Setting Up
©2022 nVent
89217391 Rev. A
57
8.
Verify fill hose is connected to the fill/drain valve and that the valve is open.
9.
Route the purge lines back to the tank, drain, etc.
10.
Start the pump on the fill kit and wait for both purge lines to fill with a solid
stream of coolant and become clear of air bubbles. (ref. image below)
Abb. 30: Purge lines
11.
Once purge lines are clear, turn on the
unit’s main power switch and set the
unit to dual pump mode.
12.
Set unit to flow control mode and set flow target to minimal value (i.e.
200LPM). (ref. image below)
Abb. 31: Control panel