background image

Isolation - Before commencing work make sure that 

the unit and Nuaire control are electrically isolated 

from the mains supply.

5

.0 Wiring

Wiring Connections for units with Ecosmart Control.

 

Wiring for units with No Heater 

Fig 16: 

Wiring for units with LPHW 

Fig 17: 

Installation, Operating and Maintenance Instructions

Standby

Fan1

Fan 2

Heating

Cooling

Fault

Frost

Tx

Rx

PWR

Min

Max

SL

Run-On

Trickle

0

1

650462

(830109)

Test

P IN

E

V I

R

D

  V

N

I

0V

0-10V

18V

EN2

EN1

0V

0-10V

BK

WHT

RED

0V

0-10V

18V

0V

0-10V

T

E

S

T

N

I

O

P

N

I     2

O

C

BMS

FAULT

RUN

DAMPER

OP

CL

N

RET

SUPPLY

N

L

SL

Note:
Customer connections

for fan and control.
5amp draw max.

INV DRIVE

EN2

EN1

0V

0-10V

BK

WHT

RED

0V

0-10V

18V

0V

0-10V

SET POINT

CO2 IN

BMS

HEAT SENS

FAULT

RUN

HEAT DEMAND

DAMPER

OP

CL

N

RET

SUPPLY

N

E

L

SL

Net Ecosmart

P IN

0V

0-10V

18V

Standby

Fan1

Fan 2

Heating

Cooling

Fault

Frost

Tx

Rx

PWR

Min

Max

SL

Run-On

Trickle

0

1 650462 (830109)

Test

1

2

3

4

5

6

7

8

9

10

11

12

13

14

24v

24v

O/P 1

O/P 1

O/P 1

T8109C

T8109C

Honeywell

T8078C

DX

COIL

COOL

DEMAND

DX-1

FROST ALARM

DX-2

INLET

SENSOR

OUTLET

SENSOR

HEATING CONTROLCOOLING CONTROL

0V

SETPOINT0-10V

10V

0V

DEADBAND

0-10V

10V

AUTO

HEAT/COOL

OFF

ON

COOL

SENSOR

ACTUATOR CONTROL (WHITE)

ACTUATOR CONTROL (BLACK)

ACTUATOR CONTROL (RED)

Note:

Customer connections

for fan and control.

5amp draw max.

6

18. 10. 17. Leaflet Number 671679

Notes: Local isolator (by others)

All inter-connections between circuit boards, blowers and sensors are made at the factory.
Remove link wire if switched live signal, an enabler or BMS signal is connected.

Notes: Local isolator (by others)

All inter-connections between circuit boards, blowers and sensors are made at the factory.
Remove link wire if switched live signal, an enabler or BMS signal is connected.

FROST PROTECTION (LPHW) NOTE:

Ecosmart frost protection is activated when the outlet

air of the unit is 4

o

C or below, when this temperature is reached, the unit reacts by shutting

down the fan to prevent a ‘wind chill’ effect reducing the temperature to a point whereby
the coil could freeze and burst. The unit will also drive open the LPHW valve to a fully open
position to allow full water flow through the coil and the main PCB will close the ‘Heat
demand’ contacts. These contacts could be used to send a signal to activate the boiler and/
or valve to open to provide heat if not already doing so.

DAVE Supply Fans (ES Models) 50/60Hz

Summary of Contents for DAVE Series

Page 1: ... are manufactured from aluzinc rectangular in section and have circular rigid spigots at each end All units are supplied with fixing brackets designed to simplify installation 1 0 Fan Unit Coding Descriptions 2 0 Handling Always handle the units carefully to avoid damage and distortion Care must be taken to ensure any slings used for hoisting do not damage the casing or the control module componen...

Page 2: ...5 190 DS3A EES H 1005 780 345 200 430 155 155 DS4A NES H 1005 840 370 250 370 150 100 DS4A LES H 1005 840 370 250 430 175 190 DS4A EES H 1005 840 370 250 430 155 155 DS4HA NES H 1005 840 370 250 370 150 100 DS4HA LES H 1005 840 370 250 430 175 190 DS4HA EES H 1005 840 370 250 430 155 155 DS5A NES H 1155 1110 1110 984 410 315 370 150 100 DS5A LES H 1155 984 410 315 430 175 190 DS5A EES H 1155 984 4...

Page 3: ...valve to a fully open position to allow full water flow through the coil and the main PCB will close the Heat demand contacts These contacts could be used to send a signal to activate the boiler and or valve to open to provide heat if not already doing so 4 1 2 Port Pressure Independent Balancing Control Valve Setting Instruction Fig 6 Remove Actuator Fig 7 Unlock Adjusting Collar Units 1 2 2H DN2...

Page 4: ...el details Note A Commissioning Procedure document leaflet No 671153 is available on request from Nuaire Tel 029 2088 5911 The Control Module Fig 12 The BMS connection is made with a plug in connector via the socket See figure 13 To ensure the connection is made only by suitably qualified and authorised personnel the plug is not supplied It is available from R S Components Part No 403 875 or Farne...

Page 5: ...ater Neutral Thermistor T Thermistor R Signal 0V Signal VE OIP 5V Note Customer connections for electric heater 40amp draw E N L L N E Heater Temperature Settings Note Customer connections for fan and control 5amp draw max 5 18 10 17 Leaflet Number 671679 Notes Local isolator by others All inter connections between circuit boards blowers and sensors are made at the factory Remove link wire if swit...

Page 6: ...OL COOLING CONTROL 0V SETPOINT 0 10V 10V 0V DEADBAND 0 10V 10V AUTO HEAT COOL OFF ON COOL SENSOR ACTUATOR CONTROL WHITE ACTUATOR CONTROL BLACK ACTUATOR CONTROL RED Note Customer connections for fan and control 5amp draw max 6 18 10 17 Leaflet Number 671679 Notes Local isolator by others All inter connections between circuit boards blowers and sensors are made at the factory Remove link wire if swi...

Page 7: ...nce Ensure all control components are secure and clean refit the cover Lubrication Motors are fitted with sealed for life bearings and do not require any lubrication Filter care replacement The filter where applicable will require cleaning on a regular basis The frequency of the cleaning operation will depend on the site conditions 7 0 Fan Components see fig 18 Key Components A Lid Base B Attenuat...

Page 8: ...es office for further details 9 0 Spares for Dave Supply fans Spare parts and replacement components are available from Nuaire Ltd Please contact us on the numbers below for further details G4 Filter Unit Size Replacement Part No DS1A ES D1A G4FILTERKIT DS2A ES D2A G4FILTERKIT DS2HA ES D2HA G4FILTERKIT DS3A ES D3A G4FILTERKIT DS4A ES D3A G4FILTERKIT DS4HA ES D4HA G4FILTERKIT DS5A ES D5A G4FILTERKI...

Page 9: ...nged so as not to bear on the casing 3 3 Equipment stored on site prior to installation should be protected from the weather and steps taken to prevent ingress of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified operational limits for the equipment are adhered to e g operational air temperature air borne contaminants and unit orientation 4 2 Where installation accessories...

Reviews: