DESCRIPTION

The nVent RAYCHEM RayClic-LE Lighted End Seal Kit is for use 

with nVent RAYCHEM IceStop, XL-Trace and HWAT heating 

cables. The connection is designed to be installed above the 

pipe insulation or mounted on the wall at the end of the heating 

cable circuit. These installation instructions should be used 

in conjunction with the IceStop, XL-Trace and HWAT System 

Installation and Operation Manuals. 
For technical support contact your nVent representative or call 

nVent (800) 545‑6258.

TOOLS REQUIRED

•  Utility knife 

•  Wire cutters

• TORX

®

 T20 screw driver

OPTIONAL ACCESSORIES (Not included in this kit):

•  nVent RAYCHEM RayClic‑SB‑02 Wall mounting bracket

KIT CONTENTS

Item Qty  Description

Lighted end seal

Pipe mounting bracket

Plastic cable ties

D 1 Clip

Cable lubricant

A

B

C

D

E

APPROVALS

718K Pipe Heating Cable 

877Z De-Icing and Snow Melting

Not UL Listed with XL-Trace heating 

cable for buried piping.

APPROVED

-w

For HWAT, IceStop, and XL-Trace only

Hazardous Locations: For IceStop (GM-XT) only

Class I, Div. 2, Groups A,B,C,D

RayClic Connection System

RayClic-LE Lighted End Seal Kit Installation Instructions

This component is an electrical device that must be 

installed correctly to ensure proper operation and to 

prevent shock or fire. Read these important warnings and 

carefully follow all the installation instructions.
•  To minimize the danger of fire from sustained electrical 

arcing if the heating cable is damaged or improperly 

installed, and to comply with the requirements of nVent, 

agency certifications, and national electrical codes, 

ground-fault equipment protection must be used. Arcing 

may not be stopped by conventional circuit breakers.

•  Bus wires will short if they contact each other. Keep bus 

wires separated.

•  Keep components and heating cable ends dry before 

and during installation.

•  The black heating cable core is conductive and can 

short. It must be properly insulated and kept dry.

•  Component approvals and performance are based 

on the use of nVent-specified parts only. Do not use 

substitute parts or vinyl electrical tape.

•  Leave these instructions with end user for reference 

and future use.

WARNING:

Summary of Contents for RAYCHEM

Page 1: ... Cable 877Z De Icing and Snow Melting Not UL Listed with XL Trace heating cable for buried piping APPROVED w For HWAT IceStop and XL Trace only Hazardous Locations For IceStop GM XT only Class I Div 2 Groups A B C D RayClic Connection System RayClic LE Lighted End Seal Kit Installation Instructions This component is an electrical device that must be installed correctly to ensure proper operation a...

Page 2: ...enough extra heating cable to make service loops as required Make sure end of heating cable is cut clean Remove the outer jacket Place metal clip over the base of exposed braid For the RayClic LE lighted end seal fold up the four outer snaps then position the connector over the snaps and press down Score around and down the outer jacket of the heating cable 3 1 8 inches from the end If you experie...

Page 3: ...nsert prepared heating cable end into connector Push until heating cable is fully inserted and end is visible through opening in connection cover plate Note RayClic connection kits are designed to be installed only once the heating cable cannot be removed once installed IceStop and XL Trace 6A HWAT Only Using wire cutters cut away 1 inch of the braid Pull exposed braid back over metal clip Using w...

Page 4: ...ailed in steps 3 through 9 pages 2 4 Close the lid and snap the lever shut Do not force lid closed if lid does not close check the connection to ensure all screws are fully tightened Tighten the nuts on the heating cable entries until grommets are compressed Position attachment clips on mounting bracket as shown Attach the connector to the mounting bracket by pressing until it snaps in place Compl...

Page 5: ...g cables Braid clip does not fit Be sure the clip is installed on the metal braid not on the outer jacket Heating cable does not have aluminum wrap Only HWAT heating cables have the aluminum wrap under the braid Skip the aluminum wrap removal step for XL Trace and IceStop heating cables Heating cable cannot be inserted into connector Check for the following Apply lubricant to heating cable primary...

Page 6: ...8 Fax 86 21 5426 3167 cn thermal info nvent com Latin America Tel 1 713 868 4800 Fax 1 713 868 2333 thermal info nvent com 2018 nVent All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates All other trademarks are the property of their respective owners nVent reserves the right to change specifications without notice Raychem IM H58082 RayClicLE EN 1805 PN P0000008...