Ground wire
1 in
14
1
3
15
2
• Attach circuit tag
to heating cable
(RaySol only).
• Push end seal completely
onto heating cable.
Note: The end seal is
designed to be installed
only once; it cannot be
removed from the heating
cable once installed. Do
not use until ready for final
installation.
• Apply appropriate
warning label to
junction box cover:
IceStop = Yellow
RaySol = Orange
XL-Trace = Orange
• Score down and around
outer jacket 1 inch from
the end.
• Remove the outer jacket.
• Do not cut or damage inner
jacket. If damaged, remove
damaged section and
repeat step 1.
• Remove exposed braid.
END SEAL INSTALLATION FOR XL-TRACE-CR AND -CT, RAYSOL, AND ICESTOP HEATING CABLES