41
Specifications Convertible Type (Rack)
ITEM
PART
NXT Ares Plus with Transformer RT 120V
Type
PF=0.9
NPTU800-OR-N NPTU1100-OR-N NPTU1500-OR-N
Capacity
VA / W
800VA / 720W
1100VA / 990W
1440VA / 1296W
Battery Number
3
Input
Voltage Rating
55-150 V
AC
(90-150 V
AC
: 0 ~ 100% Load / 75-90 V
AC
: 0 ~
75% Load / 50-75 V
AC
: 0 ~ 60% Load)
Frequency Rating
44-66 Hz (Auto Sensing)
Phase
Single phase with ground
Power Factor
≧
0.98 (Nominal voltage for 100% linear load)
Total Harmonic
Distortion
I
THD
< 7% (Nominal voltage with >1% V
THD
for 100% linear
load)
Input Connection
NEMA 5-15P
Output
Output Voltage
120V
AC
/ 100 V
AC
*
100V
AC
:
666VA/599W
120V
AC
/ 100V
AC
*
100V
AC
:
916VA/824W
120V
AC
/ 100V
AC
*
100V
AC
:
1200VA / 1080W
Voltage Regulation
within ± 2% until low-battery warning
Frequency
(Synchronized
Range)
3 Hz or 1 Hz (selectable)
Frequency (Battery
Mode)
50/60 Hz ±0.1
Current Crest Ratio
3:1
Total Harmonic
Distortion
Linear Load: V
THD
≦
3.5%
PF=0.9 Non-Linear Load: V
THD
≦
5%
PF=0.7 Non-Linear Load: V
THD
≦
9%
Output Waveform
Pure sine wave
Outlets
(3+3) NEMA 5-15R (programmable)
Overload
Capacity
Line Mode
<
105
%
continuous
106-120
%
for 30 seconds transfer to bypass
121-150
%
for 10 seconds transfer to bypass
>
150
%
Immediately transfer to bypass.
Buzzer continuously alarms.
Battery
Mode
<
105
%
continuous
106-120
%
for 30 seconds shuts down
121-150
%
for 10 seconds shuts down
>
150
%
Immediately shuts down.
Buzzer continuously alarms.
Bypass
Mode
<
105
%
continuous
106-120
%
for 250 seconds shuts down
121-130
%
for 125 seconds shuts down
131-135
%
for 50 seconds shuts down
136-145
%
for 20 seconds shuts down
146-148
%
for 5 seconds shuts down