WARNING: Reusing the grommet or using the wrong grommet can cause leaks, cracked components, shock, or fire.
Be sure the grommet you select is correct for the heating cable you plan to install. Use a new grommet whenever the
heating cable has been pulled out of the termination.
General Instructions
• The HAK-C-100 connection kit is for use only with the following heating cables: BTV, HBTV, QTVR, HQTV, XTV, HXTV, LBTV2,
FHP and VPL (-CT versions). Do not use this kit with any other heating cables.
• Select correct grommet from table on right. The grommet I.D. letter is embossed on each grommet.
Heating Cable
for FM Only
Grommet
5HBTV1-CT
B
5HBTV2-CT
B
8HBTV-1-CT
E
8HBTV-2-CT
E
10HBTV1-CT
E
10HBTV2-CT
E
12HQTV1-CT
C
12HQTV2-CT
C
20HQTV1-CT
E
20HQTV2-CT
E
5HXTV1-CT
R
5HXTV2-CT
R
10HXTV1-CT
R
10HXTV2-CT
R
Heating Cable
for FM Only
Grommet
15HXTV1-CT
R
15HXTV2-CT
R
20HXTV1-CT
R
20HXTV2-CT
R
FHP-2
E
FHP-3
C
5BTV1-CT
B
5BTV2-CT
B
8BTV-1-CT
E
8BTV-2-CT
E
10BTV1-CT
E
10BTV2-CT
E
10QTVR1-CT C
C
10QTVR2-CT C
C
Heating Cable
for FM Only
Grommet
20QTVR1-CT
E
20QTVR2-CT
E
All XTV1-CT-T3
R
All XTV2-CT-T3
R
All XTV1-CT-T2
R
All XTV2-CT-T2
R
All VPL1-CT
R
All VPL2-CT
R
LBTV2-CT
K
GROMMET SELECTION
1
3
4
2
Inserts
Cut
• Fasten the RAYCHEM universal mounting bracket (UMB)
or suitable mounting plate for another junction box to
the pipe at the desired location. Be sure the pipe strap
is under the heating cable.
• Mount box on bracket.
• Thread male half of union into box entry.
• Assemble union halves together.
• Thread compression gland with threaded inserts into
fitting until tight.
• Thread nipple into female half of union until tight.
• Thread nipple into sealing fitting until tight.
• Measure flex tube and cut to length from gland to
pipe.