Technical Data
126
89217391 Rev. A
©2022 nVent
14.6 Electrical connection
Supply voltage
-
depending on device variant
V, Ph / Hz
380 … 480+10/-5 %
AC 3~ / 50/60
-
depending on device variant
200 … 240+10/-15 %
AC 3~ / 50/60
Input power (max.)
kW
22.2
22.2 *)
Current consumption (rated current)
A
47.5
93.5 *)
Current consumption (max.)
A
75
123.3 *)
Fuse protection provided by the customer
A
100
150 *)
Frequency tolerance
continuous
%
1.0
temporary
%
2.0
Control voltage
V
24 DC
10 %
*) = referred to supply voltage 200 … 240 V
14.6.1 Supply
Name
Circuit diagram
BMK
3 phases, PE
1 Q1: 2
1 Q1: 4
1 Q1: 6
X 1 PE
14.6.2 Interfaces
Name
BMK
Data interface RS485
Modbus RTU slave
3K4: 11/21/13
3K5: 11/21/13
Data interface RS232
3K1 X1: 26/27/28
Data interface IPV4
3K1 IF2: RJ45
Data interface IPV6
12K1 X9: RJ45