Installation of a hardwired model:

 

 

The installation of the hardwired power conditioner must only be performed by a 

qualified electrician.  All local electrical codes must be followed.   

Locate the power conditioner as close to the load equipment (the equipment you want to power 

from the power conditioner) as possible

. Ensure the circuit that will be used to power the 

power conditioner is turned off and locked out.

   Using a Phillips screwdriver remove the 

cover to the power conditioner.  Once the cover is removed locate the input and output terminal 

block on the back panel of the unit.  These terminal blocks can be accessed for wiring by 

removing the knockout covers located on the back panel.   The maximum input and output 

current for each unit can be found on the rating label on the rear of the unit.  The correctly rated 

circuit and wire size must be used per the local code for connection into and out of the unit.  The 

terminal block must be torqued down to 1.33 foot-pounds during installation.  Reference FIG 1. 

for connection diagram.   
Once all the connections are made and tight inside the power conditioner reattach the cover.  

You can now turn on the circuit that will power the power conditioner.  All hard-wired power 

conditioners have an input circuit breaker located on the rear of the unit. Turn the switch to the 

ON

 position.  The blue power 

ON

 indicator (light) on the front of the unit will illuminate. Now you 

can turn on the load equipment/electronic devices. If you have any questions in this regard, 

contact the seller.   
 

 

All 

NXT POWER 

Conditioners are equipped with overload protection and this protection will turn 

off the power conditioner if overloaded.  If the power conditioner turns off due to an overload, 

remove some of the load equipment/electronic devices from the conditioner and turn the power 

conditioner on again.   
 

 

  All power conditioner uses a basic type insulation, and a grounded power network must 

be used.  

  There are no user serviceable parts inside the power conditioner, contact the seller for 

service or repair. 

  All power conditioners use hazardous voltage. 

  All power conditioners should only be used in ordinary locations. 

  All Power conditioners can be operated in continuous duty cycle.  

CAUTION 

DANGER 

RISK OF ELECTRIC SHOCK 

Summary of Contents for NPT2000-H-NS

Page 1: ...p Model Numbers for 208 or 240 VAC in 208 240 120 out 60Hz NPT 2000 2300 2500 2800 3000 3300 3500 3800 5000 5800 6000 7000 POWER CONDITIONER USER S MANUAL For use with 208 or 240 VAC 60 Hz systems...

Page 2: ...1 TABLE OF CONTENTS 1 0 INTRODUCTION 2 2 0 SAFETY GUIDELINES 2 3 0 OPERATION MAINTENANCE 3 4 0 POWER CONDITIONER RATINGS CHART 6 4 1 FIG 1 7 5 0 WARRANTY 8 6 0 CONTACT US 9...

Page 3: ...you have any additional questions after reviewing this manual please feel free to contact our technical support team by phone 888 NXT POWR or email us at service nxtpower com 2 0 SAFETY GUIDELINES Sy...

Page 4: ...conditioner is not overloaded This can be done by making sure the power conditioner is not loaded above its maximum rating please see back panel of the unit for rating information If you have any ques...

Page 5: ...oner input voltage is configured to match the supply voltage Power conditioner and load equipment can be damaged if the voltage is not configured correctly If you have any questions regarding voltage...

Page 6: ...ction diagram Once all the connections are made and tight inside the power conditioner reattach the cover You can now turn on the circuit that will power the power conditioner All hard wired power con...

Page 7: ...S 208 or 240 VAC 240 120 VAC 12 0 A 15 A 14 AWG 60 Hz NPT3000 H NS 208 or 240 VAC 208 240 120 VAC 14 4 A 20 A 12 AWG 60 Hz NPT3300 H NS 208 or 240 VAC 208 240 120 VAC 16 0 A 20 A 12 AWG 60 Hz NPT3500...

Page 8: ...s not cover any losses or damage resulting from shipment to or from the Customer or from improper installation improper application inappropriate environment abuse neglect unauthorized modifications a...

Page 9: ...ghts IL 60706 P 877 698 7697 F 708 457 2266 E service nxtpower com 022 00002 2020 REV A User manual power conditioner 2000 VA to 70000 VA 208 240 120 VAC Access additional product and support via our...