background image

10

31. 08. 21. Document Number  671746

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

BPS (V/T)-ES

Installation Manual

7.0 ELECTRICAL INSTALLATION

The electrical wiring must be carried out by competent persons, in 
accordance with good industry practice and should conform to all 
governing and statutory bodies i.e. IEE, CIBSE etc.

7.1 Main Unit Power Supply

The control is powered by a 400Vac 50Hz 3 phase & Neutral supply. 
This must be isolated local to the unit and fitted with appropriate over-
current and fault protection.

7.2 Electric Heater Power Supply 

For models with electric heating, the heating circuit is powered by 1 or 
2 separate, higher current, 400Vac 50Hz 3 phase & Neutral supplies. 
This must be isolated to the unit and fitted with appropriate over-
current protection. The main supply is still required. Electric heater 
elements are protected by a fail-safe over-temperature switch which 
will disconnect the heater supply if a temperature of 80°C is reached. 
Once the elements cool, the switch will reset but a power cycle is 
required to reset the heater supply contactor.

7.3 Power Supply Details - FLC

Unit Size

Unit (FLC)

Unit with Electric Heater  

(Electric Heater Models Only)

B*07V/**ES

4.3 A

4.3 A + 17.5 A †

B*07T/**ES

8.3 A

8.3 A + 17.5 A †

B*12V/**ES

6.8 A

6.8 A + 35 A †

B*12T/**ES

10.8 A

10.8 A + 35 A †

B*17V/**ES

9.5 A

9.5 A + 52.5 A †

B*17T/**ES

13.5 A

13.5 A + 52.5 A †

B*22V/**ES

10 A

10 A + 52.5 A †

B*22T/**ES

14 A

14 A + 52.5 A †

B*32V/**ES

15 A

15 A + 35 A + 52.5 A ‡

B*32T/**ES

15 A

15 A + 35 A + 52.5 A ‡

B*42V/**ES

19 A

19 A + 52.5 A+ 52.5 A ‡

B*42T/**ES

22.5 A

22.5 A + 52.5 A + 52.5 A ‡

* Denotes any Character. 
† These heater models require a separate power supply for the electric 
heater section, with an appropriate over-current protection device. 
‡ These heater models require two separate power supplies for the 
two (2) electric heater sections, each with an appropriate over-current 
protection device.

7.4 Wiring

All inter-connections between circuit boards, blowers and sensors are 
made at the factory. This diagram only shows the essential field wiring 
points for clarity.

Remove link wire if switched live signal, an enabler or BMS signal is 
connected.

If inlet and outlet dampers are fitted, remove the damper link 
wires. This will allow a 1 minute delay before starting the fans.

7.4.1 Switch Live

Switch Live (SL) terminal - A signal of 100-230V a.c. will activate the 
switch live signal.

Switch Live 2 (SL2) terminal - A signal of 100-230V a.c. will activate the 
switch live 2 (Fan Boost) signal.

A signal from an isolating transformer will produce an 
unpredictable result and is not recommended.

Extra low voltage versions of the switched live signals are also available. 
Link two contacts to activate the signal.

7.4.2 Volt Free Contacts

The volt free contacts are not fused. If these are used to power any 
external equipment, the installer must provide adequate fusing or other 
protections. These contacts are rated at 5A resistive, 0.5A inductive. 
 

Run connections

-   Contacts closed when fan is running.

Fault connections-

 No Fault = contacts are closed. 

 

 

Fault = contacts are opened.

Heat demand

-  

Contacts closed when heating is selected.

 

Thermal Wheel Fault Contacts 14, 15

Supply Filter dP NC Contacts 12, 13

Extract Filter dP NC Contacts 10, 11

Pump Fault Contacts

25 

Volt Free Contact Wiring

Summary of Contents for BPS T-ES

Page 1: ... manufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel burning appliances This appliance should not be used by children or persons with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given super...

Page 2: ...commend a site specific risk assessment by a competent person to determine if any additional PPE is required 2 0 INTRODUCTION The information contained in this document provides details of installation operation and maintenance for installers and users of the BOXER PACKAGED SOLUTION BPS AHU units with heat recovery The BPS AHU range is manufactured from Aluzinc corrosion resistant steel with 50mm ...

Page 3: ... Handed for Vertical PHX Units B AT FE R BPS size Frost Coil Electric 36kW Right Handed for Thermal Wheel Units B AT FE L BPS size Frost Coil Electric 36kW Left Handed for Thermal Wheel Units Frost Coil LPHW 3 B AV FL R BPS size Frost Coil LPHW Right Handed for Vertical PHX Units B AV FL L BPS size Frost Coil LPHW Left Handed for Vertical PHX Units B AT FL R BPS size Frost Coil LPHW Right Handed f...

Page 4: ...uare lifting holes at the end of each side to enable lifting In addition to this covered fork lifting channels are located across the width of the base frame if the module length is sufficient to allow this For shorter modules the fork lifting points will be along the length of the section without a covered channel Figure 3 Only individual modules should be lifted or manoeuvred The units must not ...

Page 5: ...nal time should be allocated For convenience it is preferred that wherever possible this minimum access provision is not adopted and it is recommended that a minimum of around 600mm clearance as stated in ADF 2010 is allowed Where these arrangements are not suitable the Consultant s and Contractor s project specific requirements will always be accommodated where possible 5 1 Hinged Removable Panel...

Page 6: ...ight Hand Thermal Wheel Units SUPPLY SUPPLY CONTROLS Access 600mm Top View 14 Top View of Access For Right Hand Thermal Wheel Units 5 2 Access Areas 5 2 1 Left Hand Plate Heat Exchanger Units Open Extract Open Inlet Open Supply Left Hand Unit Open Exhaust 7 Access For Left Hand Plate Heat Exchanger Units SUPPLY SUPPLY BYPASS CONTROLS Access Top View 600mm 8 Top View of Access For Left Hand Plate H...

Page 7: ...ible for the units failing a site leakage test if the above have not been carried out correctly 6 3 Module Joints After unwrapping temporarily remove the rubber weatherproof cover strip and M10 base frame bolts from any modules and store in a safe location for later use Apply the sealing gasket as necessary to the mating faces of the unit frames Typically the sealing gaskets are pre fitted to the ...

Page 8: ...pment must not be exposed to the weather in an unassembled or partially assembled state All roof terminal ductwork sealing and assembly work must be completed before the unit can be considered weather resistant 6 8 Unit Connections 6 8 1 Ducting Nuaire do not provide ductwork connections with units instead the open ended framework should be utilised Flanged connections are available as an option r...

Page 9: ...out the requirement of removing the roof terminal Figure 22 21 Removing Roof Terminal 22 Actuator Access 6 11 Damper Roof Terminal Assembly The inlet outlet dampers and roof terminals are pre assembled for BPS sizes 07 12 and 17 on a double skinned and insulated panel The panel is easily fitted to the unit with a series of quarter turns provided with a locking key Figure 23 For the larger size BPS...

Page 10: ... B 42T ES 22 5 A 22 5 A 52 5 A 52 5 A Denotes any Character These heater models require a separate power supply for the electric heater section with an appropriate over current protection device These heater models require two separate power supplies for the two 2 electric heater sections each with an appropriate over current protection device 7 4 Wiring All inter connections between circuit board...

Page 11: ...y R Right Hand airflow 7 7 Wiring Diagram Reference Table Unit Size Unit Contains NO Heater Unit Contains LPHW Heater Unit Contains Electric Heater 07 Section 7 8 1 Section 7 8 3 Section 7 8 5 12 Section 7 8 1 Section 7 8 3 Section 7 8 5 17 Section 7 8 2 Section 7 8 4 Section 7 8 6 22 Section 7 8 2 Section 7 8 4 Section 7 8 6 32 Section 7 8 2 Section 7 8 4 Section 7 8 7 42 Section 7 8 2 Section 7 ...

Page 12: ...ard ecosmart Min Trickle 0 1 Test Max SL Runon P w r S ta n d b y F a n 1 F a n 2 H e a ti n g C o o li n g F a u lt F ro s t T x R x 0 24V 15V 0 15V 230V 400V Condensate Pump HX Bypass Relay Heat Exchanger Bypass Board ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF N L1 L2 L3 E Lighting Thermal Wheel 24Vac TR Controls Extract Fan Supply Fan Fan Run Relay HX Bypass...

Page 13: ...ing Fault Frost Tx Rx Extract Fan Board Condensate Pump HX Bypass Relay Lighting Thermal Wheel Transformer 230Vac Supply Fan Contactor Extract Fan Contactor 0 24V 15V 0 15V 230V 400V ecosmart Min Trickle 0 1 Test Max SL Runon Pwr Standby Fan 1 Fan 2 Heating Cooling Fault Frost Tx Rx Fan Run Relay HX Bypass Relay 24Vac Fuse 1 6A Thermal Wheel Fault Contacts NC T14 15 Supply Filter dP Contacts NC T1...

Page 14: ...a n 2 H e a ti n g C o o li n g F a u lt F ro s t T x R x 0 24V 15V 0 15V 230V 400V Condensate Pump HX Bypass Relay Heat Exchanger Bypass Board ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF N L1 L2 L3 E Lighting Thermal Wheel 24Vac TR Controls Extract Fan Supply Fan Fan Run Relay HX Bypass Relay 24Vac Fuse 1 6A Thermal Wheel Fault Contacts NC T14 15 Supply Filter ...

Page 15: ...ate Pump HX Bypass Relay Lighting Thermal Wheel Transformer 230Vac Supply Fan Contactor Extract Fan Contactor 0 24V 15V 0 15V 230V 400V ecosmart Min Trickle 0 1 Test Max SL Runon Pwr Standby Fan 1 Fan 2 Heating Cooling Fault Frost Tx Rx Fan Run Relay HX Bypass Relay 24Vac Fuse 1 6A Thermal Wheel Fault Contacts NC T14 15 Supply Filter dP Contacts NC T12 13 Extract Filter dP Contacts NC T10 11 24Vac...

Page 16: ...ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF N L1 L2 L3 E Lighting Thermal Wheel 24Vac TR Controls Extract Fan Supply Fan Fan Run Relay HX Bypass Relay 24Vac Fuse 1 6A Thermal Wheel Fault Contacts NC T14 15 Supply Filter dP Contacts NC T12 13 Extract Filter dP Contacts NC T10 11 24Vac 0V IO Damper Relay 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP6...

Page 17: ...n 1 Fan 2 Heating Cooling Fault Frost Tx Rx Fan Run Relay HX Bypass Relay 24Vac Fuse 1 6A Thermal Wheel Fault Contacts NC T14 15 Supply Filter dP Contacts NC T12 13 Extract Filter dP Contacts NC T10 11 24Vac 0V IO Damper Relay 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 All internal connetions be...

Page 18: ...4Vac Fuse 1 6A Thermal Wheel Fault Contacts NC T14 15 Supply Filter dP Contacts NC T12 13 Extract Filter dP Contacts NC T10 11 24Vac 0V IO Damper Relay 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolat...

Page 19: ...ill reset but a power cycle is required to reset the heater supply contactor The frost coil is fitted with a burst fired controller with integral set point air off thermistor air in frost stat thermal cut out and contactor The burst fired controller is only enabled if the frost stat reads a frost condition the over temperature cut out is healthy AND a 24vac fan run signal is received from the main...

Page 20: ...ating Cooling Fault Frost TX RX Connector Ecosmart 39 Ecosmart Commissioning Board 9 4 Settings 9 4 1 Maximum Airflow Ensure the power supply is switched off and that a link wire is connected from the supply L to the SL terminal Unplug all items connected to the Net connectors Switch on the power supply Wait for the fan to complete its self test operation Measure the airflow using standard commiss...

Page 21: ...vy duty operation maintenance intervals are to be established by the operator 11 4 Filters When removing the filter access panels pay attention to the airflow direction marked on the panel this must be replaced to the exact position prior to being removed Disposable filters should be checked and changed when they become fully laden with dust Washable filters should be removed and washed in a mild ...

Page 22: ...its or by spraying with a mild detergent solution for grease deposits Solvents strong alkaline acidic or any products that may be aggressive to aluminium or plastics should not be used Do not use cleaning water over 50 C Drain lines should be checked to ensure that they are unobstructed and free draining Traps should be checked that they are fully primed and functioning Drain pans should be flushe...

Page 23: ...and any dust removed Check any thermal wheel belt motor bearings seals and if necessary clean with a soft brush or vacuum cleaner 12 0 WARRANTY The 5 year warranty starts from the day of delivery and includes parts and labour for the first year The remaining period covers replacement parts only This warranty is void if the equipment is modified without authorisation is incorrectly applied misused ...

Page 24: ...rate provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 Local Environment Humidity Ambient humidity the humidity at the unit s installed location shall be within the range 10 to 95 for controls non condensing Air humidity the humidity of the air passing through the unit shall be wit...

Reviews: