flow 
rates.

10.Not suitable for use in possible chemical corrosive 

atmospheres.

11.Do not site where the fan is exposed to water spray for 

extended periods.

3.0 What the installer will need

3mm electrician’s screwdriver and No.1 or 2 Pozidrive screwdrivers.

A 115mm dia. prepared hole with a slope to the outside, cut with a
minimum 115mm dia. core drill.

4.0 Fan Installation

Installation should be carried out by competent personnel in 
accordance with the appropriate authority and conforming to 
all statutory and governing regulations.

Installing the isolating switch and cable.

l

Isolate the mains supply.

l

Lay in the cable from the isolating switch to the fan location.

l

Lay in the cable from the isolating switch to the point of 
connection to the mains supply.

l

Install the isolating switch and make connections required.

Installing in the wall of maximum thickness 380mm.

l

Use the dimensions in fig 1. to mark the wall with the centre 
of the duct hole, the 4 wall fixing positions and the cable inlet.

l

Use the centre line to cut a 115mm dia. hole through the wall 
for the wall tube using a core drill (if replacing the tube of an 
existing 100mm dia. fan ensure the wall tube fits without 
distortion.

l

ENSURE THAT THE DUCT SLOPES DOWN, away from the fan at 
an angle of 3o to allow drainage of any incoming rain water to 
the outside.

l

Drill 4 holes for wall fixings (not supplied), in positions shown 
and fit wall plugs. (see fig 1.)

l

Align the fan in the duct hole and ensure the fan wall box fits 
flat and flush to the wall.

Nuaire Limited

Western Industrial Estate  Caerphilly  United Kingdom  CF83 1NA  

T: 029 2085 8400  F: 029 2085 8444  E: info@nuaire.co.uk  W: www.nuaire.co.uk

NA-SRHR-100

Single Room Heat Recovery Fan

Installation and Maintenance

The EMC Directive 
2004/108/EC  
The Low Voltage 
directive 
2006/95/EC

Figure 1. Wall fixing positions and cable inlet.

1

27. 04. 15 Leaflet Number 671677

Cable
entry

Centre 
line of 
duct

 

 

 

Isolation - Before commencing work 

make sure that the unit is electrically isolated 

from the mains supply. 