System instructions OBO isCon
®
EN | 31
Installing the isCon system
5 2
Mounting the isCon connect connection element
Using the screw-on connection element isCon connect, you can con-
nect OBO isCon cables to forwarding systems, e.g. to the insulated OBO
isFang interception rod system or to a separate ring cable or earthing sys-
tem using a connection terminal. At the same time, an electrical connec-
tion is created between the copper core and the black, weakly-conductive
external jacket of the isCon cable.
Scope of delivery (per packaging unit): 2 connection elements, 2 heat-
shrinkable sleeves, screw lock varnish, Allen key.
• Remove the two pin screws from the connection element using the
Allen key.
Figure 22:
Removing the pin screws
• Free the front area of the black jacket from impurities and grease us-
ing a cleaning cloth ( e. g. OBO Art. No. 5408 060).
isCon EPPA 004
Figure 23:
Using a cleaning cloth