background image

5

Leaflet Number 671051 January 2012

Installation and Maintenance

XS Wall Fan Kits

Input Power           Weight

Model

Watts

kg

Max.     Economy

XS9WA  extract

50           37              6.5

Note figures are for extract only

Electrical Specification

230V ~ 50Hz Class I. Motor thermally protected by overload

device. Cable: 1mm max. or min. Fuse: 3 amp (if fan is supplied from

a 5A lighting circuit, no local fuse is required).

Electrical Wiring cont.

XS6WA Consumption and weight

Input Power         Weight

Model

Watts

kg

Max.    Economy

XS6WA extract

38

20

4.7

Note figures are for extract only.

Electrical Specification

230V ~ 50Hz Class I. Motor thermally protected by overload

device. Cable: 1mm max. or min. Fuse: 3 amp (if fan is supplied from

a 5A lighting circuit, no local fuse is required).

XS9WA Consumption and weight

XS12WA Consumption and weight

Input Power          Weight

Model

Watts

kg

Max.   Economy

XS12WA  extract

100        70             9.4

Note figures are for extract only

Electrical Specification

230V ~ 50Hz Class I. Motor thermally protected by overload

device. Cable: 1mm max. or min. Fuse: 3 amp (if fan is supplied from

a 5A lighting circuit, no local fuse is required).

Summary of Contents for XS6WA

Page 1: ...of the push on impeller for cleaning Upward angled interior grille vanes shield workings from view and downward sloping external vanes throw off rain The fan is IP24 splash proof approved with the mot...

Page 2: ...ood t hei ns i deand out s i dewal l s us h wi t h t he s l eeve Tem por ar y Cr os sbr ace A A Install the sleeve at a slight angle lower to outside INSIDE OUTSIDE 1 2 3 5 4 6 7 8 Remove front grille...

Page 3: ...llaries Also see page 8 for details Wall Fixing Plate and Spacer This thin wall application is best covered using a Window Kit Drg shows a Wall Fixing Plate fixed to the aperture by 4 screws The Windo...

Page 4: ...ied electrician in accordance with the wiring regulations Isolation Before commencing work make sure that the unit is electrically isolated from the mains supply 1 2 3 4 Release the electrical panel f...

Page 5: ...ight Model Watts kg Max Economy XS6WA supply extract 38 20 4 7 Note figures are for extract only Electrical Specification 230V 50Hz Class I Motor thermally protected by overload device Cable 1mm max o...

Page 6: ...cover from the grille Fitting Integral Sensors optional Note Before following the pictorial sequence shown first remove the fans front cover grille 2 screws Release the four main corner screws and li...

Page 7: ...Sensors optional The XS MFC Multi Fan Control provides supply or extract variable speed and automatic or manual switching of several fans if desired see note below The control is best mounted approx 1...

Page 8: ...d with each unit 2 Has not been connected to an unsuitable electrical supply The correct supply voltage is shown on the appliance rating label attached to the unit 3 Has not been modified or repaired...

Reviews: