BPS (V/T)-ES
Installation Manual
7.6 Wiring
All inter-connections between circuit boards, blowers and sensors are
made at the factory. Remove link wire if switched live signal, an enabler
or BMS signal is connected.
If inlet and outlet dampers are fitted, remove the damper link
wires. This will allow a 1 minute delay before starting the fans.
A series of basic connection wiring diagrams have been provided to
assist on-site wiring. In order to reference the relevant diagrams please
use the code breakdown opposite to determine:
•
Unit size
•
If an electric heater is present
•
If a LPHW heater is present
The below tables can then be used to reference the required connection
and wiring diagrams.
Example:
Unit on site has code
B822V/EN/ES-L.
This indicates a size 22 unit
with electric heating (Section 7.8.6).
7.6.1 Code Description:
B 8 17 V / L R / ES - L
| | | | | | | |
1 2 3 4 5 6 7 8
1. Range:
B
= Boxer Packaged Solution
2. ErP Compliance Year:
8 or No Affix
= 2018
3. Unit Size:
07, 12, 17, 22, 32 or 42
4. Heat Recovery Type:
T
= Thermal Wheel
V
= Vertical Plate Exchanger
5. Heating Type:
E
= Electric
L
= Low Pressure Hot Water (LPHW)
N
= No Heating
6. Cooling Type:
N
= No Cooling
7. Control Type:
ES
= Classic
8. Access Handing
L
= Left Hand
(in direction of supply
R
= Right Hand
airflow)
7.7 Wiring Diagram Reference Table
Unit
Size
Unit Contains
NO Heater
Unit Contains
LPHW Heater
Unit Contains
Electric Heater
07
Section 7.8.1
Section 7.8.3
Section 7.8.5
12
Section 7.8.1
Section 7.8.3
Section 7.8.5
17
Section 7.8.2
Section 7.8.4
Section 7.8.6
22
Section 7.8.2
Section 7.8.4
Section 7.8.6
32
Section 7.8.2
Section 7.8.4
Section 7.8.7
42
Section 7.8.2
Section 7.8.4
Section 7.8.7
7.4.3 Independent Supply & Extract Speed Control
Remove NET link connection for independent speed control.
Damper Connections
Run
Signal
Fault
Signal
Min
Max SL run
on
Trickle Test
0 1
ES-CO2
Connection
BMS
Input
Signal
0-
10
V
0V
Ecosmart
Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
TX
RX
Extract
N
E
L
SL
DP
CL
N
RE
T
Link wire see note*
Heat
Demand Run Fault
Heat Demand
Signal
Damper Link
Volt Free Relay Contacts
Damper Connections
Run
Signal
Fault
Signal
Min
Max SL run
on
Trickle Test
0 1
ES-CO2
Connection
BMS
Input
Signal
0-
10
V
0V
Ecosmart
Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
TX
RX
Extract
N
E
L
SL
DP
CL
N
RE
T
Link wire see note*
Heat
Demand Run Fault
Heat Demand
Signal
Damper Link
Volt Free Relay Contacts
NET Link
26
Speed Control NET Link
7.5 Isolator Wiring Points
Main wiring points for the customer is to the isolators situated on
the sides of the units as shown below. Cable glands are for additional
ancillary cabling and are located on the sides of the units.
Unit
Isolator
Electric Heater
Isolator
27
Isolator Locations
28
Cable Gland Locations