background image

13

30. 06. 20. Document Number  671948

Nuaire | 

Western Industrial Estate 

Caerphilly 

CF83 1NA 

|

 

nuaire.co.uk

XBC+ with Ecosmart Classic (E) or No (N) Control

Installation Manual

4.0 SETTING TO WORK

Isolation - Before commencing work, make sure that the unit, 
switched live and Nuaire control are electrically isolated from the 
mains supply.

4.1 Filters

 Remove filter access panels (observe and note airflow direction labels), 
inspect filters for contamination with construction debris, replace as 
necessary. Replace access panels. 

Filter pressure drops will depend on actual flow rate and condition. 
Observe and record filter pressure drops after performance 
commissioning. Typically, filter “dirty” condition occurs when the initial 
filter “clean” readings have been increased by 125Pa.

If filter manometers, pressure switches or indicators have been fitted, 
they should be set or adjusted to reflect the commissioned system 
operation.

4.2 Heating Coils (LPHW)

Observe the Flow and Return connection labels on the unit. Drain and 
bleed valves are located on the coil. Other valves may be required in the 
system pipe-work depending on the installation (by others).

Where the wet system is at risk of frost damage, the addition of a 
proprietary anti-freeze solution to the water is recommended. Any 
frost protection offered by the unit’s integral control system will 
not operate if the power supply to the unit is interrupted.

Ecosmart frost protection is activated on any Ecosmart unit fitted with 
LPHW heating, when the outlet air temperature is 4ºC or below. The 
unit reacts by shutting down the fan to prevent a ‘wind chill’ effect 
reducing the temperature to a point whereby the coil could freeze 
and burst. The unit will also drive open the LPHW valve to a fully open 
position to allow full water flow through the coil and the main PCB 
will close the ‘Heat demand’ contacts. These contacts could be used to 
send a signal to activate the boiler and/or valve to open to provide heat 
if not already doing so.

Piped connections should be made to the unit using appropriate 
techniques, and all pipework must be independently supported. 

No hot work is permitted within one metre of the unit.

Ensure that installed pipework runs do not prevent or restrict access to 
the unit at any point.

The completed installation (including the connections within the unit, 
as these may be disturbed during installation) shall be pressure tested 
to the project engineer’s specification (This is a condition of the unit 
warranty).

4.3 Fan Sections

Access to the fan section is via lift off panels (Figures 1 & 23).

For non-Ecosmart units, wiring to the fan motor / unit terminal box 
should be mechanically protected and in made in accordance with 
the details on the motor name plate and diagram attached to the 
unit. With the unit electrically isolated, rotate the fan impeller / drive 
manually, checking that it spins freely.

Check all fixings are secure.

Units must not be operated without all access panels in place – damage 
to equipment or injury to personnel may result. Units must not be 
operated unless control interlocks are in place – damage to equipment 
may result.

Test run motor for condition and correct rotation. Check that the 
correct current overloads are fitted and that the current being drawn 
does not exceed the motor nameplate value. Excessive current 
normally indicates that the ductwork system resistance is different to 
design.

5.0 ELECTRICAL INSTALLATION

The electrical wiring must be carried out by competent persons, in 
accordance with good industry practice and should conform to all 
governing and statutory bodies i.e. IEE, CIBSE, COHSE etc.

5.1 Connections

5.1.1 Control Connections

Net

 - the 4 IDC plug-in connectors are provided for the connection of 

compatible sensors, manual controls and for linking the fans together 
under a common control. If more than 4 connections are required, 
the junction box (product code ES-JB) should be used (see data cable 
installation). 

Switch Live (SL) Terminal

 - A signal of 100-230V AC will activate the 

fan (required at each control).

Note that a signal from an isolating transformer will produce an 
unpredictable result and is not recommended.

5.1.2 Damper Connections

OP

 - 230V 50Hz 1A max supply to open the damper 

CL 

- 230V 50Hz 1A max supply to close the damper 

N

 - Neutral supply to damper 

RET

 - 230V AC return signal from the damper limit switch indicates the 

damper has reached its operating position. If the return signal is not 
present, the fan will wait for 1 minute before starting.

Note: If a damper is not fitted, connect a link wire from OP to RET. 
This will cancel the delay.

Where units are supplied in modular sections, it will be necessary to 
install and connect mains wiring between controls and devices such 
as motorised dampers, it may also be necessary to install and connect 
mains wiring between sensors and actuators.

Depending on final damper location, extension of the cable looms may 
be required.

5.1.3 Volt Free Relay Contacts

Note that the volt free contacts are not fused. If these are used to 
power any external equipment, the installer must provide adequate 
fusing or other protections.

Volt free relay contacts are rated at 5A resistive, 0.5A inductive.

Run Connections 

- Contacts closed when the fan is running

 

Fault Connections 

- No Fault = Contacts are closed 

Fault 

- Contacts are opened 

Heat Demand 

- Contacts closed when heating is selected.

5.1.4 Data Cable Connection

A 4-core SELV data cable is used to connect devices. 

Do not run data cable in the same conduit as the mains cables and 
ensure there is a 50mm separation between the data cable and other 
cables. The maximum cable run between any two devices is 300m 
when it is installed in accordance with the instructions.

Please note that the total data cable length used in any system 
must be less than 1000m. Keep the number of cable joints to a 
minimum to ensure the best data transmission efficiency between 
devices.

5.1.5 Maximum Number of Devices

The maximum number of devices (including fans) that can be 
connected together via the cable is 32, irrespective of their functions.

5.1.6 Other Low Voltage Cables

Follow the basic principle (as d). Keep the cable run as short as possible, 
less than 50 metres. Use screened cable if cable length is more than 
2m.

Summary of Contents for Xboxer XBC+ Ecosmart Classic E

Page 1: ... it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard Precautions must be taken to avoid the back flow of gases into the room from the open flue of gas or other fuel burning appliances This appliance should not be used by children or persons with reduced physical sensory or mental capabilities or lack of experience and knowledge unless...

Page 2: ...mend a site specific risk assessment by a competent person to determine if any additional PPE is required 2 0 INTRODUCTION The information contained in this document provides details of installation operation and maintenance for installers and users of the XBOXER XBC Supply and Extract Ventilation Unit with Heat Recovery This supply and extract air handling unit range comprises an combination of h...

Page 3: ...er Removal Remove filter retainer 2 x M5 screws Lower filter into filter well in the base Tilt filter and remove through panel 2 3 Minimum Controls Clearance Filter Replacement XB C 10 H A L H 2 E P L S 1 S 1 2 3 4 5 6 7 8 9 10 11 12 13 14 1 Range XBOXER 2 HX Type C Counterflow E Enthalpy 3 Unit Size 10 15 25 45 55 65 4 Unit Layout H Horizontal 5 Filter Grade A 6 Heating Type E Electric L LPHW N N...

Page 4: ...ng the offloading from the vehicle or on the site thereafter All claims for damage and or incomplete delivery must be reported to Nuaire within two days of receipt of the equipment following guidance in our terms conditions of sale 3 2 2 Offloading and Handling The weight of the unit modules and palletised items is displayed on the unit rating plate or on the packaging Some of the modules have an ...

Page 5: ...cess panels it is recommended that electrical and plumbing service connections to the unit are run at 90 degrees to the main air flow axis Control circuit connections must be segregated i e routed separately by a minimum of 50mm from power connections The unit rating label shows the maximum electrical load of the equipment Connections to the unit may include single phase supply connections and a v...

Page 6: ... A B C D SUPPLY DISCHARGE Unit Code Dimensions to Hole Centres mm A B C XBC10HA 1068 830 385 XBC15HA 1068 830 385 XBC25HA 1232 884 415 XBC45HA 1332 1020 447 XBC55HA 1632 1052 424 XBC65HA 1644 1054 430 Unit Code Dimensions to Hole Centres mm A B C D XBC10HA 240 258 367 22 XBC15HA 240 258 367 22 XBC25HA 322 273 491 22 XBC45HA 380 291 552 22 XBC55HA 450 418 608 22 XBC65HA 600 418 608 22 10 11 Unit wi...

Page 7: ...S12 1250 471 302 76 XBC25 HE MS12 1250 252 302 59 XBC25 HS MS16 1600 471 302 99 XBC25 HE MS16 1600 252 302 73 XBC45 HS MS10 1050 531 360 69 XBC45 HE MS10 1050 270 360 49 XBC45 HS MS12 1250 531 360 88 XBC45 HE MS12 1250 270 360 66 XBC45 HS MS16 1600 531 360 114 XBC45 HE MS16 1600 270 360 81 XBC55 HS MS10 1050 588 430 79 XBC55 HE MS10 1050 398 430 62 XBC55 HS MS12 1250 588 430 101 XBC55 HE MS12 1250...

Page 8: ...HE MBS S 406 387 268 406 387 260 220 277 237 36 XBC15 HE MBS L 852 833 714 406 387 260 220 277 237 44 XBC25 HS MBS S 640 621 385 640 621 342 302 511 471 50 XBC25 HS MBS L 992 973 737 640 621 342 302 511 471 64 XBC25 HE MBS S 421 402 275 421 402 342 302 292 252 40 XBC25 HE MBS L 992 973 846 421 402 342 302 292 252 54 XBC45 HS MBS S 700 681 415 700 681 400 360 571 531 60 XBC45 HS MBS L 1070 1051 785...

Page 9: ...op rods should be secured to the Unistrut channel and extended to be fixed to the four piece support brackets to be used on the underside of the attenuators Figure 15 Note once the attenuators are supported and levelled and immediately before securing the attenuator to the attenuator flange connector remove the backing from the Foam Sealing Strip The attenuators must be secured to the unit using t...

Page 10: ... RT 65 XBC65 EXHAUST RT XBC65 INTAKE RT 3 12 2 Optional Exhaust Intake Terminals 3 12 3 Terminal Part Codes 16 17 Weatherproof Kit Installation Motorised Damper Installation 3 13 Motorised Dampers If matched silencers of the same length e g XBC15 HS MS16 and XBC15 HE MS16 are being fitted to the fan unit the motorised damper e g XBC15 MD and XBC15 MD WP should to be fitted after the silencers Figu...

Page 11: ...d on the middle section of the housing After you have installed the hoses it is essential to check them for tightness of fit at the connection points and to make sure that they run without any kinks 18 19 Damper Wiring Switch Wiring S1 S2 S3 S1 S2 S3 1 0 1 0 1 0 0 1 230V Auxiliary switch Notes Caution Power supply voltage Other actuators can be connected in parallel Please note the performance dat...

Page 12: ... incorporates an alarm function If the water level in the condensate tray exceeds a maximum level for example as a result of the discharge tube becoming blocked or frozen the alarm contact will open This contact is internally connected to the heat exchanger bypass actuator and the unit will automatically be placed into bypass mode preventing further condensate production Unit operation will otherw...

Page 13: ...ult Units must not be operated unless control interlocks are in place damage to equipment may result Test run motor for condition and correct rotation Check that the correct current overloads are fitted and that the current being drawn does not exceed the motor nameplate value Excessive current normally indicates that the ductwork system resistance is different to design 5 0 ELECTRICAL INSTALLATIO...

Page 14: ...irflow Ensure the power supply is switched off and that a link wire is connected from the supply L to the SL terminal Unplug all items connected to the Net connectors Switch on the power supply Wait for the fan to complete its self test operation Measure the airflow using standard commissioning instruments at a suitable point in the ductwork If adjustment is required rotate the pot marked MAX to o...

Page 15: ...er for units without control All wiring is terminated in junction boxes fitted to the specified side of the unit Notes Do not wire the power supply to motor via the motor alarm relay as terminals are only closed after the motor is energized Any heating cooling coils fitted are supplied without control valve and actuator The alarm relay on condensate may require the use of a contactor if the host e...

Page 16: ... 20 Document Number 671948 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Classic E or No N Control Installation Manual 27 Wiring BC Control XBC25 65 5 8 2 Unit Sizes 25 65 ...

Page 17: ...ire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Classic E or No N Control Installation Manual 5 9 Wiring Diagrams for ES Control 5 9 1 Unit Sizes 10 15 with No Heating 28 Wiring ES Control XBC10 15 No Heater ...

Page 18: ...Number 671948 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Classic E or No N Control Installation Manual 29 Wiring ES Control XBC25 65 No Heater 5 9 2 Unit Sizes 10 15 with No Heating ...

Page 19: ...mber 671948 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Classic E or No N Control Installation Manual 30 Wiring ES Control XBC10 15 LPHW Heater 5 9 3 Unit Sizes 25 65 with LPHW Heating ...

Page 20: ...mber 671948 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Classic E or No N Control Installation Manual 31 Wiring ES Control XBC25 65 LPHW Heater 5 9 4 Unit Sizes 25 65 with LPHW Heating ...

Page 21: ... 671948 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Classic E or No N Control Installation Manual 32 Wiring ES Control XBC10 15 Electric Heater 5 9 5 Unit Sizes 10 15 with Electric Heating ...

Page 22: ... 671948 Nuaire Western Industrial Estate Caerphilly CF83 1NA nuaire co uk XBC with Ecosmart Classic E or No N Control Installation Manual 33 Wiring ES Control XBC25 65 Electric Heater 5 9 6 Unit Sizes 25 65 with Electric Heating ...

Page 23: ...contained in this manual and general good practice Failure to maintain the unit as recommended will invalidate the warranty The product warranty applies to the UK mainland and in accordance with Clause 14 of our Conditions of Sale Customers purchasing from outside of the UK should contact Nuaire International Sales office for further details 8 0 END OF LIFE AND RECYCLING Where possible Nuaire use ...

Page 24: ...ies are supplied with the specified equipment e g wall mounting brackets They are to be used to support the equipment only Other system components must have separate provision for support 4 3 Flanges and connection spigots are provided for the purpose of joining to duct work systems They must not be used to support the ductwork 4 4 Local Environment Humidity Ambient humidity the humidity at the un...

Reviews: