04. 02. 20. Document Number  671712

8

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

SVT28

Installation Manual

 

DECLARATION OF INCORPORATION AND INFORMATION FOR SAFE INSTALLATION,  

 

OPERATION AND MAINTENANCE

 

INFORMATION FOR SAFE INSTALLATION, OPERATION AND MAINTENANCE

 

OF NUAIRE VENTILATION EQUIPMENT

We declare that the machinery named below is intended to be assembled with 
other components to constitute a system of machinery. All parts except for 
moving parts requiring the correct installation of safety guards comply with the 
essential requirements of the Machinery Directive. The machinery shall not be 
put into service until the system has been declared to be in conformity with the 
provisions of the EC Machinery Directive.

 

To comply with EC Council Directives 2006/42/EC Machinery Directive and 2014/30/EU (EMC).
To be read in conjunction with the relevant product documentation (see 2.1)

1.0  

GENERAL

1.1  

The equipment referred to in this 

Declaration of Incorporation

 is supplied by Nuaire to be assembled into    

 

a ventilation system which may or may not include additional components. The entire system must be  

 

 

considered for safety purposes and it is the responsibility of the installer to ensure that all of the equipment is  

 

installed in compliance with the manufacturers recommendations and with due regard to current legislation   

 

and codes of practice.

2.0  

INFORMATION SUPPLIED WITH THE EQUIPMENT

2.1  

Each item of equipment is supplied with a set of documentation which provides the information required for   

 

the safe installation and maintenance of the equipment. This may be in the form of a Data   

 

 

sheet and/or Installation and Maintenance instruction.

2.2  

Each unit has a rating plate attached to its outer casing. The rating plate provides essential data relating to the  

 

equipment such as serial number, unit code and electrical data. Any further data that may be required will be  

 

found in the documentation. If any item is unclear or more information is required, contact Nuaire.

2.3 

Where warning labels or notices are attached to the unit the instructions given must be adhered to.

3.0  

TRANSPORTATION, HANDLING AND STORAGE

3.1  

Care must be taken at all times to prevent damage to the equipment. Note that shock to the unit may result in  

 

the balance of the impeller being affected.

3.2 

 When handling the equipment, care should be taken with corners and edges and that the weight distribution  

 

within the unit is considered. Lifting gear such as slings or ropes must be arranged so as not to bear on the    

 casing.
3.3  

Equipment stored on site prior to installation should be protected from the weather and steps taken to prevent  

 

ingress of contaminants.

4.0  

OPERATIONAL LIMITS

4.1  

It is important that the specified operational limits for the equipment are adhered to e.g. operational air  

 

 

temperature, air borne contaminants and unit orientation.

4.2  

Where installation accessories are supplied with the specified equipment e.g. wall mounting brackets. They    

 

are to be used to support the equipment only. Other system components must have separate provision for    

 support.
4.3  

Flanges and connection spigots are provided for the purpose of joining to duct work systems. They must not be  

 

used to support the ductwork.

4.4  

In the event of RF interference the fan may increase in speed or make high pitched noises. This is normal and   

 

will have no adverse effect on the fan. The speed and noise will return to normal once the    

 

 

interference has subsided.

5.0  

INSTALLATION REQUIREMENTS

 

In addition to the particular requirements given for the individual product, the following general requirements  

 

should be noted.

5.1 

 Where access to any part of equipment which 

moves

, or can become 

electrically live

 are not prevented by   

 

the equipment panels or by fixed installation detail (e.g. ducting), then guarding to the appropriate standard    

 

must be fitted.

5.2 

 The electrical installation of the equipment must comply with the requirements of the relevant local electrical  

 

safety regulations.

5.3 

 For EMC all control and sensor cables should not be placed within 50mm or on the same metal cable tray as   

 

230V switched live, lighting or power cables and any cables not intended for use with this product.

6.0 

 COMMISSIONING REQUIREMENTS

6.1 

 General pre-commissioning checks relevant to safe operation consist of the following:

 

Ensure that no foreign bodies are present within the fan or casing.

 

Check electrical safety e.g. Insulation and earthing.

 

Check guarding of system.

 

Check operation of Isolators/Controls.

 

Check fastenings for security.

6.2 

 Other commissioning requirements are given in the relevant product documentation.

7.0 

 OPERATIONAL REQUIREMENTS

7.1  

Equipment access panels must be in place at all times during operation of the unit, and must be secured with  

 

the original fastenings.

7.2  

If failure of the equipment occurs or is suspected then it should be taken out of service until a competent  

 

 

person can effect repair or examination. (Note that certain ranges of equipment are designed to detect and    

 

compensate for fan failure).

8.0  

MAINTENANCE REQUIREMENTS

8.1  

Specific maintenance requirements are given in the relevant product documentation.

8.2  

It is important that the correct tools are used for the various tasks required.

8.3  

If the access panels are to be removed for any reason the electrical supply to the unit must be isolated.

8.4  

A minimum period of two minutes should be allowed after electrical disconnection before access panels are    

 

removed. This will allow the impeller to come to rest.

 

NB: Care should still be taken however since airflow generated at some other point in the system can    

 

cause the impeller to “windmill” even when power is not present.

8.5  

Care should be taken when removing and storing access panels in windy conditions.

Note: All standards used were current and valid at the date of signature.

Designation of machinery:  

Axus SVT28 Impulse Fan

Machinery Types:    

High Temperature Axial Fans 400°C/2hrs

Relevant EC Council Directives: 

2006/42/EC

 

Applied Harmonised Standards: 

BS EN ISO 12100-1, BS EN ISO 12100-2, EN294, 

 

 

 

 

EN60204-1, BS EN ISO 9001

Applied National Standards: 

BS848 Parts 1, 2 and 5

Signature of manufacture representatives:

Name: 

  Position: 

  Date: 

1)A. Thomas  

 

Engineering Director 

 

31. 01. 20

2)C. Sargent  

 

Manufacturing Director   

31. 01. 20

Summary of Contents for SVT28 Series

Page 1: ...y covers During installation maintenance ensure all covers are fitted before switching on the mains supply All pole disconnection from the mains as shown in the wiring diagram must be incorporated within the fixed wiring and shall have a minimum contact separation of 3mm in accordance with latest edition of the wiring regulations This unit must be earthed Ducting must be securely fixed with screws...

Page 2: ...unit shall have a unique mounting bracket which shall enable the bracket to be positioned as a first fix component with the unit being fitted as a second fix component avoiding possible mechanical damage The Nuaire SVT28 unit shall have inlet guards for safety purposes and also to prevent debris being pulled through the fan It also has a specially designed airflow deflector to direct the jet strea...

Page 3: ... side of the bracket and unit C B A Terminal Box 55mm To adjust deflector blade A To adjust deflector blade B 2 3 5 4 Fixing Support Bracket Fixing Unit to Support Bracket Unit Dimensions Adjusting Deflector Blades 4 3 Adjusting Deflector Blades The Deflector blades are factory set for horizontal discharge default setting but can be adjusted for downward deflection using the following procedure 1 ...

Page 4: ... 30 minutes to ensure correct operation If any fault occurs the equipment should be switched off Do not re start until the fault has been rectified 7 0 SPECIFIC COMMISSIONING AND SERVICING REQUIREMENTS Motors for Smoke Extract Fans Exposure temperature time 300 C for 2 hours 400 C for 2 hours These motors are used to provide a SAFETY FUNCTION for people in the event of fire in public premises or i...

Page 5: ...his manual and general good practice The product warranty applies to the UK mainland and in accordance with Clause 14 of our Conditions of Sale Customers purchasing from outside of the UK should contact Nuaire International Sales office for further details Failure to maintain the unit as recommended will invalidate the warranty 10 0 END OF LIFE AND RECYCLING Where possible Nuaire use components wh...

Page 6: ...04 02 20 Document Number 671712 6 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk NOTES ...

Page 7: ...04 02 20 Document Number 671712 7 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk NOTES 7 ...

Page 8: ...tem components must have separate provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 In the event of RF interference the fan may increase in speed or make high pitched noises This is normal and will have no adverse effect on the fan The speed and noise will return to normal once the...

Reviews: