background image

Do not use corrosive or flammable gases or liquid with this product.
Please use within the rated pressure range. Do not apply pressure beyond recommended maximum pressure, 
permanent damage to the pressure sensor may occur.
Do not drop, hit or allow excessive shock. Even if switch body appears undamaged, internal components may 
be broken and can cause malfunction.
Turn power off before connecting wiring. Incorrect wiring or short circuit will damage and / or cause malfunction.
Do not use in environment where steam or oil vapor is present.
This product is not explosion-proof rated. Do not use in atmospheres containing flammable or explosive gases.
Avoid wiring the sensor cable adjacent to or in the same cable tray with power or high voltage lines. Doing so 
could cause malfunction due to noise.
This product is not a safety sensor. Its use is not intended to protect life and prevent bodily injury or property 
damage from dangerous parts or machinery. It is a normal object detection sensor.

SPECIFICATIONS

DPS280   

(PRESSURE)

DVS280  

(VACUUM)

Rated pressure range

0 ~ 1000 kPa
0 ~ 145 PSIG

0.0 ~ - 101.3 kPa

0 ~ 29.9" Hg Vacuum

Operating / Set pressure range

-100 ~ 1000 kPa

- 14.5 PSIG ~ + 145 PSIG

10.0 ~ - 101.3 kPa

1.45 PSIG ~ 29.9" Hg Vacuum

Maximum pressure

1500 kPa

300 kPa

(Exceeding max pressure could damage switch)

217.5 PSIG

43.5 PSIG

Fluid

Air, Non-corrosive gases, incombustible gases

Set pressure
resolution

kPa

1

0.1

kgf/cm

2

0.01

0.001

bar

0.01

0.001

psi

0.1

0.01

InHg

-

0.1

mmHg

-

1

Power supply voltage

12 to 24VDC ± 10 %, Ripple (P-P) 10 % or less

Current consumption

 45mA (with no load)

Switch output

Repeatability (Switch output)

 ± 0.2 % F.S. ± 1 digit

Hysteresis mode
Window comparator mode

Adjustable

Response time

 2.5ms (chatter-proof function: 24ms, 250ms, 500ms, 1000ms and 

1500ms selections)

Output short circuit protection

Yes

7 segment LCD display

Two color (red/green) display (sampling rate: 5 times/1sec.)

Indicator accuracy

 ± 2.0 % F.S. ± 1 digit (ambient temp: 77°F ± 5°F / 25°C ± 3°C) 

Switch ON Indicator

Green OUT Indicator

Environment

Enclosure

IP40

Ambient temp. range

Operation: 0°F ~ 122°F / 0°C ~ 50°C, Storage: 14°F ~ 140°F / -10°C ~ 

60°C

(no condensation or freezing)

Ambient humidity range

Operation/Storage: 35 ~ 85% RH (no condensation)

Withstand voltage

1000VAC in 1-min (between case and lead wire)

Insulation resistance

50Mohm min. (at 500 VDC, between case and lead wire)

Vibration

Total amplitude 1.5mm, 10Hz-55Hz-10Hz scan for

1 minute, two hours each direction of X,Y and Z

Shock

100m/s

2

 (10G), 3 times each in direction of X,Y and Z

Temperature characteristic

 ± 2% F.S. of detected pressure (77°F / 25°C) at temp.

Range of 0°F ~ 122°F / 0°C ~ 50°C

Port size

1/8 NPT Male x 10-32 UNF Female, 1/8 PT x M5, G 1/8 x M5

Lead wire

Oil-resistant cable (0.15 mm

)

Weight

Approx 45g - Switch only

Approx 90g - Switch with 2M mating cable

PNP open collector

Max. load current: 125mA

Max. supply voltage: 24VDC

Residual voltage:   1.5V

(load current 125mA)

NPN open collector

Max. load current: 125mA

Max. supply voltage: 30VDC

Residual voltage:   1.5V

(load current 125mA)

8

6

7

5

4

3

2

DPS280 / DVS280 Series

1

DPS280 / DVS280 Series

1

 

青岛秉诚自动化设备有限公司

                                                        

服务热线:

4006-918-365               

传真:

(86-532)585-10-365 

地址:中国

·

青岛市重庆南路

99

号海尔云街甲

3

号楼

7F             

网址:

http://www.ivalve.cc           Email

sales@ivalve.cc   

Summary of Contents for DPS280 Series

Page 1: ...oltage 12 to 24VDC 10 Ripple P P 10 or less Current consumption 45mA with no load Switch output Repeatability Switch output 0 2 F S 1 digit Hysteresis mode Window comparator mode Adjustable Response time 2 5ms chatter proof function 24ms 250ms 500ms 1000ms and 1500ms selections Output short circuit protection Yes 7 segment LCD display Two color red green display sampling rate 5 times 1sec Indicato...

Page 2: ...ting Cable Port Type N 1 8 NPT Male X 10 32 F R 1 8 PT X M5 G G 1 8 X M5 emale ERROR CODE INSTRUCTION PRESSURE UNIT CONVERSION TABLE Turn power off and check the cause of overload current or lower the current load under 125 mA then restart Excess load current error Residual pressure error Applied pressure error System Error Change input pressure to ambient pressure and perform zero calibration aga...

Page 3: ... mm 0 24 6 1 0 20 5 0 0 79 20 0 0 16 4 2 0 51 13 0 0 50 12 9 1 46 37 1 M3 Mounting bracket L TYPE M3 Mounting bracket S TYPE BRK280 1 BRK280 2 1 79 45 5 1 03 26 2 0 20 5 0 0 98 25 0 0 16 4 2 Units Inch mm DIMENSIONS 1 0 25 4 1 18 30 0 150 10 1 8 NPT Male x 10 32 UNF Female 1 8 PT x M5 G 1 8 x M5 M8 Female 4 Pin Mating Cable Supplied With Switch Cable O D 4 0mm Conductor Gauge 26 AWG Mating Cable 0...

Page 4: ...t responds to that change Prevents output chattering See Pressure Setting Modes for more information SoG State on Green SoR State on Red Eg If SoG is selected When the Output State is ON the large display will be green If the Output type selected below is Normally Open off the large display is Red until set point is achieved At that point the output closes goes on and the display will go Green If ...

Page 5: ...the down arrow will rapid decrease the value Once the pressure setting step is complete momentarily depress to return to sensing mode or waiting 10 seconds will automatically default to sensing mode If Output Type Normally Open was selected the LCD display will be AP 1 or if Normally Closed was selected the LCD display will be An 1 during this step To exit Auto Setting mode with AP1 displayed simu...

Page 6: ... When display unit is in PSI setting resolution is 0 2 PSI DVS280 When display unit is in PSI setting resolution is 0 02 PSI In the pressure setting mode within the available set pressure range using selected units the operator has preset the P n 1 and or P n 1 P n 2 and a Hysteresis H value Hysteresis mode N O example On ascending pressure the digital output will go on value at P1and go off when ...

Reviews: