background image

11

31. 08. 21. Document Number  671746

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

BPS (V/T)-ES

Installation Manual

7.6 Wiring

All inter-connections between circuit boards, blowers and sensors are 
made at the factory. Remove link wire if switched live signal, an enabler 
or BMS signal is connected.

If inlet and outlet dampers are fitted, remove the damper link 
wires. This will allow a 1 minute delay before starting the fans. 

A series of basic connection wiring diagrams have been provided to 
assist on-site wiring. In order to reference the relevant diagrams please 
use the code breakdown opposite to determine:

Unit size

If an electric heater is present

If a LPHW heater is present

The below tables can then be used to reference the required connection 
and wiring diagrams.

Example: 
Unit on site has code 

B822V/EN/ES-L. 

This indicates a size 22 unit 

with electric heating (Section 7.8.6).

7.6.1 Code Description: 

B 8 17 V / L R / ES - L

|   |   |   |     |  |      |      |

1  2  3 4    5 6     7    8

1. Range:  

 

= Boxer Packaged Solution

2. ErP Compliance Year: 

8  or No Affix

 = 2018

3. Unit Size: 

 

07, 12, 17, 22, 32 or 42

4. Heat Recovery Type:  

T

 = Thermal Wheel 

  

 

V

 = Vertical Plate Exchanger

5. Heating Type:   

E

 = Electric 

  

 

= Low Pressure Hot Water (LPHW) 

  

 

N

 = No Heating

6. Cooling Type: 

 

N

 = No Cooling 

 

7. Control Type: 

 

ES

 = Classic

8. Access Handing   

L

 = Left Hand 

(in direction of supply  

= Right Hand 

airflow)

7.7 Wiring Diagram Reference Table

Unit 

Size

Unit Contains 

NO Heater

Unit Contains 
LPHW Heater

Unit Contains  

Electric Heater

07

Section 7.8.1

Section 7.8.3

Section 7.8.5

12

Section 7.8.1

Section 7.8.3

Section 7.8.5

17

Section 7.8.2

Section 7.8.4

Section 7.8.6

22

Section 7.8.2

Section 7.8.4

Section 7.8.6

32

Section 7.8.2

Section 7.8.4

Section 7.8.7

42

Section 7.8.2

Section 7.8.4

Section 7.8.7

7.4.3 Independent Supply & Extract Speed Control

Remove NET link connection for independent speed control.

 

Damper Connections

Run 

Signal

Fault 

Signal

Min 

Max      SL run 

  

           on

Trickle            Test

0         1

ES-CO2

Connection

BMS

Input

Signal

0-

10

V

0V

Ecosmart

Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
TX
RX

Extract

N

E

L

SL

DP

CL

N

RE

T

Link wire  see note*

Heat

Demand   Run        Fault

Heat Demand 

Signal

Damper Link

Volt Free Relay Contacts

Damper Connections

Run 

Signal

Fault 

Signal

Min 

Max      SL run 

  

           on

Trickle            Test

0         1

ES-CO2

Connection

BMS

Input

Signal

0-

10

V

0V

Ecosmart

Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
TX
RX

Extract

N

E

L

SL

DP

CL

N

RE

T

Link wire  see note*

Heat

Demand   Run        Fault

Heat Demand 

Signal

Damper Link

Volt Free Relay Contacts

NET Link

26 

Speed Control NET Link

7.5 Isolator Wiring Points

Main wiring points for the customer is to the isolators situated on 
the sides of the units as shown below. Cable glands are for additional 
ancillary cabling and are located on the sides of the units.

 
 

Unit  

Isolator

Electric Heater 

 Isolator

27 

Isolator Locations

 
 

28 

Cable Gland Locations

Summary of Contents for BPS T-ES

Page 1: ... manufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel burning appliances This appliance should not be used by children or persons with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given super...

Page 2: ...commend a site specific risk assessment by a competent person to determine if any additional PPE is required 2 0 INTRODUCTION The information contained in this document provides details of installation operation and maintenance for installers and users of the BOXER PACKAGED SOLUTION BPS AHU units with heat recovery The BPS AHU range is manufactured from Aluzinc corrosion resistant steel with 50mm ...

Page 3: ... Handed for Vertical PHX Units B AT FE R BPS size Frost Coil Electric 36kW Right Handed for Thermal Wheel Units B AT FE L BPS size Frost Coil Electric 36kW Left Handed for Thermal Wheel Units Frost Coil LPHW 3 B AV FL R BPS size Frost Coil LPHW Right Handed for Vertical PHX Units B AV FL L BPS size Frost Coil LPHW Left Handed for Vertical PHX Units B AT FL R BPS size Frost Coil LPHW Right Handed f...

Page 4: ...uare lifting holes at the end of each side to enable lifting In addition to this covered fork lifting channels are located across the width of the base frame if the module length is sufficient to allow this For shorter modules the fork lifting points will be along the length of the section without a covered channel Figure 3 Only individual modules should be lifted or manoeuvred The units must not ...

Page 5: ...nal time should be allocated For convenience it is preferred that wherever possible this minimum access provision is not adopted and it is recommended that a minimum of around 600mm clearance as stated in ADF 2010 is allowed Where these arrangements are not suitable the Consultant s and Contractor s project specific requirements will always be accommodated where possible 5 1 Hinged Removable Panel...

Page 6: ...ight Hand Thermal Wheel Units SUPPLY SUPPLY CONTROLS Access 600mm Top View 14 Top View of Access For Right Hand Thermal Wheel Units 5 2 Access Areas 5 2 1 Left Hand Plate Heat Exchanger Units Open Extract Open Inlet Open Supply Left Hand Unit Open Exhaust 7 Access For Left Hand Plate Heat Exchanger Units SUPPLY SUPPLY BYPASS CONTROLS Access Top View 600mm 8 Top View of Access For Left Hand Plate H...

Page 7: ...ible for the units failing a site leakage test if the above have not been carried out correctly 6 3 Module Joints After unwrapping temporarily remove the rubber weatherproof cover strip and M10 base frame bolts from any modules and store in a safe location for later use Apply the sealing gasket as necessary to the mating faces of the unit frames Typically the sealing gaskets are pre fitted to the ...

Page 8: ...pment must not be exposed to the weather in an unassembled or partially assembled state All roof terminal ductwork sealing and assembly work must be completed before the unit can be considered weather resistant 6 8 Unit Connections 6 8 1 Ducting Nuaire do not provide ductwork connections with units instead the open ended framework should be utilised Flanged connections are available as an option r...

Page 9: ...out the requirement of removing the roof terminal Figure 22 21 Removing Roof Terminal 22 Actuator Access 6 11 Damper Roof Terminal Assembly The inlet outlet dampers and roof terminals are pre assembled for BPS sizes 07 12 and 17 on a double skinned and insulated panel The panel is easily fitted to the unit with a series of quarter turns provided with a locking key Figure 23 For the larger size BPS...

Page 10: ... B 42T ES 22 5 A 22 5 A 52 5 A 52 5 A Denotes any Character These heater models require a separate power supply for the electric heater section with an appropriate over current protection device These heater models require two separate power supplies for the two 2 electric heater sections each with an appropriate over current protection device 7 4 Wiring All inter connections between circuit board...

Page 11: ...y R Right Hand airflow 7 7 Wiring Diagram Reference Table Unit Size Unit Contains NO Heater Unit Contains LPHW Heater Unit Contains Electric Heater 07 Section 7 8 1 Section 7 8 3 Section 7 8 5 12 Section 7 8 1 Section 7 8 3 Section 7 8 5 17 Section 7 8 2 Section 7 8 4 Section 7 8 6 22 Section 7 8 2 Section 7 8 4 Section 7 8 6 32 Section 7 8 2 Section 7 8 4 Section 7 8 7 42 Section 7 8 2 Section 7 ...

Page 12: ...ard ecosmart Min Trickle 0 1 Test Max SL Runon P w r S ta n d b y F a n 1 F a n 2 H e a ti n g C o o li n g F a u lt F ro s t T x R x 0 24V 15V 0 15V 230V 400V Condensate Pump HX Bypass Relay Heat Exchanger Bypass Board ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF N L1 L2 L3 E Lighting Thermal Wheel 24Vac TR Controls Extract Fan Supply Fan Fan Run Relay HX Bypass...

Page 13: ...ing Fault Frost Tx Rx Extract Fan Board Condensate Pump HX Bypass Relay Lighting Thermal Wheel Transformer 230Vac Supply Fan Contactor Extract Fan Contactor 0 24V 15V 0 15V 230V 400V ecosmart Min Trickle 0 1 Test Max SL Runon Pwr Standby Fan 1 Fan 2 Heating Cooling Fault Frost Tx Rx Fan Run Relay HX Bypass Relay 24Vac Fuse 1 6A Thermal Wheel Fault Contacts NC T14 15 Supply Filter dP Contacts NC T1...

Page 14: ...a n 2 H e a ti n g C o o li n g F a u lt F ro s t T x R x 0 24V 15V 0 15V 230V 400V Condensate Pump HX Bypass Relay Heat Exchanger Bypass Board ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF N L1 L2 L3 E Lighting Thermal Wheel 24Vac TR Controls Extract Fan Supply Fan Fan Run Relay HX Bypass Relay 24Vac Fuse 1 6A Thermal Wheel Fault Contacts NC T14 15 Supply Filter ...

Page 15: ...ate Pump HX Bypass Relay Lighting Thermal Wheel Transformer 230Vac Supply Fan Contactor Extract Fan Contactor 0 24V 15V 0 15V 230V 400V ecosmart Min Trickle 0 1 Test Max SL Runon Pwr Standby Fan 1 Fan 2 Heating Cooling Fault Frost Tx Rx Fan Run Relay HX Bypass Relay 24Vac Fuse 1 6A Thermal Wheel Fault Contacts NC T14 15 Supply Filter dP Contacts NC T12 13 Extract Filter dP Contacts NC T10 11 24Vac...

Page 16: ...ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF ABB 0 0FF N L1 L2 L3 E Lighting Thermal Wheel 24Vac TR Controls Extract Fan Supply Fan Fan Run Relay HX Bypass Relay 24Vac Fuse 1 6A Thermal Wheel Fault Contacts NC T14 15 Supply Filter dP Contacts NC T12 13 Extract Filter dP Contacts NC T10 11 24Vac 0V IO Damper Relay 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP6...

Page 17: ...n 1 Fan 2 Heating Cooling Fault Frost Tx Rx Fan Run Relay HX Bypass Relay 24Vac Fuse 1 6A Thermal Wheel Fault Contacts NC T14 15 Supply Filter dP Contacts NC T12 13 Extract Filter dP Contacts NC T10 11 24Vac 0V IO Damper Relay 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 All internal connetions be...

Page 18: ...4Vac Fuse 1 6A Thermal Wheel Fault Contacts NC T14 15 Supply Filter dP Contacts NC T12 13 Extract Filter dP Contacts NC T10 11 24Vac 0V IO Damper Relay 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolator L1 E L2 L3 N L1 L2 L3 N T1 T2 T3 N 1 2 3 4 400V 3ph 50Hz Main Power Supply Overcurrent Protection By Others Local Rotary Lockable IP66 67 Isolat...

Page 19: ...ill reset but a power cycle is required to reset the heater supply contactor The frost coil is fitted with a burst fired controller with integral set point air off thermistor air in frost stat thermal cut out and contactor The burst fired controller is only enabled if the frost stat reads a frost condition the over temperature cut out is healthy AND a 24vac fan run signal is received from the main...

Page 20: ...ating Cooling Fault Frost TX RX Connector Ecosmart 39 Ecosmart Commissioning Board 9 4 Settings 9 4 1 Maximum Airflow Ensure the power supply is switched off and that a link wire is connected from the supply L to the SL terminal Unplug all items connected to the Net connectors Switch on the power supply Wait for the fan to complete its self test operation Measure the airflow using standard commiss...

Page 21: ...vy duty operation maintenance intervals are to be established by the operator 11 4 Filters When removing the filter access panels pay attention to the airflow direction marked on the panel this must be replaced to the exact position prior to being removed Disposable filters should be checked and changed when they become fully laden with dust Washable filters should be removed and washed in a mild ...

Page 22: ...its or by spraying with a mild detergent solution for grease deposits Solvents strong alkaline acidic or any products that may be aggressive to aluminium or plastics should not be used Do not use cleaning water over 50 C Drain lines should be checked to ensure that they are unobstructed and free draining Traps should be checked that they are fully primed and functioning Drain pans should be flushe...

Page 23: ...and any dust removed Check any thermal wheel belt motor bearings seals and if necessary clean with a soft brush or vacuum cleaner 12 0 WARRANTY The 5 year warranty starts from the day of delivery and includes parts and labour for the first year The remaining period covers replacement parts only This warranty is void if the equipment is modified without authorisation is incorrectly applied misused ...

Page 24: ...rate provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 Local Environment Humidity Ambient humidity the humidity at the unit s installed location shall be within the range 10 to 95 for controls non condensing Air humidity the humidity of the air passing through the unit shall be wit...

Reviews: