Shelf Manager ACB-VI
Sensor Table
20
R1.2, March 2018
15 Sensor Table
Sensor table for the primary shelf manager with IPMB address 0x10.
IPMC
Nr.
LUN Name
Type-Code
Event/Reading
Type-Code
Description
10
0
0
FRU 0 HOT_SWAP
Hot Swap
0xf0
Discrete
0x6f
This sensor returns the hot-swap states for FRU 0.
10
1
0
IPMB LINK
IPMB Link
0xf1
Discrete
0x6f
This sensor returns the IPMB link state.
10
2
0
Local Temp
Temperature
0x01 Threshold
0x01
This sensor measures the local temperature.
10
3
0
3V3_local
Voltage
0x02 Threshold
0x01
This sensor measures the local 3.3 V voltage in volts.
10
4
0
I2C_PWR_A
Voltage
0x02 Threshold
0x01
This sensor measures the 3.3 V power supply A voltage
supplied to I2C devices in volts.
10
5
0
I2C_PWR_B
Voltage
0x02 Threshold
0x01
This sensor measures the 3.3 V power supply B voltage
supplied to I2C devices in volts.
10
7
0
5V0_local
Voltage
0x02 Threshold
0x01
This sensor measures the 5 V supply voltage for the
ShMM700R on the local shelf manager in volts.
10
8
0
1V5_FPGAA
Voltage
0x02 Threshold
0x01
This sensor measures the 1.5 V voltage supplied to FPGAA
in volts. (Only with radial IPMB)
10
9
0
1V5_FPGAB
Voltage
0x02 Threshold
0x01
This sensor measures the 1.5 V voltage supplied to FPGAB
in volts. (Only with radial IPMB)
10
16
0
-48A Bus voltage
Entity Presence
0x25 Discrete
0x6f
This sensor indicates the presence of the -48 V_A at the
shelf manager backplane connector.
10
17
0
-48B Bus voltage
Entity Presence
0x25 Discrete
0x6f
This sensor indicates the presence of the -48 V_B at the
shelf manager backplane connector.
10
18
0
-48A ACB voltage
Entity Presence
0x25 Discrete
0x6f
This sensor indicates the presence of the -48 V_A behind
the shelf manager’s main fuse.
10
19
0
-48B ACB voltage
Entity Presence
0x25 Discrete
0x6f
This sensor indicates the presence of the -48 V_B behind
the shelf manager’s main fuse.
10
20
0
20V AUX
Entity Presence
0x25 Discrete
0x6f
This sensor indicates the presence of 20 V aux voltage on
shelf manager.
10
21
0
-48A ACB Fuse
Entity Presence
0x25 Discrete
0x6f
This sensor indicates the state of
-48 V_A input fuse on the shelf manager.
10
22
0
-48B ACB Fuse
Entity Presence
0x25 Discrete
0x6f
This sensor indicates the state of
-48 V_B input fuse on the shelf manager.
10
128
0
HWRI State
OEM reserved
0xde Discrete
0x6f
This sensor indicates the high-level redundancy state of
the ShMM.
10
129
0
Reboot Reason
OEM reserved
0xdd Discrete
0x6f
This sensor indicates the reason for the last reboot.