DSP LASER AP with MCS
C14
000x÷111x
Enabling of the reading of the Monitor of the
device connected to the relevant Safety output
(OUTS5, OUTS6 and OUTS7):
0: Monitor NOT Active
1: Monitor Active
C15
0000xxxx÷1111xxxx
Output management by MCS. (0: OFF, 1: ON)
OFF: Output not controlled by MCS and
downgraded to generic output.
ON: Safety outputs OUTS1, OUTS2, OUTS3
and OUTS4 controlled by MCS.
C16
xxxx0000÷xxxx1111
Output management by MCS. (0: OFF, 1: ON)
OFF: Output not controlled by MCS and
downgraded to generic output.
ON: Safety outputs OUTS5, OUTS6, OUTS7
and OUTS8 controlled by MCS.
C17
0000÷1111
Output management by MCS. (0: OFF, 1: ON)
OFF: Output not controlled by MCS
ON:
outputs
OUTG3, OUTG5, OUTG8,
OUTG12 controlled by MCS.
Together with this manual, a table similar to this is attached, which shall be filled by the
manufacturer with the values assigned to every parameter. This table shall be filled,
registered, signed and inserted in the technical documentation of the machine.