background image

8

30. 06. 20. Document Number  671958

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

MRXBOXAB-ECO5-1Z

Installation Manual

5.0 COMMISSIONING

The filters fitted inside the unit are protected with a plastic film. 
Prior to commissioning remove the covers (Figure 21), take off the 
film and replace.

1. For the required air flow rates please refer to the design specification 

for the property, follow 2.4, or refer to building regulations ADF 
2010.

2. The unit is supplied with independent control for both normal and 

boost airflows (Figure 19). 

3. Correct commissioning is essential to ensure the ventilation air flow 

rates are met. It also ensures the unit is not over ventilating and 
causing excessive power consumption. 

4. Commissioning should be carried out in accordance with building 

regulations document “Domestic ventilation compliance guide”. 

www.planningportal.gov.uk/building regulations/approved 
documents/partf/associated. 

A calibrated moving vane 

anemometer and hood will be required to carry out commissioning.

5. Adjustment valves should be locked in place to prevent further 

adjustment. 

6. Once commissioned the home owner / tenant should be informed 

that the unit should not be adjusted as it will have a detrimental 
effect on the indoor air quality and could result in condensation and 
mould growth. The clear panel covering the control has an adhesive 
panel which should be exposed and sealed post commissioning to 
prevent tampering.

7. Speed 1 is limited to never exceed speed 2, when commissioning 

speed 2 should always be set first.

5.1 Humidity Adjustment

This product contains an internal humidity sensor fitted into the air-
flow extracting from the wet rooms. When the unit senses that the 
humidity exceeds the set point the unit will boost to that set by the 
commissioned boost speed. The set point can be found on the front 
of the unit (Figure 19) and is at its least sensitive when turned fully 
clockwise. Note that the sensor is measuring humidity from all the wet 
rooms at the same time and should not be relied on to solely boost the 
unit. Additional switch should be used local to the wet rooms (Section 
4.2).

19 

20 

Unit Control On Front Panel

 (Standard Configuration Only)

Unit Control On Front Panel

 (Standard Configuration Only)

5.2 Status Indication

The status of the unit is indicated by a series of LED’s on the front cover. 

The variants are listed below.

The display on the unit control panel will not indicate when a 

higher speed setting has been triggered by an external source, such 

as an ES-PIR2 etc.

HX Bypass

(AB units only)

Speed 1

Speed 2

Speed 3

Supply Fan Fault

Extract Fan Fault

Frost Protection

Filter Change

5.3 Integral Automatic HX Bypass

Intake and extract temperatures are monitored at the point the 

airflows enter the unit, if the range falls within the set parameters the 

bypass damper is opened automatically to target an indoor comfort 

temperature all year round.
The extract temperature is an average from all wet rooms. If this 

exceeds 25°C the unit may go into bypass depending on outside 

temperatures.

5.4 Frost Protection

In the event of the intake air temperature at the unit dropping below 

the predetermined set point (-5°C as standard) the supply fan will 

reduce to minimum speed, once the temperature rises above the set 

point the fan will return to its commissioned speed.
Frost protection will only activate after ten days of continuous run 

time. If commissioning of the unit is outside of this time frame please 

notify the after sales department prior to site visit.

6.0 MAINTENANCE

It is important that maintenance checks are recorded and that the 
schedule is always adhered to, in all cases, the previous report should 
be referred to.

6.1 Routine Maintenance

Clean all areas of unit and treat any areas of corrosion.

Check all access doors for leakage and if necessary locks should be 
adjusted and any replacement gasket materials should be replaced 
as required. 

Any drain trays should be cleaned and repaired if necessary. 

6.2 Every 3 Months 

Ensure condensate drains are cleaned clear and that water can 
flow freely from unit.

6.3 Annually 

Thoroughly inspect the unit and its components for corrosion, 
acting immediately to treat/restore any damaged areas. 

All electrical terminals within the unit should be tightened. 

Check all earth connections. 

+

-

Post commissioning remove
adhesive backing and seal 

Power Fan

Failure

+

-

Ventilation Controls

- +

+

- +

-

Speed 1 

- +

Speed 2 

Speed 3

Supply  Extract  Supply  Extract  Supply  Extract

Humidity adjustment

Summary of Contents for MRXBOXAB-ECO5-1Z

Page 1: ...This unit must be earthed Ducting must be securely fixed with screws to the spigot to prevent access to live parts Duct runs terminating close to the fan must be adequately protected by suitable guard...

Page 2: ...warmer months 1 2 3 Airflow Through unit Standard Unit Airflow Through OH unit Opposite Hand Unit Transport Fixings 3 0 MECHANICAL INSTALLATION Installation must be carried out by competent personnel...

Page 3: ...o a stud partition MDF fixed behind the plasterboard using the wall MVHR DRAIN brackets Condensate drain uninsulated drain pipe with min 5o fall running to SVP Valve in ceiling Unit weight 76kG 3 3 Co...

Page 4: ...all other bedrooms This should be used as the default value If a greater level of occupancy is expected add 4 l s per occupant Any air intake terminal must be installed in accordance with the appropri...

Page 5: ...at if the installation and building works are complete the unit is left running If the building works are not complete please close the air valves or cover up the air valves to prevent condensation fo...

Page 6: ...rValve Top of ceiling void Top of ceiling void Air supply to bedrooms in ceilings via AirValve Insulated extract duct Insulated extract duct MVHR unit Nuaire MVHR DRAIN Condensate drain uninsulated dr...

Page 7: ...ctor Ecosmart Device Connector Ecosmart Device Connector MAINS 230V 50Hz N L 3 Position Switch Ancillary code MRXBOX95 3SWITCH Blue Green yellow Brown Black Supply cord from unit Grey L 1 2 Fuse 5A MA...

Page 8: ...it Control On Front Panel Standard Configuration Only Unit Control On Front Panel Standard Configuration Only 5 2 Status Indication The status of the unit is indicated by a series of LED s on the fron...

Page 9: ...please contact the After Sales Department If ordering spares please quote the serial number of the unit together with the part number if the part number is not known please give a full description of...

Page 10: ...10 30 06 20 Document Number 671958 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO5 1Z Installation Manual NOTES...

Page 11: ...11 30 06 20 Document Number 671958 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO5 1Z Installation Manual NOTES...

Page 12: ...12 30 06 20 Document Number 671958 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO5 1Z Installation Manual NOTES...

Reviews: