Diagnostic Programming Mode
NOTE: Depending on current option settings, some displays cannot be viewed.
Overview Diagnostic Mode
The current Diagnostic Programming Mode screen will display until either the Extra Cycle button is pressed
through for each screen, or the Diagnostic button is pressed. In the event of regeneration occurring while in the
Diagnostic Programming Mode, the regeneration step and time remaining will be displayed. When regeneration
completes, the display will return to the normal time of day display screen.
Entering and Exiting Diagnostic Mode
Press and release the “D” button to enter the Diagnostic Programming Mode. Pressing the Extra Cycle button will
move to the next diagnostic screen. Press the Extra Cycle button once per display until all are viewed. Pressing
the Diagnostic button while in Diagnostic Mode will cause the unit to leave the Diagnostic Mode and return to the
normal time of day display screen.
Current Flow Rate
This program step displays the calculated flow rate for the timer. The below flow rates are the maximum flow
rate the timer will read for each meter.
.
1.25” Turbine:
90 gpm (0.3 m3/m)
.
— Press the Extra Cycle button.
Peak Flow Rate
This program step displays the peak flow rate (1 minute average) since the last regeneration.
.
— Press the Extra Cycle button.
Totalizer
This program step displays the total volume of treated water that passes through the meter.
.
— Reset to zero by holding the Up and Down buttons for five seconds while in the totalizer screen.
.
— Press the Extra Cycle button.
Hours Between Last Two Regenerations
This program step displays the time between the last two regenerations saved.
.
— Press the Extra Cycle button.
Hours Since Last Regeneration
This program step displays the hours since the last regeneration.
.
— Press the Extra Cycle button.
Volume Remaining
This program step displays the volume remaining. The timer will regenerate if the volume remaining is set to
zero. The maximum ranges are the same as the maximum volume calculated on the main screen.
.
— Press the Extra Cycle button.
Reserve Capacity
This program step displays the reserve capacity, ensuring soft water is available at all times.
.
— Press the Extra Cycle button.
Previous Day’s Water Usage
This program step displays the previous day’s water usage.
.
— Press the Extra Cycle button.
Software Version
This program step displays the timer’s software program version number.
.
— Press the Extra Cycle button to exit.
NOTE: Diagnostic Programming Mode will stop if the system goes into a regeneration.
1.
2.
3.
4.
5.
6.
7.
8.
9.
Summary of Contents for 7000XTR
Page 21: ...Page 21 Notes ...
Page 22: ...Page 22 Power Head Assembly 61501 7000XT_REVA ...
Page 34: ...Page 34 Brine Tank Refill Position 40988_REVA 41121_REVA Water Conditioner Flow Diagrams ...
Page 38: ...Page 38 Dimensional Drawings 61500 7000XTR LNE_REVA ...
Page 39: ...Page 39 Meter Flow Data TR18753 Softener TR18688 Filter 41140 02_REVA ...
Page 40: ...Page 40 Injector Flow Data TR18755_REVB ...
Page 41: ...Page 41 Notes ...
Page 42: ...Page 42 Notes ...
Page 43: ...Page 43 Notes ...
Page 44: ...P N 42484 Rev A ...