30. 06. 20. Document Number  671958

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

MRXBOXAB-ECO5-1Z

Installation Manual

Ducting in the 
ceiling void.

Side view of unit 
mounted on the
block wall in a 
cupboard using 

MVHR-DRAIN

the wall brackets.

Condensate drain,
uninsulated drain 
pipe with min 5

o

 fall 

running to SVP.

Valve in ceiling.

Unit weight 

= 76kG

3.2.1 Option 1 - Solid Wall

The MVHR unit fixed to a solid wall construction using the 

mounting bracket provided.

Wall Bracket Installation Dimensions

Solid Wall Mounted Unit Installation

Solid Wall Mounted Unit Installation

Non-Solid Wall Mounted Unit Installation

3.2.2 Option 2 - Non-Solid Wall

If it is not practical to use a solid wall, the MVHR unit should be 
fixed to a stud partition with a 25mm minimum thickness MDF 
panel solidly fixed behind the plasterboard.

If fixing to a stud wall the MDF panel should extend, width wise, over a 
minimum of 3 vertical studs with centres of no more than 400mm. Add 
additional vertical supports if necessary. 

Height wise, ideally, the MDF panel should extend from floor to ceiling 
but as a minimum should be a least 2m high.

Fix the mounting bracket to the wall (Figure 3) and use the wall 
mounted bracket to mount the unit on (Figure 5).

25

25

704 crs

9.1 dia.

30

94

94

33

Ducting in the 
ceiling void.

Side view of unit 
mounted in a 

with the 25mm 

cupboard fixed to 
a stud partition

MDF fixed behind 
the plasterboard
using the wall 

MVHR-DRAIN

brackets. 

Condensate drain,
uninsulated drain 
pipe with min 5

o

 fall 

running to SVP.

Valve in ceiling.

Unit weight 

= 76kG

3.3 Condensate Drain

The MVHR unit inside the enclosure is fitted with a straight coupling to 
allow 21.5mm overflow pipe (not supplied) to be attached using solvent 
cement, the pipe should be passed through the flexible adhesive backed 
cover plate before the solvent cement is applied.

The pipe can then be inserted into the coupling of the MVHR unit and 
the cover plate slid along the length to bond against the base panel of 
the enclosure preventing noise breakout (Figure 7).

Solvent cement to be applied

Flexible adhesive backed 
cover plate

Overflow pipe

The condensate must be discharged under a water level in a U-trap 
drainpipe or an alternative drain method which acts as an airlock. This 
condensate discharge connection is suitable for 21.5mm Ø overflow 
pipe. Solvent cement should be used to make the joint. 

If using a U-trap please ensure the U-trap has been filled to a suitable 
level of water to avoid any air locks. If the condensation pipe is fitted in 
an unheated space the pipe should be in insulated to prevent freezing.

An MVHR-DRAIN is recommended for use as the primary 
condensate take-off (Figures 8 and 9).

Min 5

Drop

Collar

Condensate Trap Installation

MVHR-DRAIN Installation

Condensate drain, 
uninsulated drain pipe with 
min 5° fall running to SVP.

Condensate pipe connection to 
unit and a typical example of a 
“U” trap drainpipe 

(Standard 

configuration only).

Summary of Contents for MRXBOXAB-ECO5-1Z

Page 1: ...This unit must be earthed Ducting must be securely fixed with screws to the spigot to prevent access to live parts Duct runs terminating close to the fan must be adequately protected by suitable guard...

Page 2: ...warmer months 1 2 3 Airflow Through unit Standard Unit Airflow Through OH unit Opposite Hand Unit Transport Fixings 3 0 MECHANICAL INSTALLATION Installation must be carried out by competent personnel...

Page 3: ...o a stud partition MDF fixed behind the plasterboard using the wall MVHR DRAIN brackets Condensate drain uninsulated drain pipe with min 5o fall running to SVP Valve in ceiling Unit weight 76kG 3 3 Co...

Page 4: ...all other bedrooms This should be used as the default value If a greater level of occupancy is expected add 4 l s per occupant Any air intake terminal must be installed in accordance with the appropri...

Page 5: ...at if the installation and building works are complete the unit is left running If the building works are not complete please close the air valves or cover up the air valves to prevent condensation fo...

Page 6: ...rValve Top of ceiling void Top of ceiling void Air supply to bedrooms in ceilings via AirValve Insulated extract duct Insulated extract duct MVHR unit Nuaire MVHR DRAIN Condensate drain uninsulated dr...

Page 7: ...ctor Ecosmart Device Connector Ecosmart Device Connector MAINS 230V 50Hz N L 3 Position Switch Ancillary code MRXBOX95 3SWITCH Blue Green yellow Brown Black Supply cord from unit Grey L 1 2 Fuse 5A MA...

Page 8: ...it Control On Front Panel Standard Configuration Only Unit Control On Front Panel Standard Configuration Only 5 2 Status Indication The status of the unit is indicated by a series of LED s on the fron...

Page 9: ...please contact the After Sales Department If ordering spares please quote the serial number of the unit together with the part number if the part number is not known please give a full description of...

Page 10: ...10 30 06 20 Document Number 671958 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO5 1Z Installation Manual NOTES...

Page 11: ...11 30 06 20 Document Number 671958 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO5 1Z Installation Manual NOTES...

Page 12: ...12 30 06 20 Document Number 671958 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO5 1Z Installation Manual NOTES...

Reviews: