07. 01. 21. Document Number  671964

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

S2E

Installation Manual

1.2 Important Information

This manual contains important information on the safe and 
appropriate assembly, transport, commissioning, operation, 
maintenance, disassembly and simple troubleshooting of the product.

While the product has been manufactured according to the accepted 
rules of current technology, there is still a danger of personal injury or 
damage to equipment if the following general safety instructions and 
the warnings contained in these instructions are not complied with.

Read these instructions completely and thoroughly before 
working with the product.

Keep these instructions in a location where they are accessible 
to all users at all times.

Always include the operating instructions when you pass the 
product on to third parties.

1.3 Personal Protective Equipment

The following minimum Personal Protective Equipment (PPE) is 
recommended when interacting with Nuaire product:

Protective Steel Toed Shoes - 

when handling heavy objects.

 

Full Finger Gloves (Marigold PU800 or equivalent) - 

when 

handling sheet metal components. 

Semi Fingerless Gloves (Marigold PU3000 3DO or equivalent) 

- when conducting light work on the unit requiring tactile 
dexterity. 

Safety Glasses

 - when conducting any cleaning/cutting operation 

or exchanging filters. 

Reusable Half Mask Respirators 

- when replacing filters which 

have been in contact with normal room or environmental air.

VDE Compliant Screwdriver 

- when adjusting speed control

Nuaire would always recommend a site specific risk assessment by a 
competent person to determine if any additional PPE is required. 

2.0 INTRODUCTION

The S2E range of in-line backward curved extraction fans consists of 4 
units. All units are manufactured from galvanised steel.

The units have been designed for the extraction of polluted indoor air. 
Units feature three variable speeds and an inbuilt run on timer. The 
speeds and run-on timer are commissioned using adjustment dials 
located at outlet end of the unit.  An optional wall mounted variable 
speed control is available (S2E-SPCON2). 

2.1 Code Description: 

1

-

2

S2E

-

150

   

1. Range:  

 

S2E 

= In-line Extract Fans

2. Spigot Size: 

 

125

 = 125 mm Ø 

  

 

150

 = 150 mm Ø 

  

 

200

 = 200 mm Ø 

  

 

250

 = 250 mm Ø

3.0 MECHANICAL INSTALLATION

Installation must be completed by competent persons, in accordance 
with good industry practice and should conform to all governing and 
statutory bodies i.e. IEE, CIBSE, etc.

The unit must be installed indoors and can be installed any orientation. 
Provided its a suitable surface in a dry environment away from direct 
sources of frost, heat and water droplets or moisture generation. The 
fitted mounting brackets provide a method of installation suitable for 
direct ceiling mounting, suspending using drop rods or floor mounting.  

To reduce vibrations the unit must be mounted to a solid structure. Its 
recommended that anti-vibration mounts (AV’s) are used to further 
reduce any vibrations, these can only be used when the unit is mounted 
in a horizontal orientation, either suspended or floor mounted 

(product 

code - NAV 1)

. If AV mounts are used the installer MUST follow their 

instructions as supplied. 

Access to the unit for commissioning and maintenance requires access 
to the outlet end of the unit (minimum 300mm) and to the underside 
of the unit to remove the lid. This should considered before the 
installation takes place. 

Service / Maintenance Access – Unit must be installed with access 
to remove the lid, and a minimum of 300mm off the outlet end to 
access controls. 

3.1 Ducting

Ducting must be securely fixed with screws to the spigot to prevent 
access to rotating and live parts. Duct runs terminating close to the fan 
must be adequately protected by suitable guards.

Summary of Contents for S2E Series

Page 1: ...s damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard The replacement cord must be of the same technical specification as the original cord or greater This appliance should not be used by children or persons with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given sup...

Page 2: ...units are manufactured from galvanised steel The units have been designed for the extraction of polluted indoor air Units feature three variable speeds and an inbuilt run on timer The speeds and run on timer are commissioned using adjustment dials located at outlet end of the unit An optional wall mounted variable speed control is available S2E SPCON2 2 1 Code Description 1 2 S2E 150 1 Range S2E I...

Page 3: ...F UNIT Top View AIRFLOW J B A K H E F D G C K Comissioning Panel 1 Unit Dimensions Unit Code Unit Dimensions mm Unit Weight Kg A B C D E F G H J K S2E 125 475 299 186 125 195 505 543 149 5 15 93 6 9 S2E 150 475 299 186 150 195 505 543 149 5 15 93 7 4 S2E 200 577 339 233 200 243 608 648 169 5 20 117 9 8 S2E 250 677 409 288 250 310 708 750 204 5 15 144 13 1 ...

Page 4: ...Pole Isolator Blue Brown Black Boost 2 Gang 1 Way Wall Switch SL1 Closed Boost Operation SL2 Closed Purge Operation SL1 SL2 Closed Purge Operation Supply Cord From Unit Grey Purge Green Yellow 3 Wiring Diagram For 3 Speed Operation 4 3 Optional Control Connections Connection to Fan Fail output and S2E SPCON2 requires access to the unit PCB Figure 4 Remove lid fixings and remove lid Remove two scre...

Page 5: ...er and if can build up internally on motors and impellers shortening the life of the unit and in severe cases lead to overheating of the motors Inspect and clean the unit the motor fan assembly can be cleaned with a dry brush or dry cloth Thoroughly inspect the unit and its components for corrosion acting immediately to treat restore any damaged areas 7 0 WARRANTY The 2 year warranty starts from t...

Page 6: ...rdering spares please quote the serial number of the unit together with the part number if the part number is not known please give a full description of the part required The serial number will be found on the identification plate attached to the unit casing Telephone 02920 858 400 aftersales nuaire co uk Technical or commercial considerations may from time to time make it necessary to alter the ...

Page 7: ... such as slings or ropes must be arranged so as not to bear on the casing 3 3 Equipment stored on site prior to installation should be protected from the weather and steps taken to prevent ingress of contaminants 4 0 OPERATIONAL LIMITS 4 1 It is important that the specified operational limits for the equipment are adhered to e g operational air temperature air borne contaminants and unit orientati...

Page 8: ...nt that the specified operational limits for the equipment are adhered to e g operational air temperature air borne contaminants and unit orientation 4 2 Where installation accessories are supplied with the specified equipment e g wall mounting brackets They are to be used to support the equipment only Other system components must have separate provision for support 4 3 Flanges and connection spig...

Reviews: