3
Heating Cable Repair
nVent.com
|
13
3.1
General
• Before commencing field modifications/repairs,
heating cable resistance should be checked with an
ohmmeter to ensure that it is within ± 10% of the
cable’s calculated resistance. Record the measured
value for comparison with the measured value on
completion of repairs.
Calculated resistance = heated length (ft) x Ω/foot;
(heated length (m) x Ω/meter)
Note: Ω/foot (Ω/meter) of heating cable may be
obtained from the product data sheet H59079 for
XMI-l heating cables.
• For field repairs, check continuity of both sections
of cable to be joined using the ohmmeter. If open
circuited, do not attempt to fabricate the joint.
-
For two conductor heating cable, conductors on
far end of cable may have to be shorted together.
• Check insulation resistance (IR) of both cables to
be joined with a 1000 V DC Megohmmeter
(Appendix B); a value greater than 20 megohms
should be attained. If satisfactory follow
appropriate repair procedure to make a joint
(Section 3.3) or end cap (Section 3.4), otherwise
follow insulation drying procedure in Appendix D
before proceeding.
• When silver brazing, avoid excessive heating of
parts to be joined as this can lead to embrittlement
of materials and take care not to overheat the joint
body as the braze at the conductor joint may melt.
Also avoid overheating the corrugate as excessive
heat can damage the corrugate.
• Once a joint or end cap installation has been
started, it must be completed without interruptions.
This will prevent the cable from absorbing moisture
and causing a decrease in the insulation resistance.