Step
4
–
Creating SLIM alarm
• Slowly rotate TS
1
(NGC-
40
- SLIM) on the NGC-
40
-DEMO clockwise until both outputs turn OFF.
• Rotate TS
1
back to its original position, some value less than the trip value.
Step
5
–
Clearing the Alarm
• Click on the alarm list to view the alarms. The screen below should appear.
• Clear the Trip alarm by pressing
Trip Reset
button on the SLIM module. Both the
NGC-
40
-HTC
3
and NGC-
40
-SLIM output relays should turn ON.
Step
6
–
Clearing the SLIM alarm using the Safety Limiter button
Create another trip but this time clear the alarm by pressing the Safety Limiter Reset button on the NGC-
40
DEMO. Rotate TS
1
to a value
less than the trip temperature before pressing the reset switch.
Review – What you accomplished
• How to enter in a new temperature trip value.
• How to configure the alarm output relay for Normal, Toggle or Flash mode.
• How to create a trip condition using the NGC-
40
-SLIM reset buttons on the module or by using an external push button switch.
• How to clear alarms from the Alarm List generated by the TOUCH
1500
software.