Testing report for the OBO isCon system
8 Testing report for the OBO isCon system
Tested building:
Last name
Contact
Street/No.
Postcode/town
Telephone
1. Were all the connection elements installed correctly according to the mounting instructions?
2. Is the entire routed OBO isCon cable in the protected area of the interception system?
3. Is the black external jacket of the cable free of damage/cracks?
4. Was the separation distance calculated for the location to be protected according to VDE 0185-
305-3?
5. Is the equivalent separation distance of s ≤ 0.75 m in air, s ≤ 1.5 m for solid material maintained?
6. Is the separation distance maintained in the area between the connection element and the first
potential connection of the OBO isCon cable?
7. Is the potential connection connected to the local equipotential bonding of the system to be pro-
tected using isCon-PAE with a cable of at least 6 mm
2
?
8. Is the minimum bend radius of 345 mm for the black cable and 390 mm for the grey cable main-
tained?
9. With a stand-off installation, is the separation distance to the roof area maintained in the area up to
the first equipotential bonding clip?
10. Is the area up to the first equipotential bonding clip (distance of the calculated separation distance
to the cable) free of metallic parts/cable brackets, etc.?
Only if all the questions were answered with "Yes" are the requirements of the manufacturer for installation fulfilled.
Tester
Place/date
Signature