14.
Remove 45 mm (1 3/4 in) of the copper
tape and expose the copper strands. Install
zip tie (7) to secure the copper strands. Pull
back the copper strands.
15.
Place the compression cone between the
filler core and the copper strands. The cone
should be "pushed on" until it is flush with
the end of the filler core.
16.
Distribute the strands as evenly as
possible around the compression cone.
17.
Install a second zip tie (7) to secure the
end of the copper strands to the
compression cone. With a pair of cutting
pliers (6), trim the ends of the copper
strands evenly with the compression cone
edge.
(14)
(14)
(14)
(15)
(17)
(16)
IP8519_A
6 OF 11
INSTRUCTION SHEET