Isolation - Before commencing work make sure

that the unit and Nuaire control are electrically

isolated from the mains supply.

Fig 3. Dimensions.

using appropriate fixings.  During the operation, connect

the outlet spigot to the ductwork, if applicable, and feed the

electrical cables through the grommets into the connection

recess. 

Wire the supply and the remote switch into the unit 

terminal strips (see wiring diagrams fig 4).

Setting the thermostat

The thermostat control knob is located on the top face of

the unit.  Advance the thermostat control knob through the

ambient room temperature position (you can detect this as

a gentle click around 20

o

C position). Set the control in

excess of the ‘click’. This will trigger the fan to operate on

boost when the room temperature increases.

When the ambient room temperature increases beyond the

chosen thermostat set point, the unit will automatically

switch to the boost speed -the auto boost speed factory

set at HIGH (full) but can be changed to LOW (half) by 

relocating a link on the circuit board. (See wiring in Fig. 4).

Electrical connection

The installation must be carried out by a suitably qualified

and competent person and conform to all relevant 

regulations.

The electrical supply to the unit must be isolated by a 

suitable local double-pole isolating switch (by others) for

maintenance purposes.

Note that the mains wiring for the unit MUST be from a

fixed wiring installation.

The unit MUST be earthed.

Connect the incoming supply to the mains terminals.

Connect the remote control switch (six wires 0.5mm

2

500V

ac rated) ensuring connections match at the switch.

Replace cover plate.

Testing after installation

Manual operation

Set the remote switch to MANUAL and HIGH.

Check the unit is functioning satisfactorily by switching on

the mains supply. 

The unit should start and run on the HIGH  (full speed)

Select LOW speed and check for LOW (half speed) operation.

Switch off the mains supply.

Automatic operation

Select AUTO on the remote switch. In this mode the unit is

controlled by the integral thermostat. See ‘Setting the 

thermostat’

The fan will run continuously providing a ‘trickle 

ventilation’. 

Reducing the thermostat control setting temporarily will

trigger the fan for test purposes.

The fan should switch to the boost speed.

Reset the thermostat as detailed in previous paragraphs. 

2

16. 06. 15. Leaflet Number 671116

Installation and Maintenance

HPKF High Performance Kitchen Fan