background image

10

nuaire.co.uk 

029 2085 8400

13. 03. 19. Document Number  671188

Installation and Maintenance

Ecosmart Boxer Air Handling Units

The system’s response to a 0-10V dc BMS signal is given in the table 
below.

Note the BMS signal will override any sensors and user control 
connected in the system. The voltage tolerance is +/- 125mV and is 
measured at the fans terminal.

*Only available on relevant unit.

Ventilation 

Mode

Cooling 

Mode*

Heating 

Mode*

Local Control

0.00

-

-

OFF/ Trickle

0.25

-

-

Speed 1

0.50

0.75

1.00

Speed 2

1.50

1.75

2.00

Speed 3

2.50

2.75

3.00

Speed 4

3.50

3.75

4.00

Speed 5

4.50

4.75

5.00

Speed 6

5.50

5.75

6.00

Speed 7

6.50

6.75

7.00

Speed 8

7.50

7.75

8.00

Speed 9

8.50

8.75

9.00

Speed 10

9.50

9.75

10.00

4.1.10 LPHW Actuator Connections

LPHW actuator connection (unit sizes 3-7) must be made between the 
control and LPHW modules, using link wire provided.

Note: Actuator wiring can change dependent on direction of 
operation (Figure 23 & Figure 24).

Direction 
of Operation

Direction 
of Operation

WHITE

BROWN

GREEN

WHITE

BROWN

GREEN

BLU

BRN

BLU
BRN

BLK

BLK

Figure 23.  

Figure 25.  

Figure 24.  

5.0 Setting to Work

5.1 Electrical

5.1.1 Test Button

The test button allows the blower within the unit to be checked for its 
operation. If the fan is running already, press the button once to stop 
the fan, press again to switch on the fan.

Note that the fan will return to normal operation after 30 seconds.

MIN

MAX

 

=  Minimum speed adjustment

 

=  Maximum speed 

LED indicators

Max     SL run on

Min         

adjustment  SL   

Run on  =  Switched Live Run-On      

Timer adjustment

TRICKLE  =  Selects trickle running:   

    0 = off,  1 = selected

TEST 

=  Test button

Trickle

Test

1

0        

Pwr
Standby
Fan 1
Fan 2
Heating
Cooling
Fault
Frost
Tx
Rx

Ecosmart

Connector

5.1.2 LED Indication (Figure 25)

PWR  

 

GREEN: Power on & OK. 

STANDBY 

 

LED on when fan is not running. 

FAN 1  

 

GREEN: Fan 1 is running, RED: Fan 1 faulty. 

FAN 2  

 

GREEN: Fan 2 is running, RED: Fan 2 faulty. 

HEATING* 

 

GREEN: Heating selected 

COOLING* 

 

Not applicable, see note. 

Fault 

 

 

LED on when a fault is present on unit. 

Frost* 

   

Not applicable, see note. 

Tx 

 

 

LED on when the controller is transmitting data. 

Rx 

 

 

LED on when the controller is receiving data.

*Note that the control panel is common to all the Ecosmart products 
and will have indicators for functions that are not available in this 
particular fan. However these indicators will not be illuminated.

5.1.3 Maximum Airflow Rate

Ensure the power supply is switched off and that a link wire is 
connected from the supply L to the SL terminal. Unplug all items 
connected to the ‘Net’ connectors.

Switch on the power supply.

Wait for the fan to complete its self-test operation. Measure the 
airflow using standard commissioning instruments at a suitable 
point in the ductwork. If adjustment is required, rotate the pot 
marked ‘MAX’ to obtain the desired airflow. Remove the link wire if 
not required - see “wiring (c)”.

5.1.4 Maximum/Trickle Airflow Rate (Nominal: 40% Sizes 1 & 2; 
20% Sizes 3 to 7)

Repeat the same procedure as for maximum airflow above but 
without the link wire between supply L and SL terminal. Ensure the 
trickle switch is in the ‘ON’ position. Adjustment must be made on 
the pot marked ‘Min’.

Note that the minimum setting (nominally 40%) must be 
below the maximum setting, or the minimum setting will be 
automatically set to be the same as the maximum. 

The minimum speed set is the trickle speed at which the fan 
operates.

Note: The working speed range of the user control and sensors is 
between the minimum and maximum set points.

5.2 Mechanical

Wet systems require the setting of the flow valve. Set as general 
commissioning procedures - refer to the specified design flow 
duties and the documentation attached to each valve.

Frost protection must be incorporated on shut down and 
fresh air conditions to avoid the coil and associated pipework 
freezing. Ideally, where the system is at risk of frost damage, 
the addition of a proprietary antifreeze solution to the water is 
recommended.

DX coils have two separate cooling stages with independent 
condenser units, the coils are supplied with ends sealed. 
Connection, commissioning and setting to work is the 
responsibility of the condensing unit installer

Summary of Contents for ESBH Series

Page 1: ...t Terminals Weathering Roof Sensors User controls For systems which include supply fans with heating and or cooling coils other than where the BMS has control the appropriate user control is required...

Page 2: ...etised Forklift Slings via spreaders fitted to unit with base frame Figure 2 Figure 3 Figure 4 2 0 HANDLING Upon receipt of the equipment an inspection should be made and before commencement of liftin...

Page 3: ...equired install on a secure and level surface use the base frame and the weather roof tailored for each system Connect ducting inlet or extract cowls as appropriate 3 2 5 Wet Pipe Connections 3 2 Asse...

Page 4: ...erse effect on lighting etc There are no inrush starting currents quoted because the Ecosmart control incorporates a soft starting speed control feature The inverters are pre set to match the fan heat...

Page 5: ...itted DX2 coil Signal for if fitted 25 30 2 5 Set air off of LPHW coil temperature 0V 0 10V BMS signal Connections to Damper N L SL DP CL N RET Remove this link wire if NET connections for ECOSMART de...

Page 6: ...n 2 Heating Cooling Fault Frost Tx Rx Ecosmart signal Heat demand Run signal Fault signal DAMPER FAULT RUN HEAT DEMAND L3 L2 L1 N E 400V 50Hz 3ph N mains supply for fan 5 6 3 1 4 2 U V W E L1 L2 L3 U...

Page 7: ...1 15 13 14 12 9 7 5 8 6 10 11 15 12 14 13 CONTACTER A1 A2 ON OFF AUTO HEATER COOL Cooling signal demand Frost alarm signal DX1 coil Signal for if fitted Signal for DX2 coil if fitted 25 3 0 25 Set air...

Page 8: ...15 13 14 12 CONTACTER A1 A2 ON OFF AUTO HEATER COOL Cooling signal demand Frost signal alarm DX1 coil Signal for if fitted DX2 coil Signal for if fitted Connect to inlet sensor after unit is assemble...

Page 9: ...e as Data cable installation Keep the cable run as short as possible and less than 50 metres 4 1 9 BMS Input Signals The BMS connection is made with a plug in connector via the socket Figure 22 To ens...

Page 10: ...hen a fault is present on unit Frost Not applicable see note Tx LED on when the controller is transmitting data Rx LED on when the controller is receiving data Note that the control panel is common to...

Page 11: ...lt Tension Size 7 All belt drive units incorporate belt tensioning devices To adjust the belt tension slacken the pinch bolt on the sides of the motor plate Turn the adjusting bolt clockwise to tighte...

Page 12: ...s of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified operational limits for the equipment are adhered to e g operational air temperature air borne contaminants and unit orie...

Reviews: