background image

Set point 

adjuster screw

Small screwdriver

Note colour 

code guide 

label when 

fitting

Backplate

(rear view)

10m sensor connection

wire (supplied).

Clearance aperture for wire

should be approx 20mm dia

to allow passage of plug end.

Allow approx 75mm of wire 

through for fitting to the 

backplate

Wire can be located behind

a wall panel or fixed to wall 

surface.

Plug end

Before fixing the backplate 

to the wall,  fit the plug end 

from sensor body into the 

backplate.  

Note that colour coded 

connections are matching 

Sensor can now clip onto 

backplate

Wall

To fan connector  

box terminal  

marked NET

Fixing screws supplied

IMPORTANT! Please refer to the 

installation instructions of the fan to

check the compatibility of this sensor.

Parts check list:

l

ES-TEMP Temperature Sensor

l

1 off 10 metre length of plugged 

SELV cable

ES-TEMP Temperature Sensor

Designed to be compatible with the Ecosmart

system, this temperature sensor unit is

supplied with a pre-plugged, 10 metre length

of communications cable. 

Note: longer

lengths are available if required.

The sensor operates with Safe Extra Low

Voltage (SELV) with power supplied from

the fan unit via the communications cable.

The ES-TEMP Sensor will vary the ventilation

rate automatically according to the 

measured temperature.

Fault indication

The LED will change from green to red if

any fan connected in that zone has failed.

Multiple Sensors

Multiple sensors can be connected to the

network. Please refer to the actual fan

installation instructions for exact 

quantities.

Installing the Sensor

The sensor unit should be installed away

from any direct source of heat (e.g. 

radiators) and areas where it would be

subjected to waterspray.

The Sensor is supplied complete with 

10 metres of connecting cable with plugs

attached. Sensors are also supplied with all

fixings and are clipped into a backplate wall

mounting bracket. 

a) Fix one end of the 10m cable to the fans 

customer connection box (connection 

sockets marked NET).

b) Select a suitable location for the sensor 

and arrange the cable in position. Leave 

approx. 75mm of the cable free at the

mounting point to ease the connection 

of the plug. (fig. 1).

c) Carefully separate the sensor from the 

backplate using a small screwdriver 

(see Fig 2)  

Note: the sensor will remain 

connected by its internal cable.

d) Release this cable from the bracket by 

simply pulling the plug off the socket pins 

in the backplate.

e) Before fixing the backplate to the wall, 

connect the wall fixed cable end plug to 

the upper set of pins on the bracket (fig 3)

N

ote: check the colour code matching

on

when fitting the plug onto the pins. 

Arrange the cable to lay in the cable slot 

at the top of the backplate moulding and 

fix the bracket to the wall surface using 

the screws supplied. 

f) The sensor plug can now be connected 

into the backplate N

ote: check the colour

code matching

when fitting the plug onto

the pins.

Clip the sensor body in the backplate arms

and adjust the sensor body to the desired

position.

Data cable installation

A 4-core SELV data cable is used to 

connect devices. 

Do not run data cable in the same conduit

as the mains cables and ensure there is a

50mm separation between the data cable

and other cables. The maximum cable run

between any two devices is 300m when it

is installed in accordance with the 

instructions.

Please note that the total data cable length

used in any system must be less than

1000m. Keep the number of cable joints to 

a minimum to ensure the best data 

transmission efficiency between devices.

Adjusting the sensor set points

Adjustable temperature setting 10 -35 

o

C

Assuming the sensor(s) are installed,

adjustment of the set points achieved by

tilting the sensor forwards which exposes

the adjustment aperture (see fig 5). 

Using a small screwdriver, gently turn the

dial either clockwise or anti-clockwise to

increase or decrease the set point.

When adjustments are made to the sensor,

the LED light on the sensor front will flash

on and off to show the set point. First,

green flashes will indicate the set point in

TENS, then red flashes will indicate UNITS.

For example 2 green flashes and three 

red flashes show a temperature set point 

of 23 

o

C.

ES-TEMP 

Temperature Sensors

Installation Guide

Figure 1.

Figure 2.

Figure 3.

Figure 4.

Figure 5.

Nuaire Limited

Western Industrial Estate  Caerphilly  United Kingdom  CF83 1NA  

T: 029 2085 8400  F: 029 2085 8444  E: info@nuaire.co.uk  W: www.nuaire.co.uk

03. 07. 15. Leaflet Number 671128

The EMC Directive 

2004/108/EC     

The Low Voltage 

directive 

2006/95/EC

Reviews: