17. 11. 21. Document Number  671861

Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk

MRXBOXAB-ECO3-AE(OH)SW & MRXBOXAB-ECO5-AE(OH)(SC/SW)

Installation Manual

5.0 COMMISSIONING

The filters fitted inside the unit are protected with a plastic film. 
Prior to commissioning remove the covers (Figure 20), take off the 
film and replace.

1. For the required air flow rates please refer to the design specification 

for the property, follow 2.4, or refer to building regulations ADF 
2010.

2. The unit is supplied with independent control for both normal and 

boost airflows (Figure 18). 

3. Correct commissioning is essential to ensure the ventilation air flow 

rates are met. It also ensures the unit is not over ventilating and 
causing excessive power consumption. 

4. Commissioning should be carried out in accordance with building 

regulations document “Domestic ventilation compliance guide”. 

www.planningportal.gov.uk/building regulations/approved 
documents/partf/associated. 

A calibrated moving vane 

anemometer and hood will be required to carry out commissioning.

5. Adjustment valves should be locked in place to prevent further 

adjustment. 

6. Once commissioned the home owner / tenant should be informed 

that the unit should not be adjusted as it will have a detrimental 
effect on the indoor air quality and could result in condensation and 
mould growth. The clear panel covering the control has an adhesive 
panel which should be exposed and sealed post commissioning to 
prevent tampering.

7. Speed 1 is limited to never exceed speed 2, when commissioning 

speed 2 should always be set first.

 

18 

Unit Control On Front Panel

 (Standard Configuration Only)

+

-

Post commissioning remove
adhesive backing and seal 

Power Fan

Failure

+

-

Ventilation Controls

- +

+

- +

-

Speed 1 

- +

Speed 2 

Speed 3

Supply  Extract  Supply  Extract  Supply  Extract

Humidity adjustment

5.1 Humidity Adjustment

This product contains an internal humidity sensor fitted into the air-
flow extracting from the wet rooms. When the unit senses that the 
humidity exceeds the set point the unit will boost to that set by the 
commissioned boost speed. The set point can be found on the front 
of the unit (Figure 18) and is at its least sensitive when turned fully 
clockwise. Note that the sensor is measuring humidity from all the wet 
rooms at the same time and should not be relied on to solely boost the 
unit. Additional switch should be used local to the wet rooms (Section 
4.2).

5.2 Status Indication

The status of the unit is indicated by a series of LED’s on the front cover. 

The variants are listed below.

The display on the unit control panel will not indicate when a 

higher speed setting has been triggered by an external source, such 

as an ES-PIR2 etc.

 

 

19 

Unit Control On Front Panel

 (Standard Configuration Only)

HX Bypass

(AB units only)

Speed 1

Speed 2

Speed 3

Supply Fan Fault

Extract Fan Fault

Frost Protection

Filter Change

5.3 Integral Automatic HX Bypass

Intake and extract temperatures are monitored at the point the 

airflows enter the unit, if the range falls within the set parameters the 

bypass damper is opened automatically to target an indoor comfort 

temperature all year round.
The extract temperature is an average from all wet rooms. If this 

exceeds 25°C the unit may go into bypass depending on outside 

temperatures.

5.4 Summer / Winter Switch

When the switch position is set to Summer the integral automatic 
summer bypass is fully operational, in the alternative Winter position 
the HX bypass is disabled to ensure the unit is constantly in heat 
recovery mode.

5.5 Speed 3 Operation (SW Units Only)

Speed 3 will be non-operational if the intake temperature is greater 
than the extract temperature.

5.6 Frost Protection

In the event of the intake air temperature at the unit dropping below 

the predetermined set point (-5°C as standard) the supply fan will 

reduce to minimum speed, once the temperature rises above the set 

point the fan will return to its commissioned speed.
Frost protection will only activate after ten days of continuous run 

time. If commissioning of the unit is outside of this time frame please 

notify the after sales department prior to site visit.

Summary of Contents for MRXBOXAB-ECO5-AESC

Page 1: ...cerning the safe use of the appliance by a person responsible for their safety Children shall not play with the appliance Cleaning and user maintenance shall not be carried out by children 1 1 Hazard Symbols REFER TO INSTRUCTION MANUAL Read and understand the installation and maintenance manual before installing operating or maintaining this product 1 2 Important Information This manual contains i...

Page 2: ...se to house Supply air Exhaust air from house to outside Extract air from house Intake air Exhaust air from outside from house to outside Supply air to house 2 Airflow Through OH unit Opposite Hand Unit Intake air from outside Extract air from house to house Supply air Exhaust air from house to outside Extract air from house Intake air Exhaust air from outside from house to outside Supply air to h...

Page 3: ...ing the wall MVHR DRAIN brackets Condensate drain uninsulated drain pipe with min 5o fall running to SVP Valve in ceiling Unit weight 56kG 3 3 Condensate Drain The MVHR unit inside the enclosure is fitted with a straight coupling to allow 21 5mm overflow pipe not supplied to be attached using solvent cement the pipe should be passed through the flexible adhesive backed cover plate before the solve...

Page 4: ...l s 1 2 13 17 21 25 29 Notes 1 In addition the minimum ventilation rate should be no less than 0 3 l s per m of internal floor area This includes all floors e g for a two story building add the ground and first floor areas 2 This is based on two occupants in the main bedroom and a single occupant in all other bedrooms This should be used as the default value If a greater level of occupancy is expe...

Page 5: ...ut very high moisture levels are likely to occur Therefore it is advisable that if the installation and building works are complete the unit is left running If the building works are not complete please close the air valves or cover up the air valves to prevent condensation forming in the ductwork and the MRXBOX unit due to natural migration of warm air 3 8 Dimensions 11 Unit Dimensions 754 5 2 7 ...

Page 6: ...ceilings via Air Valve mounted unit Nuaire wall MVHR DRAIN Condensate drain uninsulated drain pipe with min 5o fall running to SVP Insulated extract duct 3 9 2 Rectangular Ducting 13 Typical Rectangular Ducting Arrangement For Wall Mounted Units Exhaust air from kitchen bathroom to outside via air brick Minimum distance as specified in building regulations Intake air from outside via air brick All...

Page 7: ... underside of the MVHR unit within The cable should be fed through rubber blanking plug to provide a seal when the cover is re fitted 4 2 Wiring Diagrams 4 2 1 Unit Serving Kitchen And Bathroom 15 Wiring Diagrams Unit Serving Kitchen And Bathroom ECO3 3A Fuse BS 1362 ECO5 5A Fuse BS 1362 MAINS 230V 50Hz Light Room Light Switch Double Pole N L 3 Pole Isolator Kitchen Switch Blue Brown Black Optiona...

Page 8: ...en the unit senses that the humidity exceeds the set point the unit will boost to that set by the commissioned boost speed The set point can be found on the front of the unit Figure 18 and is at its least sensitive when turned fully clockwise Note that the sensor is measuring humidity from all the wet rooms at the same time and should not be relied on to solely boost the unit Additional switch sho...

Page 9: ...ve a full description of the part required The serial number will be found on the identification plate attached to the unit casing Telephone 02920 858 400 aftersales nuaire co uk Technical or commercial considerations may from time to time make it necessary to alter the design performance and dimensions of equipment and the right is reserved to make such changes without prior notice 6 0 MAINTENANC...

Page 10: ...10 17 11 21 Document Number 671861 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO3 AE OH SW MRXBOXAB ECO5 AE OH SC SW Installation Manual NOTES ...

Page 11: ...11 17 11 21 Document Number 671861 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO3 AE OH SW MRXBOXAB ECO5 AE OH SC SW Installation Manual NOTES ...

Page 12: ...12 17 11 21 Document Number 671861 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk MRXBOXAB ECO3 AE OH SW MRXBOXAB ECO5 AE OH SC SW Installation Manual NOTES ...

Reviews: