20|
LA VIDA OPERATING MANUAL
NW Explorations
5.1.1
Generators
There are two generators on La Vida in the generator
room. To port is a Northern Lights 16kW. To starboard
is a Northern Lights 20kW. Both are well sound insulated
and are very quiet to not be noticeable from the cabins.
For most cruising needs, you should only need to run one
generator or just the inverter. If you are running a heavy
load, you will want to start the second generator if the
total load is > 70% of the generator. You can estimate
the load in kW with the following formula:
kW load=(110V Amps + 2x the 220V Amps) / 10
For example: If the 110V system is using 50 Amps, and
the 220V system is using 25 Amps, you are using ( 50 + (2
x 25) ) /10 = 10kW, which is fine on either generator.
5.1.2
Shorepower
The aft shorepower connectors are two Glendinning Cable Masters to port of the cockpit steps.
The forward shorepower connectors are on the starboard side of the bridge. The shorepower
panel lets you set shorepower System 1 and System 2 to be the forward or aft connectors
depending on which one is in use. The Cablemaster breaker should be on and the switch to deploy
and retrieve the shore cable is in the side, port cabinet in the aft cockpit.
5.1.3
Inverter
The inverter is a Victron Multiplus 24/3000/70 3kw Inverter / 70Amp Charger located behind the
stairs down to the guest cabins. The control panel, is a touch screen on the right end of pilot
house overhead instrument panel.