Installation and Maintenance

mrXbox90S Mechanical Ventilation with Heat Recovery

5.0 Installation 

Installation must be carried out by competent personnel in 

accordance with the appropriate authority and conforming to all

statutory and governing regulations.

All mains wiring must be in accordance with the current I.E.E.

Regulations, or the appropriate standards. 

Ensure that the mains supply (Voltage, Frequency and Phase) 

complies with the rating label. It is recommended that the connection

to the unit is made with flexible cable.

The unit must be fitted indoors, away from any direct sources of heat,

water spray or moisture generation.

The units condensate drain must be connected to the building foul

water drainage system.

If an extract grille associated with the unit is sited in a room containing

a fuel burning unit, the installer must ensure that air replacement is

adequate for both units. Also ensure that the units external grilles are

located at least 600mm away from any flue outlet.

If the ductwork passes through an unheated loft void or similar

location, it should be insulated.

Certain applications may require the installation of sound attenuation

to achieve the sound levels required.

Unit installation procedure can be summarised as 
follows:

1.  Placing the unit (5.1)

2.  Connecting the ducts (5.2)

3.  Connecting the condensate discharge (5.3)

4.  Electric wiring diagram:

connecting the multiple switch and, if necessary, the power 

supply (5.4)

The mrXbox90s must be installed in accordance with:

•  the regulations for ventilation of dwellings and residential 

buildings

•  the safety regulations for low-voltage installations (current 

IEE regulations)

•  the regulations for connection to interior sewers in dwellings 

and residential buildings

• any additional regulations of the local utilities

• the installation instructions for the mrXbox90s 

5.1 Placing the unit

The mrXbox90S can be directly mounted to the wall using the 

suspension strips supplied for that purpose. For a vibration-free

result the unit must be mounted to a solid wall with a minimum mass

of 200kg/m

2

. (NB: a gypsum block or metal stud wall does not 

suffice. Additional measures such as double panelling or extra studs

are required).

•  the unit must be placed level

•  the installation room must be such that a good condensate 

dis charge with air trap and pitch for condensate can be made

•  the installation room must be frost-free

•  make sure there is a free space of at least 70cm at the front of

the unit and a free headroom of 1.8m for cleaning the filters 

and carrying out maintenance

5.2 Connecting ducts

The air outlet duct does not have to be fitted with a control valve; the

unit itself controls the air quantities.

To prevent condensation on the outside of the outside air inlet duct

and the air outlet duct from the mrXbox90S, these ducts must be 

insulated externally vapour-proof as far as the unit.

Pay attention to crosstalk and installation noise, also for incorporated

ducts. Design the duct with separate branches to the valve to prevent

crosstalk. if necessary, the input ducts must be insulated, for instance

when they are installed outside the insulated shell. 

The duct must always have an adequate diameter, of 150mm for air

quantities up to 250 m

3

/h, a diameter of 160mm for air quantities up

to 325 m

3

/h and a diameter of 180mm for air quantities up to 400

m

3

/h. The duct spigots of the unit are fitted with loose sealing rings

160mm diameter.

Figure 6. A duct diameter of 125mm is recommended.

Summary of Contents for mrXbox90S

Page 1: ...tem 150 pa at 180 m3 h Filters supplied to be replaced post commissioning Coding mrXbox90S 1 2 Function components 1 Interior temperature sensor measures the temperature of the air from the dwelling 2...

Page 2: ...fact ory def ault settings Speed 1 Speed 2 Speed 3 X Watt age per fan Resist ance Duct Pressure P a 26 Flow R ate m3 h 42 86 Dimensional references 1 spigot to dwelling Supply warmed fresh air 2 spig...

Page 3: ...he right it shows the readout value for instance the preset volume Example The display now shows that the unit is running at ventilation setting 3 at a flow rate of 150 m3 h The four keys have the fol...

Page 4: ...allations current IEE regulations the regulations for connection to interior sewers in dwellings and residential buildings any additional regulations of the local utilities the installation instructio...

Page 5: ...ent fouling and draught Ducting references 1 to dwelling Supply warmed fresh air 2 to outside Exhaust cool stale air 3 from dwelling Extract warm stale air 4 from outside Intake cool fresh air 5 3 Con...

Page 6: ...Combination of a mechanical switch and a radio controlled RC transmitter It s possible to combine 2 RC transmitters with each other It s also possible to combine a mechanical switch with RC transmitt...

Page 7: ...ted with a pressure controlled filter indication and frost control For optimum performance of these features we recommend you initialise the unit This will ensure that the system pressure as function...

Page 8: ...ing 2 U3 setting 3 Settings U4 and U5 do not apply to this unit 3 Press key OK for 1 second to display the selected parameter value 4 The selected parameter value can be changed using keys or 5 The mo...

Page 9: ...cause some settings have an influence on the correct operation of the unit these have been placed in a separate installer parameters set Consequently these parameters can only be modified by the insta...

Page 10: ...s key F 1 second If no key is operated for 5 minutes Press key OK 1 second If no key is operated for 1 minute Press keys F and OK 3 seconds Press key or Press F or key 1 second Press F or key 1 second...

Page 11: ...r data and pressing key takes you back to step no 1 After 5 minutes this menu automatically disappears and the display will show the operational situation again In the event of an error the error code...

Page 12: ...red to modify the settings from operational mode By way of example parameter 8 bypass mode is changed from 1 to 2 1 Press key F for 3 seconds to activate the settings menu 2 Press keys F and OK for 3...

Page 13: ...display the LED on the switch will light up When the filters have been cleaned or replaced press the key OK to reset the filter indication The text FIL will blink for a moment and then the display wil...

Page 14: ...measures the temperature of to the basic pcb the input air is defective The Check the sensor connection to unit operates as normal the wiring Replace the sensor F10 The temperature sensor that Contact...

Page 15: ...th a new filter the filter indication must be reset by pressing key OK The display will blink for a moment to confirm that the filter has been reset The unit will return to operational mode 10 0 Repla...

Page 16: ...ithin the unit is considered Lifting gear such as slings or ropes must be arranged so as not to bear on the casing 3 3 Equipment stored on site prior to installation should be protected from the weath...

Reviews: